Datasheet

Technical data
Dimensions Width Length Height NS 35/7,5
[mm] 23 130 65.5 10 85 - 10 85 -
Max. electrical data I
max.
[A] U
max.
[V] Max. Ø [mm²] AWG (UL)
32
1
) 1500
2
) 0.75 - 25 - 1500 - - 1200 - -
IEC 60269-1/-2
Rated data IEC UL CSA IEC/
EN60079-7
Rated voltage [V] 1500
2
) - - - 1500 - - - 1200 - - -
Nominal current / cross section [A] / [mm²] 32
1
) / 16--- ---- ----
Rated cross section [mm²]25--- ---- ----
Cross section range AWG18 - 3--- ---- ----
Connection capacity Solid Stranded Ferrule
without/with plastic sleeve
1 conductor [mm²] 1.5 - 25 0.75 - 25 1.5 - 16 1.5 - 16 - - - - - - - -
2 conductors (of the same type) [mm²] 1.5 - 4 0.75 - 10 1.5 - 4 - - - - - - - - -
2 stranded conductors with a TWIN ferrule [mm²] - - - 1.5 - 10 - - - - - - - -
General data
Fuse type / dimensions – / [mm] gG / gPV / 10.3 x 85
Stripping length [mm] 11
Screw thread M5
Tightening torque [Nm] 2.5 - 2.5
Insulating material PA
Ordering data
Description Color Type Order No.
Pcs. /
Pkt.
Fuse terminal block, for mounting on NS35..., for
10 x 85 mm cartridge fuse inserts
black UK 10,3-HESI 1500V 3062760 5
Midget fuse, 10.3x85mm, 1500V, nominal
current:2A
white
Nominal current: 4A white
Nominal current: 6A white
Nominal current: 8A white
Nominal current: 10 A white
Nominal current: 12 A white
Nominal current: 16 A white
Midget fuse, 10.3x85mm, 1200V, nominal
current:20A
white
Nominal current: 25 A white
Accessories
Partition plate, 2mm wide gray TPN-UK 3003062 10
Screwdriver SF-SL 0,6X3,5-100 S-VDE 1212587 10
Center groove marking EML (16,5X5)R (see Catalog 5)
406
PHOENIX CONTACT
UK screw connection - lever-type fuse
terminal block for photovoltaics,
1500V
Notes:
The rated voltage is 1250V and the maximum operating
voltage is 1500V.
Higher ambient temperatures are an additional strain on fuse
inserts. In applications of this kind, the shift of the rated current
should be taken into consideration accordingly.
For tools for stripping and crimping solar cables and connectors,
see Catalog 5.
For detailed information on applications and power dissipation
data, see phoenixcontact.net/products
1
) The current and voltage are determined by the fuse.
2
) Maximum operating voltage 1500V.
Fuse terminal block
Terminal block for protecting PV strings
Particularly suitable for protecting
monocrystalline and polycrystalline
modules
Suitable for standard 10.3x85mm fuse
inserts with gPV characteristic
Electric strength up to 1500VDC
Generous marking options for the unique
identification of lines
Fuses
Special fuses with ultra-rapid PV
characteristic (gPV)
Use in PV strings with a nominal voltage
of up to 1500VDC
Safe shutdown even in the event of short-
circuit currents that are just above the
nominal current
Diode terminal blocks
For diode terminal blocks for protecting
PV strings, see page 144
Terminal blocks
UK universal terminal blocks
25 (25) mm², 32 A, 1500 V, lever-type fuse
terminal block