User Manual

PSEN cs2.1p
Operating Manual PSEN cs2.1p
1003268-EN-07
14
PNOZmulti
I2
I0
I1
grün
grau
gelb
PNOZmulti PSENcode
A1
A2
Y32
n.c.
S11
S21
12
22
2
7
8
6
1
3
4
5
A1
A2
0 V
24 V
Legend:
I0 Input OSSD
I1 Input OSSD
I2 Signal input
Teaching in the actuator
Teaching in the actuator for the first time:
The first actuator PSEN cs2.1 detected by the safety switch is automatically taught in as
soon as it is brought into the response range.
To teach in a new actuator:
} A maximum of 8 learning procedures are possible.
1. The actuator that is to be taught in must be brought into the safety switch's response
range as the only transponder. As soon as the actuator is detected, the "Safety Gate"
LED will flash yellow.
2. After 20 s has elapsed, the "Safety Gate" LED turns to quick yellow flashes. Trigger a
system reset in the next 120 s by interrupting the power supply.
3. When the supply voltage is switched back on, the learning procedure is complete and
the number of permitted additional learning procedures is reduced by 1.
NOTICE
The actuator must not be removed during the learning procedure.
This actuator cannot be retaught on the same safety switch.