User Manual

11
5. INDICATION AND CONTROL
5.1 LCD Display
The Converter LCD display shows the input voltage, output voltage, output frequency, output
load level, and temperature.
5.2 Thermal Protection
If the Converter detects that it is starting to overheat, it will sound a sequence of 32 beeps
every two seconds. The LCD will show high temperature symbol when the inside is too hot.
If the Converter continues to overheat, it will eventually turn itself off to protect itself from
damage. Once the Converter has cooled off sufficiently, it will automatically restart.
5.3 Output Short Circuit Protection
If the Converter detects that the output voltage is too low for at least 250 ms, and the output
is short circuited or extremely overloaded. The Converter will shut down and attempt to
restart after 30 seconds.
The Converter will continue attempting to restart up to 30 times. If the overload is still
present after 30 attempts, the Converter shuts down and latches off. To restore the
Converter operation, remove the cause of the output short circuit or extreme overload, then
push the main control button for 1 second, the Converter will turn on again.