PNOZ s4.
Preface This document is the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal purposes. Suggestions and comments for improving this documentation will be gratefully received. Pilz®, PIT®, PMI®, PNOZ®, Primo®, PSEN®, PSS®, PVIS®, SafetyBUS p®, SafetyEYE®, SafetyNET p®, the spirit of safety® are registered and protected trademarks of Pilz GmbH & Co. KG in some countries.
PNOZ s4.1 Safety relay PNOZ s4.1 The safety relay provides a safety-related interruption of a safety circuit. The safety relay meets the requirements of EN 60947-5-1, EN 60204-1 and VDE 0113-1 and may be used in applications with } E-STOP pushbuttons } Safety gates } Light beam devices It is suitable for use in furnaces in accordance with EN 50156-1.
PNOZ s4.1 Safety features The relay meets the following safety requirements: } The circuit is redundant with built-in self-monitoring. } The safety function remains effective in the case of a component failure. } The correct opening and closing of the safety function relays is tested automatically in each on-off cycle. } The unit has an electronic fuse.
PNOZ s4.1 } Manual start: Unit is active once the input circuit is closed and then the start circuit is closed. Monitored start with falling edge: Unit is active once } – the input circuit is closed and then the start circuit is closed and opened again. – the start circuit is closed and then opened again once the input circuit is closed.
PNOZ s4.1 } Calculation of the max. cable length lmax in the input circuit: Rlmax = max. overall cable resistance (see technical details) Rl / km = cable resistance/km } Use copper wire that can withstand 60/75 °C. } Sufficient fuse protection must be provided on all output contacts with capacitive and inductive loads.
PNOZ s4.
PNOZ s4.
PNOZ s4.1 Operation The unit is ready for operation when the Power LED is permanently lit. LEDs indicate the status and errors during operation: LED on LED flashes Information Status indicators and error indicators may occur independently. In the case of an error display, the "Fault" LED will light or flash (exception: "Supply voltage too low"). An LED that is also flashing indicates the potential cause of the error. An LED that is lit and is static indicates a normal operating status.
PNOZ s4.1 Fault Diagnostics: Internal error, unit defective } Remedy: Switch supply voltage off and then on again, change unit if necessary. Power Diagnostics: Supply voltage too low } Remedy: Check the supply voltage. In1, In2 alternately Fault Diagnostics: Short detected between S12 and S22 } Remedy: Rectify short across contacts, switch supply voltage off and then on again.
PNOZ s4.1 Power, In1, In2, Out, Reset, Fault Diagnostics: The operating mode selector switch "mode" is in its start position (vertical position) } Remedy: Switch off the supply voltage and set the required operating mode on operating mode selector switch "mode". Faults - malfunctions } Contact malfunctions: If the contacts have welded, reactivation will not be possible after the input circuit has opened.
PNOZ s4.1 Technical details General Approvals Electrical data Supply voltage Voltage Type Voltage tolerance Output of external power supply (AC) Output of external power supply (DC) Frequency range AC Residual ripple DC Continuous duty Max. inrush current impulse Reset circuit Feedback loop Max.
PNOZ s4.1 Electrical data Voltage at Input circuit DC Reset circuit DC Feedback loop DC Current at Input circuit DC Reset circuit DC Feedback loop Number of output contacts Instantaneous safety contacts (N/O) Auxiliary contacts (N/C) Inputs Number Semiconductor outputs Number Voltage Current Relay outputs Max. short circuit current IK Utilisation category In accordance with the standard Auxiliary contacts, AC1 at Min. current Max. current Max. power Auxiliary contacts, DC1 at Min. current Max. current Max.
PNOZ s4.1 Relay outputs Utilisation category In accordance with the standard Auxiliary contacts, AC15 at Max. current Auxiliary contacts, DC13 (6 cycles/ min) at Max. current Safety contacts, AC15 at Max. current Safety contacts, DC13 (6 cycles/ min) at Max.
PNOZ s4.1 Conventional thermal current while loading several contacts Ith per contact at UB AC Conv. therm. current with 1 contact Conv. therm. current with 2 contacts Conv. therm. current with 3 contacts Ith per contact at UB DC Conv. therm. current with 1 contact Conv. therm. current with 2 contacts Conv. therm. current with 3 contacts Times Switch-on delay With automatic reset typ. With automatic reset max. With automatic reset after power on typ. With automatic reset after power on max.
PNOZ s4.1 Times 750124 Delay-on de-energisation With E-STOP typ. 10 ms With E-STOP 20 ms max. With power failure 40 ms typ. With power failure 80 ms max. Recovery time at max. switching frequency 1/s After E-STOP 50 ms After power fail- 100 ms ure Waiting period with a monitored reset With rising edge 120 ms With falling edge 250 ms Min.
PNOZ s4.1 Environmental data 750124 Airgap creepage In accordance EN 60947-1 with the standard Overvoltage cate- III gory Pollution degree 2 Rated insulation volt- 250 V age Rated impulse with- 4,00 kV stand voltage Protection type Mounting (e.g.
PNOZ s4.1 Mechanical data Spring-loaded terminals: Terminal points per connection Stripping length Dimensions Height Width Depth Weight 750124 – 750154 – 751124 2 751154 2 – – 9 mm 9 mm 98,0 mm 22,5 mm 120,0 mm 190 g 98,0 mm 22,5 mm 120,0 mm 210 g 100,0 mm 22,5 mm 120,0 mm 190 g 100,0 mm 22,5 mm 120,0 mm 210 g The standards current on 2009-12 apply. Safety characteristic data Operating mode EN ISO 13849-1: 2006 PL Safety con- PL e tacts, instantaneous EN ISO 13849-1: 2006 Category Cat.
PNOZ s4.1 Order reference Order reference Product type Features Terminals Order no. 750 124 PNOZ s4.1 24 VDC Screw terminals PNOZ s4.1 C 24 VDC Spring-loaded terminals 751 124 PNOZ s4.1 48 - 240 VAC/DC PNOZ s4.1 C 48 - 240 VAC/DC Screw terminals 750 154 Spring-loaded terminals 751 154 EC declaration of conformity This product/these products meet the requirements of the directive 2006/42/EC for machinery of the European Parliament and of the Council.
In many countries we are represented by our subsidiaries and sales partners. ... Please refer to our homepage for further details or contact our headquarters. Pilz GmbH & Co. KG Felix-Wankel-Straße 2 73760 Ostfildern, Germany Telephone: +49 711 3409-0 Telefax: +49 711 3409-133 E-Mail: pilz.gmbh@pilz.de Internet: www.pilz.com Technical support +49 711 3409-444 support@pilz.