Datasheet

https://www.phoenixcontact.com/us/produkte/5603258
Nov 13, 20131/3
Passive module-UM-DELTAV/A/SI/BFI/TP-5603258
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in
the user's documentation. Our General Terms of Use for Downloads are valid
(http://download.phoenixcontact.com)
Fuse module with separable test sockets, fuse failure display and shield connection terminals (for
analog cards of the Delta V control system)
Product Features
These system-specific interface modules for DeltaV modules are used in combination with the relevant system cables
Key commercial data
package_quantity
1
GTIN
4017918955038
Technical data
Dimensions
Width
61 mm
Height
126 mm
Depth
71 mm
Ambient conditions
Ambient temperature (operation)
-20 °C ... 50 °C
Ambient temperature (storage/transport)
-20 °C ... 70 °C
General
Nominal voltage U
N
24 V DC
Max. current carrying capacity per branch
50 mA (in as-supplied state, with one 50 mAF fuse, max. 1 A
permitted)
Number of positions
16
Test voltage
500 V (50 Hz, 1 min.)
Mounting position
Any
Standards/regulations
IEC 60664
Standards/regulations
DIN EN 50178
Standards/regulations
IEC 62103
Connection data for connection 1
Connection name
Field level
Connection method
Screw connection

Summary of content (3 pages)