Datasheet

IMG-2100T/ IMG-2105AT
6
Product
IMG-2100T IMG-2105AT
Serial Interface
Serial Ports
1 x DB9 male for RS232
1 x 4-Pin Terminal block for RS422 / RS485
Serial Standards RS232 / 4-wire RS422 or RS485 / 2-wire RS485
Baud Rate (Data Rate) 50bps to 921Kbps
Data Bits 5, 6, 7, 8
Parity Type 1, 1.5, 2
Stop Bit Odd, Even, None, Space, Mark
Flow Control
RTS/CTS and DTR/DSR (RS232 only)
XON/XOFF
Signals
RS232: TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
RS422: Tx+, Tx-, Rx+, Rx-, GND
4-wire RS485: Tx+, Tx-, Rx+, Rx-, GND
2-wire RS485: Data A (+), Data B (-), GND
Pin Assignment
Operation Mode
RTU Master/RTU Slave/ASCII Master/ASCII Slave
Master mode: Supports up to 32 TCP slave connection requests
Slave mode: Supports up to 32 TCP master connection requests
Ethernet Interface
Ethernet Ports 1 x RJ45 1 x SFP
Standard 10/100BASE-TX 100BASE-FX
Distance 100m 2km to 120km, vary on SFP modules
ESD Protection 6KV
Surge Protection 2KV
Hardware
Installation DIN-rail kit and wall-mount ear
Enclosure IP 30 metal
Dimensions (W x D x H) 32 x 87.8 x 135 mm 32 x 87.8 x 135 mm
Weight 392g 390g
LED Indicators
System: Power 1, Power 2, Fault, SYS
TP/SFP Port: Link/ Active
Serial Port: Tx and Rx
Power Requirements 9~48V DC / 24V AC, redundant power with reverse polarity protection
Power Consumption
Full Loading
9VDC: 0.35A (3.15 watts)
12VDC: 0.28A (3.36 watts)
24VDC: 0.12A (3 watts)
48VDC: 0.08A (3.84 watts)
Full Loading
9VDC: 0.44A (3.96 watts)
12VDC: 0.33A (4 watts)
24VDC: 0.17A (4.08 watts)
48VDC: 0.1A (4.8 watts)
Connector
Removable 6-pin terminal block for power input
Pin 1/2 for Power 1, Pin 3/4 for fault alarm, Pin 5/6 for Power 2
Alarm
Provides one relay output for power failure
Alarm relay current carry ability: 1A @ DC 24V
Reset Button
< 5 sec: System reboot
> 5 sec: Factory default
Management
Management Interfaces
Web management
Telnet Console management
Windows-based VCOM Utility management
SNMPv1, v2c / SNMP Trap
UNI-NMS monitoring
PLANET Smart Discovery Utility
Specications