User Manual

PSEN cs1.1p
Operating Manual PSEN cs1.1p
21095-EN-08
9
} S
o
: Typical operating distance: 21 mm
} S
r
: Typical release distance: 32 mm
} S
ar
: Assured release distance: 40 mm
Lateral and vertical offset
Lateral offset Vertical offset
[1]
[2]
[3]
[4] [4]
[5]
[6]
Power / Fault
Safety Gate
Input
[4]
[4]
Legend:
} [1]: Hysteresis
} [2]: Typical operating distance S
O
} [3]: Typical release distance S
r
} [4]: Offset in mm
} [5]: Operating distance in mm
} [6]: Response range
Wiring
Please note:
} Information given in the Technical details [ 18] must be followed.
} The max. cable length l
max
in the input circuit is calculated from
the max. cable capacitance at the safety outputs (see Technical data [ 18]).
the minimum permitted supply voltage at the sensor (19.2 V).
} The power supply must meet the regulations for extra low voltages with protective sep-
aration (SELV, PELV).