Datasheet

For further information and full technical data, visit phoenixcontact.net/products
Technical data
1
) Technical data
1
)
Dimensions Width Length Height Width Length Height
[mm] 10.2 71.5 50.3 (NS 35/7,5) 10.2 97 50.3 (NS 35/7,5)
Max. electrical data I
max.
[A] U
max.
[V] max. Ø [mm²] AWG (UL) I
max.
[A] U
max.
[V] max. Ø [mm²] AWG (UL)
65 1000 0.2 - 16 16-6 70 1000 0.2 - 16 16-6
Max. bridge current [A] 57 57
Rated data IEC UL / CUL CSA Ex IEC UL / CUL CSA Ex
Rated voltage [V] 1000 600 600 550 1000 600 600 -
Nominal current / cross section [A] / [mm²] 57 / 10 65 / - 65 / - 50 / 10 57 / 10 55 / - 55 -
Ordering data Ordering data
Description Color Type Order No.
Pcs. /
Pkt.
Type Order No.
Pcs. /
Pkt.
Terminal block gray ST 10 3036110 50 ST 10-TWIN 3035288 25
blue ST 10 BU 3036123 50 ST 10-TWIN BU 3035292 25
Ground terminal green-yellow ST 10-PE 3036136 50 ST 10-TWIN-PE 3035302 25
Accessories
1
) Accessories
1
)
Cover, width 2.2 mm gray D-ST 10 3036644 50 D-ST 10-TWIN 3035315 50
Terminal blocks - CLIPLINE complete
10 mm ST... spring-cage connection terminal blocks
65 A, feed-through terminal block 70A, feed-through terminal block,
3 connections
Ex:

KEMA 01ATEX2260 U / IECEx KEM 06.0033U
①①
Feed-through and multi-conductor
terminal blocks and ground terminals
Notes:
1
) For additional accessories and technical data, see page 200.
For information on installation and using accessories for Ex
applications, see page 602.
Technical data
1
) Technical data
1
)
Dimensions Width Length Height Width Length Height
[mm] 10 87 49 (NS 35/7,5) 10 87 50 (NS 35/7,5)
Max. electrical data I
max.
[A] U
max.
[V] max. Ø [mm²] AWG (UL) I
max.
[A] U
max.
[V] max. Ø [mm²] AWG (UL)
57 400 0.2 - 16 - 57 400 0.2 - 16 -
Max. bridge current [A] 57 57
Rated data IEC UL / CUL CSA Ex IEC UL / CUL CSA Ex
Rated voltage [V] 400 - - - 400 - - -
Nominal current / cross section [A] / [mm²] 57 / 10 - - - 57 / 10 - - -
Ordering data Ordering data
Description Color Type Order No.
Pcs. /
Pkt.
Type Order No.
Pcs. /
Pkt.
Terminal block gray STI 10 3038215 25
blue STI 10 BU 3038228 25
Neutral disconnect terminal block blue STN 10 3038244 25
Ground terminal green-yellow STI 10-PE 3038231 25
Accessories
1
) Accessories
1
)
Cover, width 2 mm gray D-STI 10/16 3038309 25 D-STI 10/16 3038309 25
Support bracket, to hold the neutral busbar, set
every 20 cm, 2 mm wide
blue AB-STI 16/10 3037669 10 AB-STI 16/10 3037669 10
201
PHOENIX CONTACT
57 A, feed-through terminal block 57 A, neutral disconnect terminal block

①①
Installation terminal blocks
Notes:
1
) For additional accessories and technical data, see page 200.
Assembly instruction:
In order to securely fix the neutral busbar in place, support
brackets must be placed at the beginning and end of each terminal
strip as well as every 20cm on longer terminal strips.
The corresponding support brackets can be found at
phoenixcontact.net/products