Palapala a ka mea nona

8910013 - REV E05/21 PAGE 2 OF 3
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
PSN Series
Power Supplies
PSN-106 Wiring Diagram
N
G
H
Comm
Low Battery
AC Power
Gnd Fault
Battery -
Battery connection (non-power limited).
Use two (2) 12V batteries connected in series.
Common relays are
non-power limited.
120VAC 50Hz~60H
z
240VAC 50Hz~60H
z
Connect to separate
unswitched AC circuit
LOW AC
RELAY
NC COM NO
TROUBLE
RELAY
NC COM NO
Battery +
White
Black
Ground
IN2
- + EOL
IN1
- + EOL
REF
EOL
DC PWR
- +
NAC6
- +
NAC4
- +
NAC3
- +
NAC1
- +
NAC2
- +
NAC5
- +
S1
S2
S3
S4
S5
S6
S8
S7
Trigger
- +
NAC1 NAC4 NAC5 NAC6NAC3NAC2
DC PWR
COMM
DC Power
- +
Status LED's
E.O.L.
ON
E.O.L.
OFF
Bulk Options
120/240 VAC
Jumper Position
GND FAULT
DETECT ENABLE
Optional
Reference
E.O.L.
Factory Installed
Interconnect.
120|240
120|240
Fuse
Note: PSN-64 and PSN-106 draw 15 mA when polarity reverses and the power
supply is triggered. There is no current draw in Standby Mode.
Ordering Information
Model Description Stock No.
PSN-106
10 A Power Supply, 6 NAC Circuits,
Red Enclosure
3006437
PSN-106B 10 A Power Supply, 6 NAC Circuits,
Black Enclosure
3006446
PSN-64 6 A Power Supply, 4 NAC Circuits,
Red Enclosure
3006436
firealarmresources.com