Configure PITreader
The configuration of the PITreader is described in the operating manual for the authentica-
tion system PITreader.
Checking the unit
Once the unit has been installed and aligned, final inspections must be carried out before it
can be put into service.
INFORMATION
This inspection may only be carried out by qualified personnel.
} Check the PIT gb RLLE y ETH for damage.
} Always test the function with a connected evaluation device.
} Check the function of the E-STOP.
} Check the function of the other control elements.
Troubleshooting
Error Cause Description/measure
LED off 0V voltage supply not
present and/or no signal
at corresponding input
Check the wiring of the inputs
and outputs and rectify wiring
errors
No output signal with control
element operation
24V voltage supply not
present
Check the wiring of the inputs
and outputs and rectify wiring
errors
Function of the unit impaired Connection cable dam-
aged
Check connection cable and ex-
change if necessary
Control element damaged External force Contact Pilz and arrange a re-
placement for the defective con-
trol element.
LED on PITreader flashes red Fault on the PITreader
(e.g. hardware error,
configuration error, in-
valid or uncoded
transponder key, …).
See LED display
PITreader [ 17].