User Manual

ILB BT ADIO MUX...
Preliminary Preliminary Preliminary Preliminary
7173_en_11 PHOENIX CONTACT 11 / 18
6 Local diagnostic and status
indicators
Figure 1 Diagnostic and status indicators
7 Connect supply, actuators, and
sensors
Figure 2 Connecting cables
Strip 8 mm off the cables.
Secure the cable by removing the screwdriver.
LED Color Meaning
PWR
UA Green 24 V actuator supply
UL Green 24 V communications power
OUT
E Red Short circuit/overload at one of the
outputs
1 ... 16 Yellow Status of the outputs
IN
1 ... 16 Yellow Status of the inputs
FS
FS Red Wireless connection interrupted,
analog and digital outputs set to 0
LINK QUALITY
LQ Green Link quality (bit error rate)
4 LEDs 0%...0,05%
3 LEDs 0,05%...1%
2 LEDs 0.1%...1.7%
1 LED >1.7%
OFF No connection established
If the error LED of a group of 16outputs lights
up (e.g.,connector 2 and 3), this indicates
that a short circuit or overload is present at
one or more of the outputs in this group.
DI16
16
DO
AO2
AI2
QUA
LITY
LIN
K
UA
UL
P
W
R
1
FS
BLUETOOTH
UA
UL
PWR1
1
2
5
DO
16
DO
16
6
9
10
13
14
E
E
4
12
3
11
8
16
7
15
1
2
5 6
9
10
13
14
4
12
3
11
8
16
7
15
D16ID16I
FS
AO2
AI2
LINK
QUALITY
LINK
QUALITY
CAUTION: Electric shock
The device is only intended for operation with
SELV according to IEC 60950/EN 60950/VDE
0805.
A
B