Preface This document is a translation of the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal purposes. Suggestions and comments for improving this documentation will be gratefully received. Pilz®, PIT®, PMI®, PNOZ®, Primo®, PSEN®, PSS®, PVIS®, SafetyBUS p®, SafetyEYE®, SafetyNET p®, the spirit of safety® are registered and protected trademarks of Pilz GmbH & Co. KG in some countries.
Content Section 1 Introduction 1.1 Validity of documentation 1.2 Using the documentation 1.3 Definition of symbols 5 5 5 5 Section 2 Safety 2.1 2.2 2.2.1 2.2.2 2.2.3 2.3 7 7 7 7 8 8 8 Intended use Safety regulations Use of qualified personnel Warranty and liability Disposal For your safety Section 3 Unit features 9 Section 4 Block diagram 10 Section 5 Function description 11 Section 6 Installation 14 Section 7 Commissioning 7.1 Wiring 7.2 Connection 7.3 Application 7.3.
Content Section 8 Operation 8.1 Status messages 8.1.
Introduction 1 Introduction 1.1 Validity of documentation This documentation is valid for the true power converter PMD s10 from Version 2.0. It is valid until new documentation is published. This operating manual explains the function and operation, describes the installation and provides guidelines on how to connect the product. 1.2 Using the documentation This document is intended for instruction. Only install and commission the product if you have read and understood this document.
Introduction INFORMATION This gives advice on applications and provides information on special fea tures.
Safety 2 Safety 2.1 Intended use The true power converter PMD s10 used to measure and monitor the rated power or true power on electrical consumers.
Safety 2.2.2 Warranty and liability All claims to warranty and liability will be rendered invalid if 2.2.3 } The product was used contrary to the purpose for which it is intended } Damage can be attributed to not having followed the guidelines in the manual } Operating personnel are not suitably qualified } Any type of modification has been made (e.g. exchanging components on the PCB boards, soldering work etc.). Disposal } 2.
Unit features 3 Unit features } Relay outputs: – 2 auxiliary changeover contacts (C/O) } Analogue output for current and voltage } Galvanic isolation of analogue outputs } Automatic measuring range is set automatically for current and voltage } The following unit parameter settings are menudriven and infinitely variable via a dis play and rotary knob with key function (turn and push): – Maximum true power } – Switching threshold for underload and overload – Warning threshold – Monitoring
Block diagram 4 Block diagram *Insulation between the nonmarked area and the relay contacts: Basic insulation (over voltage category III), Protective separation (overvoltage category II) Operating Manual PMD s10 22092EN04 10
Function description 5 Function description The PMD s10 monitors the set upper and lower true power limit on a single or three phase supply or on the DC supply. The unit operates in accordance with the principle of Aron cir cuit. } Relay outputs (K1 and K2): K1 and K2 operate in normally energised mode. In their default state, auxiliary contacts 1114 and 2124 are closed and auxiliary contacts 1112 and 2122 are open. Normally energised mode is the default setting.
Function description Function diagram 1 Hysteresis Hysteresis tstart tstart tstart tstart Legend } P: Actual true power } tstart: Startup suppression time } tr: Reaction time Operating Manual PMD s10 22092EN04 12
Function description Function diagram 2 at Generator operation Motor operation Legend } P: Actual true power } U/I: Analogue output signal INFORMATION Measuring range limit value Pmax (selectable) When simultaneously using an external current and an external voltage transformer, the selectable measuring range limit value is calculated from the following formula: Pmax = (1.0 W … 11.5 kW) x CT x VT Examples: 1. Current transformer CT 100 : 1 and no voltage transformer VT 1 : 1 Pmax = (1.0 W … 11.
Installation 6 Installation } The unit should be installed in a control cabinet with a protection type of at least IP54. } Use the notch on the rear of the unit to attach it to a mounting rail. } In environments exposed to heavy vibration or when installing on a vertical mounting rail (35 mm), the unit should be secured using a fixing element (e.g. retaining bracket or end angle). } Push the unit upwards or downwards before lifting it from the mounting rail.
Commissioning 7 Commissioning 7.1 Wiring Please note: } Only wire the unit when the supply voltage is switched off! } Use copper wiring. } To prevent contact welding, a fuse should be connected before the output contacts (see Technical details [ 31]). } Ensure that the cables are laid carefully, because an open circuit in the measuring cir cuit will cause the unit to malfunction. } Information given in the Technical details [ 31] must be followed.
Commissioning With continuous currents of > 12 A the measuri8ng current has to be measured via an ex ternal current transformer. With voltage > 500 V the voltage has to be measured via an ex ternal voltage transformer. 7.3.
Commissioning 7.3.
Commissioning 7.3.
Commissioning 7.3.4 Circuit for motor (1 AC) with CT L1 N 24V 0V K k L2 L1 L3 K3 W/I3 K1 U/I1 L l PMD s10 Reset extern K1 U2 U1 Y1 Y2 U I 0V 11 12 14 A1 21 22 24 A2 K1 H2 A M1 IN > 12A M1~ V PE 7.4 Read and set parameters Some settings are required in the unit's menu in order to operate the unit. Before you start, make sure you know how to read values from the display and use the rotary knob to set parameters (see Sample configuration [ 28]). 7.
Commissioning – Press the knob downwards [2] while keeping the bar pressed in [2] [1] Rotate and press the knob Rotate } Select menu item } Set the parameter/numeric value with the following rotational speed: – Slowly: Units – Quickly: Tens – Very quickly: Hundreds Press 7.5.2 } Confirm selection/setting } Switch to menu Display Display Meaning > Value can be set Power P Parameter name ....
Commissioning INFORMATION If you operate the unit without a chip card, the "Fault" LED will light and the following message will appear once only: Insert SIM Card. If you change the parameters, the Insert SIM Card message will reappear. When the chip card is inside the unit, 7.5.3.1 } the chip card is checked to verify the device identifier and ensure that the data is identical. } Unit parameters are automatically saved to the chip card during operation.
Commissioning 7.5.3.2 Write data to chip card If you are inserting a chip card which has not yet been written by a PMD s10, you have the option to: Allow data to be written to the chip card Insert chip card 1. > select Insert SIM Card Write SIM? no 2. Write SIM? yes Data is written to the chip card Power P …. Do not allow data to be written to the chip card Insert chip card 1. Insert SIM Card 7.5.3.
Commissioning } Confirm the message Load SIM yes?. The data is transferred. INFORMATION Note that device parameters with data from device version 2.0 cannot be transferred to a unit with version 1.0. In this case the message appears Write SIM no? 7.5.4 Menu overview 7.5.4.1 "Settings" menu and submenu 7.5.4.2 } Constant display parameter, to be shown on the display during operation } Measuring range limit value (Pmax) Maximum true power of the load.
Commissioning 7.5.4.3 } External output Ext. CT) Transmission ratio of the external current transformer; if there is no external current transformer set 1 : 1 } External voltage transformer (ext.
Commissioning 7.5.4.4 "Settings", "Advanced Settings" and "Info" menu (schematic representation) Power P .... W Settings Display > Power P .... W > Display Escape Pmax .... kW > Pmax .... kW > Pmax Escape ... Escape > Reset auto > Reset Escape PWO ...% Pmax > PWO ...% Pmax > PWO Escape PWU ...% Pmax > PWU ...% Pmax > PWU Escape Reset auto Settings Escape Advanced Settings ... Escape Load Default > Load Def. yes? > Load Def. Esc Adv.Set. Escape Info tOperate ...
Commissioning 7.5.5 Set the parameter value Set parameters "Settings" menu Default value Parameters can be set from ... to Leave unchanged Pmax > Pmax > Pmax > Pmax 5.50 kW 1.00 W 11.5 KW Escape Po > Po > Po > Po 80 % Pmax 0% Pmax 100 % Pmax Escape Pu > Pu > Pu > Pu 20 % Pmax 0% Pmax 100 % Pmax Escape tstart > tstart > tstart > tstart 3.0 s 0.0 s 30.0 s Escape tr > tr > tr > tr 0.10 s 0.00 s 30.
Commissioning Default value Parameters can be set from ... to Leave unchanged Rel. K2 > Rel. K2 > Rel. K2 ... Pu Pu Pwo ... > Rel. K2 > Rel. K2 > Rel. K2 Pwu Pwo Pwu Escape Rel. K1 > Rel. K1 > Rel. K1 > Rel. K1 norm. on norm. on norm. off Escape Rel. K2 > Rel. K2 > Rel. K2 > Rel. K2 norm. on norm. on norm. off Escape ext. CT > ext. CT > ext. CT > ext. CT 1:1 1:1 1000 : 1 Escape ext. VT > ext. VT > ext. VT > ext.
Commissioning } Set the startup suppression time tstart: Restart the motor, monitor the output and measure the time it takes for the rated load to be displayed in normal mode. (Default setting: 3 s). Set the startup suppression time tstart so that the unit masks the startup phase. } Set the reaction time tr: Set the reaction time tr so that the unit does not react to transi ent overload or underload. } Optional settings: – Manual or automatic reset – 7.6.
Commissioning 9. > select Menue Escape 10. Power P .... 2. Set current transformer: CT 10 : 1 Power P 1. …. Settings 2. > select Advanced Settings 3. Pwo 70% Pmax 4. ext. CT 1:1 5. > ext. CT 1:1 6. > select > ext. CT 1:1 7. ext. CT 10 : 1 8. > select Advanced Settings Escape 9. Advanced Settings 10. > select Menue Escape 11. Power P ....
Operation 8 Operation 8.1 Status messages LEDs indicate the status and errors during operation: LED on LED status 8.1.
Technical details 9 Technical details General Approvals Electrical data Supply voltage Voltage Kind Voltage tolerance Output of external power supply (AC) Output of external power supply (DC) Frequency range AC Continuous duty External unit fuse protection min. External unit fuse protection F1 max.
Technical details Relay outputs Number of output contacts Auxiliary contacts (C/O) Utilisation category In accordance with the standard Utilisation category of auxiliary con tacts AC1 at Min. current Max. current Max. power DC1 at Min. current Max. current Max. power Utilisation category In accordance with the standard Utilisation category of auxiliary con tacts AC15 at Max. current DC13 (6 cycles/min) at Max.
Technical details Environmental data Ambient temperature Temperature range Storage temperature Temperature range Condensation during operation EMC Vibration In accordance with the standard Frequency Amplitude Airgap creepage In accordance with the standard Overvoltage category Pollution degree Rated insulation voltage Rated impulse withstand voltage Rated impulse withstand voltage Supply voltage, auxiliary con tacts, analogue output Protection type Mounting area (e.g.
Technical details Mechanical data Stripping length with springloaded terminals Dimensions Height Width Depth Weight 760100 761100 – 9 mm 98,0 mm 45,0 mm 120,0 mm 340 g 100,0 mm 45,0 mm 120,0 mm 370 g Where standards are undated, the 201201 latest editions shall apply.
Order reference 10 Order reference Product type Features Connection type Order no.
EC declaration of conformity 11 EC declaration of conformity This/(These) product(s) fulfil the requirements of the low voltage directive 2006/95/EG. The complete EC Declaration of Conformity is available on the Internet at www.pilz.com/down loads. Representative: Norbert Fröhlich, Pilz GmbH & Co. KG, FelixWankelStr.
Technical support is available from Pilz round the clock.