User manual

FL SWITCH LM
3-46
PHOENIX CONTACT 7278_en_01
flWorkFWCtrlTrapDestCapacityMax
flWorkFWCtrlTrapDestEnable
flWorkFWCtrlPasswd
OID 1.3.6.1.4.1.4346.11.11.11.2.3
flWorkFWCtrlPasswdSet
OID 1.3.6.1.4.1.4346.11.11.11.2.2.1.1.2
Syntax IP address
Access Read/write
Description Contains the IP address of the target component, which should receive the traps.
OID 1.3.6.1.4.1.4346.11.11.11.2.2.2
Syntax Integer32
Access Read
Description Contains the maximum permissible number of trap receivers.
OID 1.3.6.1.4.1.4346.11.11.11.2.2.3
Syntax Integer
Access Read/write
Description This object can be used to disable the "send SNMP traps" function:
Sending permitted 2
Sending not permitted 1
OID 1.3.6.1.4.1.4346.11.11.11.2.3.1
Syntax Octet string (2 - 24)
Access Read/write
Description A new password can be entered here with a maximum of 12 characters. Example:
- Your new password should be "factory3".
- The password must be entered a second time for confirmation.
- Your entry "factory3factory3".
- Your password for write access is now: "factory3".
For security reasons, the response is always "*****" for read access.