5-9
5.5 Install antenna
5 Installation
5.5Install antenna 5500Install antenna 5-
The antenna is positioned on the control cabinet or on a flat surface, us-
ing one hole mounting. The InduraNET p antenna cable is a 2 m long co-
axial cable for high frequency applications with an impedance level of
50 Ohms.
Please refer to the section entitled "Antenna assembly" for information
on providing sufficient reception.
Procedure:
` In the control cabinet ceiling, punch or drill a hole suitable to take an
M32 thread fitting (> 32 mm diameter).
` Feed the antenna cable through the punched hole and assemble the
antenna.
` Screw on the antenna using the nut on the M32 thread.
` Install the antenna cable from the antenna to the InduraNET p station.
The minimum bending radius is 15 mm.
The antenna cable must not be bent or trapped.
The antenna cable must not be split and then rejoined.
Excess cable must not be wound like a coil. Excess cable should be
looped.
` Screw the antenna cable on to the socket labelled “ANT” on the
InduraNET p station.
The torque on the SMA screw connection is 0.7 – 1.1 Nm. You can
achieve the appropriate torque by tightening the screw firmly by
hand.
NOTICE
InduraNET p devices may be damaged if they are operated with-
out an antenna.
` Always operate the PSSu WB S IDN device with the antenna
connected.
CAUTION!
The radio approval will be rendered invalid if a third-party
antenna is used.
` InduraNET p devices should only be used with the antennas
PSS ANT 1 IDN and PSS ANT 2 IDN.