Installation Guide
7077-171 • July 10, 2012
26
We strongly recommend a minimum of 60
inches (1.5m) vertical, however above the
eve is preferred.
Both installations are approved for mobile home
installations. Must use 3 or 4 inch (76 to 102mm)
“L” or “PL” Listed pellet venting or Listed double
wall pipe and authorized Outside Air Kit in mobile
homes. Single wall pipe is approved for residential
installations only.
Air Clearance to Pipe:
This appliance was tested with standard 3 inch
(76mm) Listed pellet vent.
Pellet pipe manufacturers Listed reduced clear-
ance pipe may be use for reduce clearance from
3 inch (76mm) air clearance to no less than 1 inch
(25mm) air clearance to combustibles for approved
Listed pellet pipe.
Follow pipe manufactures listed air clearances
to combustibles and installation instructions
for all reduced air clearances installations.
C. Vertical into Existing Class A Chimney
B. Through The Wall & Vertical - External
A. Vertical - Interior - Typical Installation
PREFERRED METHOD #1
PREFERRED METHOD #2
8
Venting Systems
Firestop
Flashing
Rain Cap
6 in.
(152mm)
Min.
Non-combustible Hearth Pad
10 in. (254mm) Min.
12 in.
(305mm)
Minimum
Clean-out T
Non-combustible Hearth Pad
Clean-out Cover
Tee
Wall Thimble
Support
Bracket
Every 60 in.
(1.5 m)
12 in.
(305mm)
Minimum
Rain Cap
Flashing
10 in. (254 mm) Minimum
6 in. (152 mm)
Minimum
Firestop
Flashing
Rain Cap
Non-combustible Hearth Pad
Follow vent manufacturer’s
clearances for reduced clearances
12 in. (305mm) Minimum
Ceiling Support
6 in. (152mm) Flue
Connector
6 in. (152mm) Class A
Chimney Connector
Adapter
6 in.
(152mm)
Min.
10 in. (254mm) Min.
Clean-out T