Conventional ther-
mal current while
loading several
contacts
750124 750154 751124 751154
Ith per contact at UB
AC
Conv. therm. cur-
rent with 1 con-
tact
6,00 A 6,00 A
Conv. therm. cur-
rent with 2 con-
tacts
6,00 A 6,00 A
Conv. therm. cur-
rent with 3 con-
tacts
4,50 A 4,50 A
Ith per contact at UB
DC
Conv. therm. cur-
rent with 1 con-
tact
6,00 A 6,00 A 6,00 A 6,00 A
Conv. therm. cur-
rent with 2 con-
tacts
6,00 A 6,00 A 6,00 A 6,00 A
Conv. therm. cur-
rent with 3 con-
tacts
4,50 A 4,50 A 4,50 A 4,50 A
Times 750124 750154 751124 751154
Switch-on delay
With automatic
reset typ.
170 ms 170 ms 170 ms 170 ms
With automatic
reset max.
300 ms 300 ms 300 ms 300 ms
With automatic
reset after power
on typ.
350 ms 350 ms 350 ms 350 ms
With automatic
reset after power
on max.
600 ms 600 ms 600 ms 600 ms
With manual reset
typ.
40 ms 40 ms 40 ms 40 ms
With manual reset
max.
300 ms 300 ms 300 ms 300 ms
With monitored
reset with rising
edge typ.
35 ms 35 ms 35 ms 35 ms
With monitored
reset with rising
edge max.
50 ms 50 ms 50 ms 50 ms
With monitored
reset with falling
edge typ.
55 ms 55 ms 55 ms 55 ms
With monitored
reset with falling
edge max.
70 ms 70 ms 70 ms 70 ms