7.1 Terminal point assignment
Figure 3 Terminal point assignment
The feeding points have the same ground potential. All
ground supplies on a device are electrically connected with
one another.
The communications power is also electrically connected
via all contacts. In this way, it can supply all potentials with
just one feed-in, without the need for additional terminals.
Power plug
Digital output and input connectors
Analog output connector
Analog input connector
NOTE: device damage
The terminal points for GND and U
L
can have
a total current of 8A per terminal point. Make
sure that this value is not exceeded.
Terminal point Assignment
Connector 1: PWR
1.1, 2.1 24 V actuator supply
1.2, 2.2 24 V communications power
1.3, 2.3 GND
1.4, 2.4 FE
Connector 2: OUT1 Connector 3: OUT2 Connector 4: IN1 Connector 5: IN2
1.1 O1 2.1 O2 1.1 O9 2.1 O10 1.1 I1 2.1 I2 1.1 I9 2.1 I10
1.2 O3 2.2 O4 1.2 O11 2.2 O12 1.2 I3 2.2 I4 1.2 I11 2.2 I12
1.3 O5 2.3 O6 1.3 O13 2.3 O14 1.3 I5 2.3 I6 1.3 I13 2.3 I14
1.4 O7 2.4 O8 1.4 O15 2.4 O16 1.4 I7 2.4 I8 1.4 I15 2.4 I16
Connector 6: Analog OUT
1.1 +U1 Channel 1 voltage output 2.1 +U2 Channel 2 voltage output
1.2 +I1 Current output channel 1 2.2 +I2 Current output channel 2
1.3 AGND Analog ground 2.3 AGND Analog ground
1.4 Shield connection 2.4 Shield connection
Connector 7: Analog IN
1.1 +U1 Voltage input, channel 1 2.1 +U2 Voltage input, channel 2
1.2 +I1 Current input, channel 1 2.2 +I2 Current input, channel 2
1.3 AGND Analog ground 2.3 AGND Analog ground
1.4 Shield connection 2.4 Shield connection