Polarity Reversal and City Tie Module (Model:PR-5100) Terminal Connections
See Appendix C on page 37 for module speci cations. Wire as shown in Figure 15 below using proper wire gauges. Refer to
LT-877POT for more details.
Note that for use in the USA, the installer must add an Atlantic Scienti c (Tel. 407-725-8000) Model #24544 Protective Device,
or similar ULI-Listed QVRG Secondary Protector, as shown. For use in Canada, the protective device is still recommended, but
the PR-5100 may be connected directly to polarity reversal and city tie wiring.
If UDACT-9100 and PR-5100 are used then
Protector not needed. UDACT-9100 has integral protector and PR-5100 is plugged into it.
Notes:
The terminal blocks are “depluggable” for ease of wiring.
The city tie interface is not power limited.
Use either the PR-5100’s City Tie or Reverse Polarity Interface Module - not both.
Figure 15: PR-5100 Polarity Reversal and City Tie Module Terminal Connections
When wiring devices, please keep in mind the following:
Plug PR-5100 ribbon cable (P1) into the main re alarm module.
All circuits are power limited and must use type FPL, FPLR, or FPLP power limited cable.
For polarity reversal operation, short the city tie connection.
+
-
USE A SHORTING WIRE WHEN
THE CITY TIE IS NOT IN USE.
PROTECTED
+
-
2
1
S
1
2
S
1
1
2
2
S
S
POLARITY REVERSAL ALARM
24VDC OPEN
12VDC AT 3.5 mA
8 mA MAX SHORT
PR-5100
UNPROTECTED
+
+
-
-
DIN RAIL CONNECTION
TO EARTH GROUND
CITY TIE LOCAL ENERGY
RATED 24 VDC FILTERED
TRIP COIL 14 OHMS,
250mA, 5mV RIPPLE
CONFORMS TO NEMA STANDARD
SB3-1969 INTENDED FOR
CONNECTION TO POLARITY
REVERSAL CIRCUIT OF A REMOTE
STATION RECEIVING UNIT HAVING
COMPATIBLE RATINGS.
PROTECTOR
1
2
S
1
2
S
UNPROTECTED
PROTECTOR
PROTECTED
2
1
S
1
2
S
+
-
DIN RAIL CONNECTION
TO EARTH GROUND
POWER LIMITED
POWER LIMITED
+
POLARITY REVERSAL SUPV
24VDC OPEN
12VDC AT 3.5 mA
8 mA MAX SHORT
POWER LIMITED CABLE TYPE FPL,
FPLR OR FPLP MUST BE USED FROM
PR-5100 TO PROTECTORS