PZE X4V } Safety relays Operating Manual 1003200-EN-09
Preface This document is a translation of the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal purposes. Suggestions and comments for improving this documentation will be gratefully received. Pilz®, PIT®, PMI®, PNOZ®, Primo®, PSEN®, PSS®, PVIS®, SafetyBUS p®, SafetyEYE®, SafetyNET p®, the spirit of safety® are registered and protected trademarks of Pilz GmbH & Co. KG in some countries.
Contents Introduction Validity of documentation Using the documentation Definition of symbols 4 4 4 4 Safety Intended use Safety regulations Safety assessment Use of qualified personnel Warranty and liability Disposal For your safety 5 5 5 5 6 6 6 6 Unit features 6 Safety features 7 Block diagram/terminal configuration 7 Function description 7 Installation 8 Wiring 8 Preparing for operation 9 Operation Status indicators 9 9 Faults – Interference 10 Dimensions in mm 10 Technical deta
PZE X4V Introduction Validity of documentation This documentation is valid for the product X4V. It is valid until new documentation is published. This operating manual explains the function and operation, describes the installation and provides guidelines on how to connect the product. Using the documentation This document is intended for instruction. Only install and commission the product if you have read and understood this document. The document should be retained for future reference.
PZE X4V INFORMATION This gives advice on applications and provides information on special features. Safety Intended use El bloque de ampliación de contactos X4V cumple los requisitos de las normas EN 60947-5-1, EN 60204-1 y VDE 0113-1 y sirve como dispositivo de ampliación para el refuerzo y la multiplicación de los contactos de seguridad sin retardo de un dispositivo base. Los dispositivos base son todos los dispositivos de seguridad con supervisión de circuito de realimentación.
PZE X4V Use of qualified personnel The products may only be assembled, installed, programmed, commissioned, operated, maintained and decommissioned by competent persons. A competent person is someone who, because of their training, experience and current professional activity, has the specialist knowledge required to test, assess and operate the work equipment, devices, systems, plant and machinery in accordance with the general standards and guidelines for safety technology.
PZE X4V } See order reference for unit types Safety features The unit meets the following safety requirements: } The contact expander module expands an existing circuit. As the output relays are monitored via the base unit's feedback loop, the safety functions on the existing circuit are transferred to the contact expander module. } The safety function remains effective in the case of a component failure. } Earth fault in the feedback loop: Detected, depending on the base unit that is used.
PZE X4V } Functional procedure once the input circuit is opened (e.g. safety contacts on the base unit are opened): – The supply voltage is not present at input (A1) of the contact expansion module. – The LEDs "CH.1" and "CH.2" go out. – Safety contacts 17-18, 27-28, 37-38 and 47-48 are opened redundantly once the delay time has elapsed. NOTICE At the latest the safety contacts open after the delay time tv + 50% of the value, even in the case of a component failure.
PZE X4V Preparing for operation Supply voltage AC DC 24 V DC A1 A2 PZE 0V Input circuit Single-channel Base unit: Safety relay PNOZ X 24 V DC Driven via safety contacts Dual-channel A1 PZE A2 0V Base unit: Safety relay PNOZmulti O1 0V Driven via semiconductor outputs (24 VDC) Feedback loop A1 A2 PZE L- Base unit: Safety relay PNOZ X Base unit: Safety relay PNOZmulti Y1, Y2 and Input are inputs on the base unit; they evaluate the feedback loop Operation NOTICE The safety function shou
PZE X4V Faults – Interference By closing or interrupting the input circuit you can check whether the unit switches on or off correctly. For safety reasons, the unit cannot be started if the following faults are present: } Contact malfunction: As the contact block is connected to a base unit, reactivation will not be possible if the contacts have welded after the input circuit has opened. } Open circuit, short circuit or earth fault ( e.g.
PZE X4V Electrical data Max. inrush current impulse Current pulse, A1 Pulse duration, A1 Inputs Number Voltage at Input circuit DC Current at Input circuit DC Max. overall cable resistance Rlmax Single-channel at UB DC Relay outputs Number of output contacts Safety contacts (N/O), delayed Max. short circuit current IK Utilisation category In accordance with the standard Utilisation category of safety contacts delayed AC1 at Min. current Max. current Max. power DC1 at Min. current Max. current Max.
PZE X4V Relay outputs 774580 Utilisation category in accordance with UL 250 V AC G.U. (same poVoltage larity) With current 6A Voltage 24 V DC G. U. With current 6A Pilot Duty B300, R300 External contact fuse protection, safety contacts In accordance with the standard EN 60947-5-1 External contact fuse protection, delayed safety contacts Max.
PZE X4V Environmental data Ambient temperature Temperature range Storage temperature Temperature range Climatic suitability Humidity Condensation during operation EMC Vibration In accordance with the standard Frequency Amplitude Airgap creepage In accordance with the standard Overvoltage category Pollution degree Rated insulation voltage Rated impulse withstand voltage Protection type Mounting area (e.g.
PZE X4V Mechanical data Conductor cross section with screw terminals 1 core flexible 2 core with the same cross section, flexible with crimp connectors, no plastic sleeve 2 core with the same cross section, flexible without crimp connectors or with TWIN crimp connectors Torque setting with screw terminals Dimensions Height Width Depth Weight 774580 774581 774582 0,2 - 4 mm², 24 - 10 AWG 0,2 - 4 mm², 24 - 10 AWG 0,2 - 4 mm², 24 - 10 AWG 0,2 - 2,5 mm², 24 - 14 AWG 0,2 - 2,5 mm², 24 - 14 AWG 0,2 - 2,5
PZE X4V Inputs Max. overall cable resistance Rlmax Single-channel at UB DC Relay outputs Number of output contacts Safety contacts (N/O), delayed Max. short circuit current IK Utilisation category In accordance with the standard Utilisation category of safety contacts delayed AC1 at Min. current Max. current Max. power DC1 at Min. current Max. current Max. power Utilisation category In accordance with the standard Utilisation category of safety contacts delayed AC15 at Max.
PZE X4V Conventional thermal current while loading several contacts Ith per contact at UB DC AC1: 240 V, DC1: 24 V Conv. therm. current with 1 contact Conv. therm. current with 2 contacts Conv. therm. current with 3 contacts Conv. therm. current with 4 contacts Times Switch-on delay With automatic start after power on typ. With automatic start after power on max.
PZE X4V Mechanical data Mounting position Mechanical life Material Bottom Front Top Connection type Mounting type Conductor cross section with screw terminals 1 core flexible 2 core with the same cross section, flexible with crimp connectors, no plastic sleeve 2 core with the same cross section, flexible without crimp connectors or with TWIN crimp connectors Torque setting with screw terminals Dimensions Height Width Depth Weight 774586 Any 10,000,000 cycles 774583 Any 10,000,000 cycles PPO UL 94 V0 ABS
PZE X4V INFORMATION A safety function's SIL/PL values are not identical to the SIL/PL values of the units that are used and may be different. We recommend that you use the PAScal software tool to calculate the safety function's SIL/PL values. Supplementary data CAUTION! It is essential to consider the relay's service life graphs. The relay outputs' safety-related characteristic data is only valid if the values in the service life graphs are met.
Number of cycles x 1000 PZE X4V Switching current (A) Fig.: Service life graphs at 110 VDC Example } Inductive load: 0.2 A } Utilisation category: AC15 } Contact service life: 1 000 000 cycles Provided the application to be implemented requires fewer than 1 000 000 cycles, the PFH value (see Technical details [ 10]) can be used in the calculation. To increase the service life, sufficient spark suppression must be provided on all relay contacts.
PZE X4V EC declaration of conformity This product/these products meet the requirements of the directive 2006/42/EC for machinery of the European Parliament and of the Council. The complete EC Declaration of Conformity is available on the Internet at www.pilz.com/support/downloads. Representative: Norbert Fröhlich, Pilz GmbH & Co. KG, Felix-Wankel-Str.
Technical support is available from Pilz round the clock.