Agency Approvals
W54 series is UL 1077 Recognized as Supplementary Protectors, File
E69543, for Canada and the United States. Available models meet
Ignition Protection requirements in accordance with UL 1500
(excludes models rated >30A). CSA Accepted as Supplementary
Protectors (Appliance Component Protectors), File 240027 (to
125VAC, excludes models rated >30A). Approved to VDE
0642/EN60934 (Circuit Breakers for Equipment) License Number
40007877 (excludes models rated >20A, models with screw terminals,
models with silver-tin oxide contacts). CCC mark compliant,
certificate 2004010307123217.
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that users also seek out the pertinent approvals files of
the agencies/laboratories and review them to confirm the product meets the
requirements for a given application.
Time vs. Current Trip Curve @ +25°C
Overload Trip Times
100%
135%
200%
300%
400%
500%
600%
800%
1000%
No Trip
Trip in 1 hour
5.0 - 30.0 Sec.
1.8 - 7.6 Sec.
1.0 - 4.5 Sec.
0.6 - 3.0 Sec.
0.4 - 2.2 Sec.
0.2 - 1.2 Sec.
0.15 - 0.8 Sec.
.1 1 10 100 1000
Time In Seconds
1000
900
800
700
600
500
400
300
200
100
0
Load Current As A Percent
Of Breaker Rating
10,000
135
Features
• 5 to 40 amp ratings.
• Cannot be manually tripped.
• Button extends for visual trip indication.
• Push button to reset breaker.
• Numerous mounting and termination options.
• Choice of silver-cadmium oxide or silver-tin oxide contacts.
• Optional bottom marking of amperage rating.
Electrical Data @ 25°C
Calibration: Will continuously carry 100% of rating.
May trip between 101% and 134%, but must trip at 135% of
rating within one hour at +25°C.
Dielectric Strength: 1,500VAC (60 seconds).
Mechanical/Environmental Data
Operating Temperature Range: 0°C to +60°C.
Termination: .250” (6.35mm) quick connects or #8-32 screws.
Mounting: Various options. See Ordering Information and drawings.
Approximate Weight: 0.9 oz. (25.0g).
Current Typical Current Typical
Rating Resistance Rating Resistance
in Amps in Ohms in Amps in Ohms
5.0 0.050 15.0 0.017
6.0 0.042 20.0 0.012
7.0 0.036 25.0 0.010
8.0 0.031 30.0 0.008
10.0 0.025 35.0 0.007
12.0 0.021 40.0 0.006
.465
(11.8)
1.22
(31.0)
.846
(21.5)
SEE TERMINAL DRAWINGS
FOR DETAIL
1.378
(35.0)
.575
(14.6)
.157 MAX.
(4.0)
CLOSED
POSITION
SEE MOUNTING
BUSHING AND
MOUNTING HARDWARE
DRAWINGS FOR DETAIL
.303
(7.7)
.102
(2.6)
.031
(.8)
.118 DIA
(3.0)
Outline Dimensions
Typical Resistance vs. Current Rating @25°C
Insulation Resistance: 100 megohms.
Maximum Operating Voltages: 50VDC; 250VAC .
Interrupt Capacity: 1,000 amps in accordance with UL standard 1077.
Resettable Overload Capacity: Ten times rated current.
Reset Time: 60 seconds.
W54 series
Push To Reset Only
P&B Thermal Circuit Breaker
Ambient Compensation Table
To use this chart: Divide the breaker
rating by the correction factor to
determine the compensated rating.
Calculate the overloads in terms of
the compensated rating to use the
published trip curve.
Do not use these devices outside
their specified operating temperature
ranges.
Ambient Rating Correction Factor
Temperature
in °C 5-8A Models 9-30A Models
10 .90 .80
20 .98 .90
25 1.00 1.00
30 1.10 1.05
40 1.25 1.15
50 1.61 1.31
60 2.00 1.55
Optional Protective Boot
Silicone rubber boot is bonded to integral alumimum nut.
1-1423696-5
Black boot for W54 with
3/8”-24 bushing.
1-1423696-6
Clear boot for W54 with
M11 X 1.0 bushing.
.63 DIA.
(16.0)
.622
(15.8)
.799
(20.3)
.70 DIA.
(17.8)