5.4 Output Overload Alarm
The Converter can accept up to 129% of full load(See spec. for each model's rating) before
continuous alarm sounds. If the output current drawn by the load exceeds the Converter’s
over current alarm threshold, the CPU timer will start to count. If the overload continues for
more than one minute an audible alarm will sound as long as the overload is present. If the
overload alarm continues for more than one minute, the Converter will turn off the output.
After a 30 second delay, the Converter output will restart.
5.5 Output Overload Protection
If the output of the Converter is loaded to more than its output overload protection threshold
for more than two seconds, it will turn off its output, sound an audible alarm, and LCD will
display overload symbol. After a 30 second delay, the Converter will turn on the output again.
If the overload is no longer present, the audible alarm will stop, and the output will operate
normally. If the overload is still present, the Converter will once again turn off the output and
wait 30 seconds before attempting to start again.