Datasheet

Electrical data Utilization categories
Alternate current: AC15 (50...60 Hz)
Ue (V) 250 400 500
Ie (A) 6 4 1
Direct current: DC13
Ue (V) 24 125 250
Ie (A) 6 1,1 0,4
Alternate current: AC15 (50...60 Hz)
Ue (V) 24 120 250
Ie (A) 4 4 4
Direct current: DC13
Ue (V) 24 125 250
Ie (A) 4 1,1 0,4
Thermal current (Ith): 4 A
Rated insulation voltage (Ui): 250 VAC 300 VDC
Protection against short circuits: fuse 4 A 500 V type gG
Pollution degree: 3
with 4 poles
M12 connector
Thermal current (Ith): 2 A
Rated insulation voltage (Ui): 30 VAC 36 VDC
Protection against short circuits: fuse 2 A 500 V type gG
Pollution degree: 3
with 8 poles
M12 connector
Alternate current: AC15 (50...60 Hz)
Ue (V) 24
Ie (A) 2
Direct current: DC13
Ue (V) 24
Ie (A) 2
Thermal current (Ith): 10 A
Rated insulation voltage (Ui): 500 VAC 600 VDC
400 VAC for contact blocks 20, 21, 22, 33, 34
Protection against short circuits: fuse 10 A 500 V type aM
Pollution degree: 3
without
connector
For the correct installation of all articles, please see “Utilization requirements” chapter, from page 6/1 to page 6/4.
Technical data
© 2005 Copyright Pizzato Elettrica
General Catalog 18
page 4/11
4
General Catalog 18
page 4/12
© 2005 Copyright Pizzato Elettrica
4
Markings and quality marks:
Approval IMQ: EG610 (FR-FX-FK series)
Approval UL: E131787
Approval EZU: 1010151
In conformity with standards:
IEC 947-5-1, IEC 337-1, EN 60947-5-1, CEI EN 60947-5-1, CEI 17-45, IEC 204-1,
EN 60204-1, CEI 44-5, EN 1088, EN ISO 12100-1, EN ISO 12100-2, IEC 529, EN
60529, CEI 70-1, NFC 63-140, VDE 0660-200, VDE 0113, CENELEC EN 50013,
BG-GS-ET-15.
Approvals:
IEC 947-5-1, UL 508.
General data
Ambient temperature: from -25°C to +80°C
Version for operation in ambient temperature from -40°C to +80° C on request
Max operating frequency: 3600 operations cycles
1
/hour
Mechanical endurance: 1 million of operations cycles
1
Max actuating speed: 0,5 m/s
Min. actuating speed: 1 mm/s
Actuator extraction force 10 N (30 N -E3 version)
(1) One operation cycle means two movements, one to close and one to open contacts, as foreseen
by IEC 947-5-1 standard.
Cross section of the conductors (exible copper wire)
Contact blocks 20, 21, 22, 33, 34: min. 1 x 0,34 mm
2
(1 x AWG 22)
max. 2 x 1,5 mm
2
(2 x AWG 16)
Contact blocks 5, 6, 7, 9: min. 1 x 0,5 mm
2
(1 x AWG 20)
max. 2 x 2,5 mm
2
(2 x AWG 14)
Safety switches with separate actuator
Patent pending
Housing
Made of glass-reinforced polymer, self-extinguishing, shock-proof thermoplastic
resin and with double insulation
FR and FK series one conduit entry
FX series two conduit entries
FW series three knock out conduit entries
Protection degree: IP67 (electrical contacts)
In conformity with requirements requested by:
Low Voltage Directive 73/23/EEC and subsequent modications and
completions. Machinery Directive 98/37/EEC.
Electromagnetic Compatibility 89/336/EEC and subsequent modications and
completions.
Positive contact opening in conformity with standards:
IEC 947-5-1, EN 60947-5-1, CEI EN 60947-5-1, VDE 0660-206.
Main data
Housing polymer housing, from one to
three conduit entries
Protection degree IP67
9 contact blocks available
8 stainless steel actuators available
M12 assembled connector versions
Silver contacts gold plated versions