Manual
PNOZ s6
Operating Manual PNOZ s6 
21398-EN-08
5
Installation
Install base unit without contact expansion module:  
}  Ensure that the plug terminator is inserted at the side of the unit.
Connect base unit and PNOZsigma contact expansion module: 
}  Remove the plug terminator at the side of the base unit and at the contact expansion 
module.
}  Connect the base unit and the contact expansion module to the supplied connector be-
fore mounting the units to the DIN rail.
Installation in control cabinet 
}  The safety relay should be installed in a control cabinet with a protection type of at least 
IP54.
}  Use the notch on the rear of the unit to attach it to a DIN rail (35 mm).
}  When installed vertically: Secure the unit by using a fixing element (e.g. retaining brack-
et or end angle).
}  Push the device upwards or downwards before lifting it from the DIN rail.
Wiring
Please note:
}  Information given in the "Technical details" must be followed.
}  Outputs 13-14, 23-24, 33-34 are safety contacts; output 41-42 is an auxiliary contact 
(e.g. for display).
}  Auxiliary contact 41-42 and semiconductor output Y32 should not be used for safety 
circuits!
}  To prevent contact welding, a fuse should be connected before the output contacts (see 
technical details).
}  Calculation of the max. cable length l
max
 in the input circuit:
 R
lmax
 = max. overall cable resistance (see technical details) 
R
l
 / km = cable resistance/km
}  Use copper wire that can withstand 60/75 °C.
}  Sufficient fuse protection must be provided on all output contacts with capacitive and in-
ductive loads.