Installation Guide

7077-171 • July 10, 2012
8
2
User Guide: General Operating Information
LED
Color
Number of
Flashes between
pauses
Description Notes
Green Steady ON
(max time 2 min-
utes)
Feed Motor is running continuously.
(This primes the feed tube).
When priming the feed system and lling
the repot, NO NOT OVERFILL FIREPOT
FOR IGNITION. The unit will automati-
cally go into start up following the
prime function.
Green 1x Unit is off and ready.
To start appliance, follow start up sequence.
Green 3x Appliance is in the start up/ignition
sequence or in shutdown.
During shut down, the blowers will shut off
when the exhaust temperature has cooled.
Green Varies
When in the automatic mode, the
number of ashes between pauses
indicates the burn rate (1 for low up to
5 for high).
Adjust the dial control to change the desired
room temperature.
Amber Steady ON
Appliance is set and running at either
the minimum or maximum power
levels.
The unit will shut off only when the hopper
runs out of fuel, the user changes the
dial control to a different state, or the unit
senses an error.
Red
1x
Empty Hopper Alarm
This alarm is caused by the re going out
from lack of fuel. See troubleshooting sec-
tion for more information.
Red 2x Exhaust Probe Alarm Failed component error. See troubleshoot-
ing section for more information.
Red 3x Ambient Probe Alarm Failed component error. See troubleshoot-
ing section for more information.
Red 4x Missed Ignition
There are a total of 2 tries per ignition
sequence. If after 2 tries there is no rise in
exhaust temperature this error will occur.
See the troubleshooting section for addi-
tional information and correction.
Red 8x Exhaust Gas Over Temperature Alarm The exhaust temperature exceed the allow-
able limit. See the troubleshooting section
for more information and correction.
I. LED Color Coding Chart and Explanation
WARNING
Fire Risk
Do NOT operate appliance:
With appliance door open.
Firepot oor open.
Do NOT store fuel:
Closer than required clearances to com-
bustibles to appliance
Within space required for loading or ash
removal.