Installation Guide
Wiring
CAUTION
• While connecting the wires, please follow
the wiring diagram strictly.
• The refrigerant circuit can become very
hot. Keep the interconnection cable away
from the copper tube.
4. Clamp down the cable with the cable clamp.
The cable must not be loose or tug on the
u-lugs.
5. Reattach the electric box cover.
Using the wire controller to set external
static pressure (some models):
You can use the unit’s automatic airow
adjustment function to set external static
pressure.
Automatic airow adjustment is the volume
of blow-o air that has been automatically
adjusted to the quantity rated.
1. Make sure the test run is done with a dry
coil. If the coil is not dry, run the unit for 2
hours in FAN-ONLY mode to dry the coil.
2. Check that both the power supply wiring and
duct installation have been completed
Check that any closing dampers are open.
Check that the air lter is properly attached
to the air suction side passage of the unit.
3. If there is more than one air inlet and outlet,
adjust the dampers so that the airow rate
of each air inlet and outlet conforms with
the designed airow rate. Make sure the
unit is in FAN-ONLY mode. Press and set
the airow adjustment button on the
remote control to change the airow rate
from H or L.
4. Set the parameters for automatic airow
adjustment. When the air conditioning unit
is o, perform the follwoing steps:
- Press “COPY”.
- Press “+” or “-” to select the AF.
- Press “CONFIRM”. The air conditioning
unit will then start the fan for automatic
airow adjustment.
ON will ash when the fan
is on during automatic
airow adjustment.
After 3 to 6 minutes, the air conditioning
unit will stop operating, once automatic airow
adjustment has nished.
•
•
CAUTION
• DO NOT adjust the dampers when
automatic airow adjustment is active.
CAUTION
• If there is no change after airow
adjustment in the ventilation paths, be sure
to reset the automatic airow adjustment.
• If there is no change to ventilation paths
after airow adjustment, contact your dealer,
especially if this occurs after testing the
outdoor unit, or if the unit has been moved
to a dierent location.
• Don’t use automatic airow adjustment with
the remote control if you are using booster
fans, outdoor air processing units, or an HRV
via duct.
• If the ventilation paths have been changed,
reset airow automatic adjustment as
described from step 3 onwards.
Page 25