TROUBLESHOOTING
NOTE: Before removing and replacing the Converter/charger, perform the following checks:
a. Disconnect the AC power from the vehicle/device.
b. Disconnect the wiring and Battery from the Converter Positive + output terminal.
c. Re-connect the AC power to energize the Converter.
d. Using a voltmeter, measure the voltage at the Converter – and + Output terminals.
> The Converter/Charger is OK if the voltage reading is between 54 VDC and 55 VDC (typically 54.4 VDC).
> Otherwise check the table below:
CONDITION POSSIBLE CAUSE
No 48 VDC output
• 120 VAC not connected to coach or the coach AC circuit breaker is in the off position.
• Reversed battery fuses blown. (Battery wiring connections are reversed),
• Severe overload or shorted load. Remove all loads and retest per above instructions.
• Converter/Charger internal failure.
Converter cycles On & Off
• Fan air flow is inadequate or blocked. (1” minimum free air space at each end required)
• Converter/Charger internal failure.
Reversed Battery fuses blown
• Battery wiring connections are reversed.
• Defective battery, possible bad cells.
48 VDC output is too low
• Attached load exceeds rating of the Converter/Charger.
• Defective battery, possible bad cells.
• Converter/Charger internal failure.