Datasheet

TRC ELECTRONICS, INC. 1.888.612.9514 www.trcelectronics.com/meanwell
SPECIFICATION
120W Single Output Industrial DIN RAIL
NDR-120 s e r i e s
File Name:NDR-120-SPEC 2015-10-29
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
Note.6
FREQUENCY RANGE
EFFICIENCY (Typ.)
INPUT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVER TEMPERATURE
SAFETY STANDARDS
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVER VOLTAGE
AC CURRENT (Typ.)
1200ms, 60ms/230
VAC 2500ms, 60ms/115VAC at full load
16ms/230VAC 10ms/115VAC at full load
90 ~ 264VAC 127 ~ 370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)]
47 ~ 63Hz
85.5%
2.25A/115VAC 1.3A/230VAC
29 ~ 33V
88%
56 ~ 65V
89%
20A/115VAC 35A/230VAC
<1mA / 240VAC
14 ~ 17V
Protection type : Shut down o/p voltage, re-power on to recover
Shut down o/p voltage, re-power on to recover
Ul508, TUV EN60950-1 approved
;(meet EN60204-1)
Compliance to EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A
-20 ~ +70 (Refer to "Derating Curve")
20 ~ 95% RH non-condensing
-40 ~ +85, 10 ~ 95% RH
±0.03%/ (0 ~ 50)
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
456.3K hrs min. MIL-HDBK-217F (25)
40*125.2*113.5mm (W*H*D)
0.6Kg; 20pcs/13Kg/1.16CUFT
NDR-120-24 NDR-120-48
24V 48V
5A 2.5A
0 ~ 5A 0 ~ 2.5A
120W 120W
120mVp-p 150mVp-p
24 ~ 28V 48 ~ 55V
±1.0% ±1.0%
±0.5% ±0.5%
±1.0% ±1.0%
NDR-120-12
12V
10A
0 ~ 10A
120W
1
00mVp-p
12 ~ 14V
±2.0%
±0.5%
±1.0%
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25/ 70% RH
ENVIRONMENT
SAFETY &
EMC
(Note 4)
PROTECTION
RIPPLE & NOISE (max.)
Note.2
VOLTAGE TOLERANCE Note.3









EMC IMMUNITY
EMC EMISSION
105 ~ 1
30% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
DIN Rail Power Supply • Industrial • High Efciency • 120W
Mean Well NDR-120 Series
TRC ELECTRONICS, INC.
Providing exceptional customer service since 1982