Quick Guide
5
3. Wiring DC Power Inputs
The 6-contact terminal block connector on the front panel of Industrial Managed
Switch is used for two DC redundant power inputs. Please follow the steps below
to insert the power wires.
1.Insert positive/negative DC power wires into contacts 1 and 2 for DC POWER 1,
or5and6forDCPOWER2.
50/60 Hz
DC POWER
ON
RingRing
AlarmAlarm I/OI/O
AlarmAlarmDC 1
OFF
ON
AC POWER
OFF
DC Input
:
36-60V
, 0.6A max.
DC 2
ACAC
DC1DC1
R.O.R.O.DC2DC2
22
44 66
11 33 55
100-240V , 0.6A max.
GNDGNDDO 1DO 0DI 1DI 0
Max. Fault Alarm Loading: 24V, 1A
Figure 3-1: IGS-5225-16T4S Power Wiring
2.Tightenthewire-clampscrewsforpreventingthewiresfromloosening.
1 2 3 4 5 6
V1+ V1- V2+ V2-
Power 1 Power 2
Positive(+)Pin Negative(-)Pin
IGS-5225-16T4S Pin1/5 Pin2/6
Note
The wire gauge for the terminal block should be in the range
between 12and24 AWG.