Installation Guide

Fig. 7.2 Fig. 7.3
Refrigerant Piping
Connection
Oil traps
CAUTION
When the indoor unit is installed higher than
the outdoor unit:
An oil trap should be installed every 10m
(32.8ft) of vertical suction line riser.
(See Fig. 7.2)
-If oil flows back into the outdoor unit’s
compressor, this might cause liquid
compression, or deterioration of oil return.
Oil traps in the rising gas piping can prevent
this.
CAUTION
The indoor unit is installed higher than the
outdoor unit
When the outdoor unit is installed higher than
the indoor unit:
-It is recommended that vertical suction risers
not be upsized. Proper oil return to the
compressor should be maintained with suction
gas velocity. If velocities drop below 7.6 m/s
(1500 fpm (feet per minute)), oil return will be
decreased. An oil trap should be installed every
6m (20ft) of vertical suction line riser.
(See Fig. 7.3)
The outdoor unit is installed higher than the
indoor unit