5.5 Install antenna
5 Installation
5.5Install antenna 5500Install antenna 5-
The antenna is positioned on the control cabinet or on a flat surface, us-
ing one hole mounting. The InduraNET p antenna cable is a 2 m long co-
axial cable for high frequency applications with an impedance level of
50 Ohms.
Please refer to the section entitled "Antenna assembly" for information
on providing sufficient reception.
Procedure:
` In the control cabinet ceiling, punch or drill a hole suitable to take an
M32 thread fitting (> 32 mm diameter).
` Feed the antenna cable through the punched hole and assemble the
antenna.
` Screw on the antenna using the nut on the M32 thread.
` Install the antenna cable from the antenna to the InduraNET p station.
– The minimum bending radius is 15 mm.
– The antenna cable must not be bent or trapped.
– The antenna cable must not be split and then rejoined.
– Excess cable must not be wound like a coil. Excess cable should be
looped.
` Screw the antenna cable on to the socket labelled “ANT” on the
InduraNET p station.
– The torque on the SMA screw connection is 0.7 – 1.1 Nm. You can
achieve the appropriate torque by tightening the screw firmly by
hand.
NOTICE
InduraNET p devices may be damaged if they are operated with-
out an antenna.
` Always operate the PSSu WB S IDN device with the antenna
connected.
CAUTION!
The radio approval will be rendered invalid if a third-party
antenna is used.
` InduraNET p devices should only be used with the antennas
PSS ANT 1 IDN and PSS ANT 2 IDN.