EVD-2 Installation, Operation, and Instruction Manual Electronic Vibration Detector System (All specifications subject to revision.) EVD-M Controller EVD-R Remote Pickup RTA (optional) POTTER ELECTRIC SIGNAL COMPANY, LLC St. Louis, MO (866) 956-1211 • (314) 595-6900 • FAX (314) 595-6999 www.pottersignal.
EVD-2 • 5401042 • REV N • 6/09 WARRANTY INFORMATION The essential purpose of any sale or contract for sale of any of the products listed in the POTTER catalog or price list is the furnishing of that product. It is expressly understood that in furnishing said product, POTTER does not agree to insure the Purchaser against any losses the Purchaser may incur, even if resulting from the malfunction of said product.
EVD-2 • 5401042 • REV N • 6/09 CONTENTS General Information Features Specifications Ordering Information EVD-M Controller Accumulator Function EVD-M Controller Details EVD-M Terminal Connections EVD-R Remote Pickup End of Line Resistor Locations EVD-R Remote Pickup Details EVD-R Terminal Connections Recommended Wiring EVD-2 System Recommended Wiring Recommended Wire Types Recommended Control Panel Wiring and RTA Connections Installation EVD Wiring with Safe Detector Zone and 24 hr Alarm Zone EVD Wiring wit
EVD-2 • 5401042 • REV N • 6/09 4
EVD-2 • 5401042 • REV N • 6/09 General Information The EVD-2, Electronic Vibration Detector System, is listed by Underwriters Laboratories, Inc. and Underwriters Laboratories of Canada for primary protection of Mercantile or Bank, safe or vault and supplementary protection of interior units such as file cabinets, display cases, walls and ceilings. The System must be used with an appropriate UL listed control unit.
EVD-2 • 5401042 • REV N • 6/09 If the main burglar panel has ground fault detection circuitry, it may be necessary to power the EVD from a separate power supply, not from the auxiliary power on the burglar panel. Alternately, the safe may be insulated from ground. EVD-M Controller The EVD-M controller is a microprocessor controlled, vibration detector that incorporates advanced detection methods for identifying all common types of attacks.
EVD-2 • 5401042 • REV N • 6/09 EVD-M Terminal Connections Terminal Terminal Description No.
EVD-2 • 5401042 • REV N • 6/09 Figure 3. EVD-R Remote Pickup Details MAGNETICALLY ACTIVATED TEST SWITCH FIELD WIRING TERMINAL BLOCK (SEE NOTE 6) CABLE CLAMP DWG# 1042-3 EVD-R Terminal Connections Terminal No.
EVD-2 • 5401042 • REV N • 6/09 Figure 4. Recommended Wiring EVD-2 System (Shown with 2 additional EVD-R remote pickups) EVD-R EVD-M EVD-R EVD-R Recommended Wiring Figure 4 shows the recommended wiring for an EVD-2 system with two additional EVD-R remote pickups. (All wiring should be as specified in Table 1 or with UL listed equivalents.) 1. Cable clamp knockout locations are shaded.
EVD-2 • 5401042 • REV N • 6/09 Recommended Control Panel Wiring and Remote Test and Annunciator Connections Figure 5a. Installation The EVD-2 System must be installed in accordance with all applicable local codes. 1. Mount EVD-M controller and any EVD-R remote pickups and wire according to Figures 4 and 5a. Remove end of line resistors from the EVD-M and all EVD-R's except the last EVD-R in the remote pickup network. If no remote pickups are installed do not remove the end of line resistors on the EVD-M.
EVD-2 • 5401042 • REV N • 6/09 Recommended Control Panel Wiring With Safe Detector Zone and 24 Hour Alarm Zone (High security B cable and connections to 24 hr zone as shown are required for UL safe compatible installations) Figure 5b DWG# 1042-16a 11
EVD-2 • 5401042 • REV N • 6/09 Recommended Control Panel Wiring With Safe Detector Zone Only (4 Conductor Shielded Cable Required) Figure 5c 12
EVD-2 • 5401042 • REV N • 6/09 Sensitivity Adjustments 1. Adjust the EVD-M’s internal pickup sensitivity control, RV1, to 1/2 scale (12 o’clock position). Refer to Figure 1 for adjustment location. 2. If remote pickups are installed, adjust the EVD-M’s remote pickup network sensitivity control, RV2, to the minimum setting listed in Table 2. If no EVD-R’s are installed, adjust RV2 to the minimum setting, fully counter-clockwise. Refer to Figure 1 for adjustment location.
EVD-2 • 5401042 • REV N • 6/09 Recommended Detector Locations Single Detector Applications All safe applications must have at least an EVD-M or an EVD-R on the body of the safe. When only one detector is required on a safe, mount the detector on the exterior of the safe on the door hinge side, near the front edge and centered within the height of the safe.
EVD-2 • 5401042 • REV N • 6/09 Table 5 Max.
EVD-2 • 5401042 • REV N • 6/09 Recommended Detector Locations Detector on safe door: If necessary, the detector can be mounted on the safe door (single door only). Mount the detector 1.75" from the edge of the hinge side of the door, centered on equal distance between both hinges. Fig. 9 shows the recommended detector location when mounting the detector on the door. Note: When the detector is mounted on the safe door, the maximum linear distance decreases to 73.
EVD-2 • 5401042 • REV N • 6/09 Table 8 Recommended Maximum EVD-M/EVD-R Spacing for Wall Protection Material Sensitivity Setting Detector Range Rectangular Area of 100% Coverage Steel plate at least 1/4" thick Minimum 8.0' 11.3' x 11.3' 8' x 13.9' 10' x 12.5' 15' x 5.6' - Half 15.0' 21.2' x 21.2' 8' x 28.9' 10' x 28.3' 15' x 26' 20' x 22.4' Maximum 20.0' 28.3' x 28.3' 8' x 39.2' 10' x 38.7' 15' x 37.1' 20' x 34.6' Monolithic concrete at least 6" thick Minimum 16.0' 22.6' x 22.