4-1
4.1 Module features
4 Function description
44000Function descriptionFunction description4-4.1Module features4100Module features4-
4.1.1 Integrated protection mechanisms
Integrated protection mechanisms4-
When the PSSu E F PS1(-T) is used to supply the system, the module
supply is buffered for 20 ms if the supply voltage is interrupted.
The module provides the following diagnostic data:
` Module status
` Module error
4.1.2 Base station in InduraNET p
Base station in InduraNET p4-
The module is a base station in InduraNET p and extends the PSSu
module bus across a radio link. The base station is always the termina-
tion module in a base system. The base station can communicate with
up to four remote stations.
The module provides connections for external supplies.
` The module does not switch the external supplies.
` The external supplies are galvanically isolated from the module bus
supplies and from each other.
` The module has no current limitation on the external supplies.