Operating Manual PSSu H m F DP ETH SD Operating Manual PSSu H m F DP ETH SD PSEN enc m1 eCAM, PSEN enc m2 eCAM PSEN enc s1 eCAM, PSEN enc s2 eCAM Position Monitoring Operating Manual — No.
Preface This document is a translation of the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal purposes. Suggestions and comments for improving this documentation will be gratefully received. Pilz®, PIT®, PMI®, PNOZ®, Primo®, PSEN®, PSS®, PVIS®, SafetyBUS p®, SafetyEYE®, SafetyNET p®, the spirit of safety® are registered and protected trademarks of Pilz GmbH & Co. KG in some countries. SD means Secure Digital.
English Contents Contents Contents .................................................................................................................. 1 1 General ................................................................................................................. 3 1.1 Scope ...................................................................................................................................... 3 1.2 Applied directives and standards.................................................
Contents English 5.9.1 Signal characteristic of the incremental interface ................................................... 37 5.10 LED status display ................................................................................................................ 39 6 SSI format............................................................................................................. 40 6.1 Sign of life counter ..........................................................................................
English General 1 General This operating manual includes the following topics: ● General function description ● Essential safety information with details of intended use ● Characteristic data ● Assembly ● Installation/commissioning ● SSI interface 1.
English General 1.2 Applied directives and standards The measuring systems PSEN enc m1 eCAM and PSEN enc m2 eCAM have been developed, designed and manufactured in compliance with the applicable European and international standards, directives and regulations.
English General 1.3 General function description The rotary measuring system • PSEN enc mx eCAM is an absolute multi-turn position measuring system with synchronous serial interface (SSI). • PSEN enc sx eCAM is an absolute single-turn position measuring system with synchronous serial interface (SSI). The measuring system consists of a redundant, dual-channel system, in which optical and magnetic sensing units are arranged on a drive shaft, designed as a hollow shaft or solid shaft. 1.3.
English General 1.3.2 Overall system overview optische Abtastung SSI Antrieb Welle N SSI S magnetische Abtastung Fig. 1: System schematic A Measuring channel 1, single-turn and multi-turn ● Optical detection of the number of steps/revolution ● Max. 8192 steps/revolution, accuracy: 13 Bit ● Synchronous serial interface (SSI) ● Incremental signals for position feedback B Measuring channel 1, multi-turn ● Magnetic detection of the number of revolutions ● Max.
English Essential safety information 2 Essential safety information 2.1 Definition of symbols and instructions DANGER! This means that death or serious injury will occur if the relevant preventive measures are not taken. WARNING! This means that death or serious injury can occur if the relevant preventive measures are not taken. CAUTION! This means that a minor injury can occur if the relevant preventive measures are not taken.
English Essential safety information 2.2 General hazards when using the product The product, described below as the measuring system, is manufactured using state-of-the-art technology.
English Essential safety information 2.3 Intended use The measuring system can be used to detect angular movement and to prepare measured data for control systems within plants.
English Essential safety information 2.4 Warranty and liability All claims to warranty and liability will be rendered invalid if 10 ● The product was used contrary to the purpose for which it is intended ● Damage can be attributed to not having followed the guidelines in the manual ● Operating personnel are not suitably qualified ● Any type of modification has been made (e.g. exchanging components on the PCB boards, soldering work etc.). Pilz GmbH & Co.
English Essential safety information 2.5 Organisational measures ● The operating manual must always be kept ready-to-hand at the location where the measuring system is used ● In addition to the operating manual there are also generally applicable legal and other binding regulations regarding accident prevention and environmental protection, which must be observed and communicated.
English Essential safety information 2.7 Safety information Please note: 12 – Wiring work should only be carried out when the supply voltage is switched off; the same applies when opening and closing electrical connections. – Do not undertake any welding operations if the measuring system is already wired / switched on. – An appropriate heating/cooling measure should be used at the installation site to prevent the ambient temperature exceeding or falling below the permitted limit values.
English Essential safety information The measuring system contains electrostatically sensitive assemblies and components, which can be damaged if handled incorrectly. Avoid finger contact with the measuring system connection contacts and apply the relevant ESD protective measures. Disposal If the device is to be disposed of after its service life, the applicable country-specific regulations must be observed. Pilz GmbH & Co.
Transport / storage English 3 Transport / storage ● ● 14 Transport instructions – Do not drop the device or expose it to heavy impact! The device contains an optical system. – Only the original packaging should be used! Inappropriate packaging material can result in the device becoming damaged in transit. Storage – Storage temperature: -30 to +80℃ – Store in a dry place Pilz GmbH & Co.
English Assembly 4 Assembly 4.1 Solid shaft version The measuring system is connected to the drive shaft via an elastic coupling. The coupling absorbs any deviations in the axial and radial direction between the measuring system and drive shaft. This prevents excessive load on the bearing. The centering collar with selective fit is used for centering in relation to the shaft. The device is fixed to the machine using three screws in the flange.
English Assembly Fig. 2: Flange assembly 16 Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Deutschland Telefon +49 711 3409-0, Telefax +49 711 3409-133, E-Mail: pilz.gmbh@pilz.
English Assembly 4.2 Hollow shaft version 4.2.1 Requirements As the installation is application-dependent, the following instructions do not claim to be exhaustive. The measuring system should be installed on a greaseless shaft. The clamping ring fixing should prevent axial slippage of the measuring system on the drive shaft, see Figure 3. Additional measures may be required to prevent axial slippage of the measuring system. The clamping of the measuring system must not have an axial load.
English Assembly Fig. 4: Positive locking Fig. 5: Requirements of the shaft mounting 18 Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Deutschland Telefon +49 711 3409-0, Telefax +49 711 3409-133, E-Mail: pilz.gmbh@pilz.
English Assembly 4.2.2 Dowel pin Simultaneous rotation of the measuring system, caused by the resulting torque, is prevented by a dowel pin on the machine side. The measuring system has a 6 mm deep 4K7 groove insertion on the back to hold the dowel pin. The dowel pin must reach at least 4 mm into the groove insertion. Fig. 6: Using a dowel pin to prevent simultaneous rotation When inserting the measuring system, position it so that the dowel pin is seated correctly in the groove insertion.
English Assembly Fig. 7: Assembly schematic 20 Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Deutschland Telefon +49 711 3409-0, Telefax +49 711 3409-133, E-Mail: pilz.gmbh@pilz.
English Installation / Preparation for commissioning 5 Installation / Preparation for commissioning 5.1 EMC requirements CAUTION! Invalid measurement values conducted interference! due to radiated and • Radiated interference from hand-held radios, lightning strikes on the network, mobile phones and emissions from individual devices can cause the measuring system to malfunction. Pilz GmbH & Co.
English Installation / Preparation for commissioning • In particular, sources of conducted interference such as frequencycontrolled drives (circuit feedback) have a negative effect on the function of the measuring system. The 24 V power supplies must comply with SELV/PELV. The shielding effect of cables must also be guaranteed after installation (bending radius!) and after changing connectors. If in doubt, use a more flexible cable with a higher current carrying capacity.
English Installation / Preparation for commissioning 5.2 SSI communication mode SSI mode is a synchronous serial communication mode for the position of the measuring system. By using the RS422 interface for communication, sufficiently high transmission rates can be achieved. The measuring system receives a sequence of clock signals from the data receiver (control system) and responds with the current position value, which is transmitted serially and synchronously with the sent clock pulse.
English Installation / Preparation for commissioning 5.3 SSI, RS422 communication technology RS422 communication requires one cable pair for the signals Data+ and Data– and one cable pair for the signals Clock+ and Clock–. The serial data is transmitted without reference to earth as a voltage difference between two corresponding cables. The receiver simply evaluates the difference between two cables, so that commonmode interference on the transmission line does not corrupt the usable signal.
English Installation / Preparation for commissioning Idle signal = 2 V Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Deutschland Telefon +49 711 3409-0, Telefax +49 711 3409-133, E-Mail: pilz.gmbh@pilz.
English Installation / Preparation for commissioning 5.4 Cable specification Signal Cable specification Data+ / Data– (RS422+ / RS422–) Clock+ / Clock– (RS422+ / RS422–) A+ / A– Min. 0.25 mm2, shielded stranded pair Min. 0.25 mm2, shielded stranded pair B+ / B– Supply +24 VDC / 0 V Min. 0.5 mm2, shielded stranded pair The maximum cable length depends on the SSI clock frequency and cable composition and should match the table below.
English Installation / Preparation for commissioning 5.5 Connection Connection data, terminal block X1, X2: – Version with slider mechanism – Grid dimension: 2.5 mm – Cable cross section, strand: 20-28 AWG – Rated current: 6 A Handling: – Move slider mechanism to “1” – Insert strand – Move slider mechanism to “2” and lock Terminal assignment: Guide/clamp for the cable strands Fig. 10: Connection cover open Pilz GmbH & Co.
English Installation / Preparation for commissioning 5.5.1 Supply voltage, X1 NOTICE Risk of undetected damage to the internal electronics due to incorrect overvoltages! • If an overvoltage of >36 VDC is applied inadvertently, the measuring system must be inspected on site.
English Installation / Preparation for commissioning 5.5.2 Measuring systems, X2 PIN 1 2 3 4 5 6 Signal N.C. INK A– INK A+ N.C.
English Installation / Preparation for commissioning 5.6 Shield connection The shield connection is made via special EMC-compliant cable screw connections, in which the cable shield can be connected internally. Cable screw connection assembly, type A Pos. 1 Union nut Pos. 2 Sealing insert Pos. 3 Contact sleeve Pos. 5 Screw socket 1. Trim the shield braid / shield foil to the dimension "X". 2. Slide the union nut (1) and sealing insert / contact sleeve (2) + (3) over the cable. 3.
English Installation / Preparation for commissioning Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Deutschland Telefon +49 711 3409-0, Telefax +49 711 3409-133, E-Mail: pilz.gmbh@pilz.
Installation / Preparation for commissioning English Cable screw connection assembly, type B Pos. 1 Pos. 2 Pos. 3 Pos. 4 Union nut Clamping insert Inner O-ring Screw socket 1. 2. 3. 4. Trim the shield braid / shield foil to the dimension "X" + 2 mm. Slide the union nut (1) and clamping insert (2) over the cable. Bend the shield braid / shield foil by approx. 90°.
English Installation / Preparation for commissioning 1 2 3 4 Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Deutschland Telefon +49 711 3409-0, Telefax +49 711 3409-133, E-Mail: pilz.gmbh@pilz.
English Installation / Preparation for commissioning 5.7 Count direction M1 M2 Fig.
English Installation / Preparation for commissioning 5.8 SSI interface NOTICE Risk of damage to subsequent electronics due to overvoltages caused by a missing earth reference point! • If the earth reference point is missing entirely, e.g. 0 V of the power supply is not connected, voltages equal to the level of the supply voltage can occur at the outputs of this interface. • An earth reference point must be guaranteed to be present at all times. In the rest condition, Data+ and Clock+ are high.
English Installation / Preparation for commissioning tp Monoflop time Monoflopzeit Clock Clock Takt+ pulse Pulse Daten+ Data Fig. 12: Typical SSI communication sequences 1 Takt+ Clock pulse Daten+ Data 2 3 1 2 MSB intern internal re-triggerbares Monoflop retriggerable monoflop Fig. 13: SSI communication format 36 4 T Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Deutschland Telefon +49 711 3409-0, Telefax +49 711 3409-133, E-Mail: pilz.gmbh@pilz.
English Installation / Preparation for commissioning 5.9 Incremental interface To output the absolute position, the standard version of the measuring system also has an incremental interface in addition to the SSI interface. • The measuring system checks the outputs on this interface for external voltage sources. The measuring system is shut down if voltages > 5.7 V arise. In this state, the measuring system behaves as though it were not connected.
Installation / Preparation for commissioning English Edge evaluation Measuring system Counter evaluation 4096 pulses single 4096 Counter pulses/rev. double 8192 Counter pulses/rev. quadruple 16384 Counter pulses/rev. Fig. 14: Counter evaluation) 38 Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Deutschland Telefon +49 711 3409-0, Telefax +49 711 3409-133, E-Mail: pilz.gmbh@pilz.
English Installation / Preparation for commissioning 5.10 LED status display Fig. 15: LED status display Power LED, green CH1: Measuring channel 1, CH2: Safety system ON Supply voltage absent or outside the range 11…28 VDC, hardware error Ready for operation, normal condition Error LED, red CH1: Measuring channel 1, CH2: Safety system OFF Ready for operation, no fault Fault condition; general fault indicator for faults which result in the data output being shut down.
SSI format English 6 SSI format 6.1 Multi-turn Bit 0-11 MSB Bit 12-24 Bit 25-39 LSB MT, 12 Bit ST, 13 Bit Err1, 1Bit Err2, 1 Bit SoL, 5 Bit 8 Bit Multi-turn resolution Single-turn resolution Error bit Measuring channel 1 Error bit Measuring channel 2 Sign of life counter Reserved 224-213 212-20 20 20 24-20 27-20 Both measuring system channels use the same SSI data format. 6.
English Replacing the measuring system 7 Replacing the measuring system The following points must be noted when replacing the measuring system: ● The new measuring system must have the same item number as the system being replaced. Any deviations from this must be cleared with Pilz. ● You must ensure that the count direction set via hardware switches on the new measuring system matches the previous count direction.
Technical details English 1000 Technical Technische 1details Daten Technical details Electrical data Supply voltage UB DC Power consumption at UB DC Polarity protection Scanning principle Absolute values, measuring channel 1 Interface Output driver Resolution per revolution Number of revolutions Update rate Coding Absolute values, measuring channel 2 Interface Output driver Resolution per revolution Number of revolutions Update rate Coding Incremental values Interface Signal level Number of increments Si
Mechanical data Axial shaft load capacity Radial shaft load capacity Mechanical service life Weight 50 N No. 544012, 544022 90 N No. 544012, 544022 3.9 x 1010 850 g No. 544012, 544022 950 g No. 544011, 544021 Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.
In many countries we are represented by our subsidiaries and sales partners. ... Pilz GmbH & Co. KG Felix-Wankel-Straße 2 73760 Ostfildern, Germany Telephone: +49 711 3409-0 Telefax: +49 711 3409-133 E-Mail: pilz.gmbh@pilz.de Internet: www .pilz.com +49 711 3409-444 support@pilz.com InduraNET p®, Pilz®, PIT®, PMCprotego®, PMI®, PNOZ®, Primo®, PSEN®, PSS®, PVIS®, SafetyBUS p®, SafetyEYE®, SafetyNET p®, the spirit of safety® are registered and protected trademarks of Pilz GmbH & Co. KG in some countries.