3. The control module has a knock-out plug hole. Knock-out the plug hole and run the BAS wire to the
controller.
5. If connecting the controller to a Modbus BAS system system run the A(-), B(+), GND terminals from the
nearest BAS system component and connect to terminals 6, 7, and 8 (-, +, Gnd) of the IntelliStation con-
trol Module 1096.
A grommet or wire protector should be used to protect the wire from being damaged by the enclosure hole
opening.
4. If connecting the controller to a BACnet MSTP system run the A(-), B(+), GND terminals from the nearest
BAS system component and connect to terminals 6, 7, and 8 (-, +, Gnd) of the IntelliStation control
Module 1069.
NOTICE
IntelliStation
®
and BAS
connections
must be properly
grounded.
DANGER
!
!
DO NOT ground to the enclosure. Ground (“Gnd”) terminal must be
connected to terminal “A” marked “Gnd”.
!
DO NOT ground to the enclosure. Ground (“Gnd”) terminal must be
connected to terminal “A” marked “Gnd”.
When the unit powers up it displays the warning message will be shown until 100 seconds has elapsed.
After 100 seconds the control will automatically redirect to the “Home” screen. The settings menu can be
accessed prior to the time elapsing by touching anywhere on the screen.
From the home screen touch the PRGM icon to access the “Programming” menu.
BAS
®
Settings in the Intellistation Control Module Menu