Data Sheet

TB67S279FTG
2017-09-15
8
5. RESET function
The RESET pin initializes the internal electrical angle.
Note: Built-in digital filter of 0.625 μs (±20 %) is adopted to RESET pin.
RESET
Function
High
Initializes the internal electrical angle
Low
Normal operation
When the RESET pin is set to High, the current setting for each H-bridge (Ach and Bch) will be set to the value below. Also,
the MO pin outputs Low level when the electrical angle corresponds to the initial value.
Step resolution Ach current Bch current Electrical angle
1/32 step setting 71 % 71 % 45°
1/16 step setting 71 % 71 % 45°
1/8 step setting 71 % 71 % 45°
1/2 (b) step setting 71 % 71 % 45°
1/4 step setting 71 % 71 % 45°
1/2 (a) step setting 100 % 100 % 45°
1/1 step setting 100 % 100 % 45°
6. MO (Monitor output: electrical angle monitor) function
MO pin outputs an internal initial electrical angle as a signal. The MO is an open drain type pin; therefore to use the function
properly, please pull up the MO output to VCC. (The pull-up resistor value should be set between 10 kΩ and 100 kΩ.) The
pin level is high impedance (Hi-Z) during the normal operation (internal MOSFET is turned off and pin voltage is VCC). And
when the internal electrical angle is equal to the initial angle, the pin level will be Low (internal MOSFET is turned ON) as
shown below.
MO Function
VCC (Hi-Z)
Electrical angle is not at the initial position
Low
Electrical angle is at the initial position
Note: Hi-Z: High impedance state
Note: The equivalent circuit diagrams may be simplified or some parts of them may be omitted for explanatory purposes.
(10 kΩ to 100 kΩ)
MO
VCC
If the electrical angle is equal to the initial
angle, the internal MOSFET is turned on and
the pin voltage level is Low.
If the electrical angle is not equal to the initial
angle, the internal MOSFET is turned off and
the pin voltage level is High (VCC).