Submittal Sheet

* The wetted surface of this product contacted by consumable water contains less
than 0.25% of lead by weight.
** With equal pressure
*** Minimum fl ow when IntelliStation is installed at or near hot water source recircu-
lating tempered water with a properly sized continuously operating recirculating
pump. (5GPM minimum)
**** low limit cannot be less than the cold water temperature. For best operation,
hot water should be at least 2°F above desired set point.
LEAD FREE
*
ES-P-INTELLISTATIONJR.
Job Name
–––––––––––––––––––––––––––––––––––––––––––
Contractor
––––––––––––––––––––––––––––––––––––––––––––
Job Location
–––––––––––––––––––––––––––––––––––––––––
Approval
–––––––––––––––––––––––––––––––––––––––––––––
Engineer
–––––––––––––––––––––––––––––––––––––––––––––
Contractor’s P.O. No.
––––––––––––––––––––––––––––––––––
Approval
–––––––––––––––––––––––––––––––––––––––––––––
Representative
––––––––––––––––––––––––––––––––––––––––
Powers product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Powers Technical Service. Powers reserves the right to change or modify product design, construction, specifications, or materials with-
out prior notice and without incurring any obligation to make such changes and modifications on Powers products previously or subsequently sold.
IntelliStation
®
Jr.
Digital Water Mixing Valve
Features
• Programmable set point range 60°F to 180°F for wide range of temperature
• Lead Free* construction to comply with lead free* installation requirement
• 3.5" full-color, user-selectable touch screen display
• High temperature Sanitization mode to address water born bacteria
• Integral check valves on hot and cold inlets to prevent cross flow
• In case of power failure, valve flows full cold for safety
Configurable on location. Does not require factory pre-programming, lap top
or special software
Control module support BAS (Building Automation System) communication
with BACnet MSTP and Modbus protocols. It is native to the unit and does
not require an add on module
Mixed outlet temperature can be adjusted/monitored at the valve or
remotely by BAS (Building Automation System)
• Includes single operating sensor for a mixed outlet temperature reading
• Pass code protected for security
• Programmable hi/lo temperature alert
• Programmable schedule for setback of temperature
• Real time clock for time stamping of error messages
• Control water temperature ± 2°F in accordance with ASSE 1017
• Wi-Fi enable for software upgrades
Specifications
Maximum Operating Pressure......................... 200psi (1379kPa)
Maximum Hot Water Temperature .................. 200°F (93°C)
Minimum Hot Water Supply
Temperature** .................................... 2°F (1°C) above set point
Hot Water Inlet Temperature Range ................ 120-180°F (49-82°C)
Cold Water Inlet Range .................................. 39-80°F (4-26°C)
Minimum Flow *** ........................................ 0.5gpm (1.89lpm)
Temperature Adjustment Range**** ................ 60-180°F (16-82°C)
Listing /Compliance ....................................... ASSE 1017, cUPC, NSF
CSA 24/UL873, Bacnet Testing Laboratories (BTL), CE
Weight ......................................................... LFIS075VL 13lb (6kg)
LFIS100VL 17lb (8kg)
LFIS150VL 16lb (7kg)
LFIS200VL 19lb (9kg)
Ambient Temperature ................................... 32°F (0°C) to 122°F (50°C)
Ambient Humidity .......................................... 0 - 90 RH non-condensing
SUITABLE FOR INDOOR USE ONLY
Technical Specification
Power ................................ 115-230 V (ac) ± 10%, 50/60 Hz, 20 VA
Actuator Load ...................... 24 V (dc), 0.55 A, 13 W
1017
The information contained herein is not intended to replace the full
product installation and safety information available or the experience of
a trained product installer. You are required to thoroughly read all instal-
lation instructions and product safety information before beginning the
installation of this product.
NOTICE
E365015
Temp. Ind. and Reg. Equip.
LFIS150VL

Summary of content (3 pages)