PTSG-12 Operators Manual Power Technology Southeast, Inc.
Limited Warranty on Power Tech Generators Power Technology Southeast, Inc. warrants to you, the original purchaser, that each product of our manufacture is free from defects in materials, and workmanship. That each generator will deliver its rated output as indicated on The Power Technology Nameplate, if properly installed, serviced, and operated under normal conditions in accordance with Power Technology’s instructions.
Engine Maintenance Service Schedule Maintenance Service Item Engine Oil Level Deterioration & Leakage *See Note Daily Every 150 Hours Every 500 Hours Every 1000 Hours Remarks X Engine Oil Change * X Or Once a Year Oil Filter Change * X Or Once a Year Coolant Level X Coolant Leakage X Coolant Change X Fuel Level X Fuel Leakage X As Necessary Fuel Filter Replacement X Air Filter Replacement X Damaged Worn Or Loose Belts ** Replace Fuel Hoses X Check Radiator Hoses & Clamps
GENERATOR ASSEMBLY INFORMATION EXCITER TYPE GENERATOR The exciter pole pieces contain residual magnetism, which sets up lines of force across the air gap to the exciter armature. When the exciter begins to rotate a voltage is induced and current flow is initiated in the exciter armature AC windings. This voltage is fed to the rotating rectifier assembly, rectified and fed to the alternator field, which sets up lines of force across the air gap to the alternator stator windings and to the output circuit.
ROTATING FIELD ASSEMBLY (ROTOR) The rotating field assembly consists basically of four members: 1) the shaft assembly, 2) the core assembly, 3) the field coil damper windings, and 4) balance lugs to provide a high degree of static and dynamic balance. CORE ASSEMBLY The core assembly consists of a quantity of thin steel plates compressed and fastened together to form a single laminated assembly. The field windings are wound around this assembly.
3 DESCRIPTION 1. END COVER 2. EXCITER ROTOR 3. EXCITER STATOR 4. REAR HOUSING BRACKET 5. ROTOR BEARING 6. MAIN STATOR ASSEMBLY** 7. MAIN ROTOR ASSEMBLY GENERATOR ASSEMBLY VOLTAGE REGULATOR **NOTE: 15KW NS-GENCAN 02RTR1520EXC 02STA1520EXCG 02HB15TCGE 02BRG207 02STMN15 02RTRMN15 02GEN15TCGE 06REG634AVC PART NUMBER 17.
VOLTAGE TEST Zero or Low Voltage Check Main Breaker On GenSet Overload High Voltage Output Voltage OK Check AMP Draw From equipment Replace AVR Check Load Distribution One Voltage Line may be Higher than the other Check Gen End 12 VOLT BATTERY TEST One Coil Low Voltage Replace Stator Both Coils Low Voltage Sensing Voltage Low or None Replace Stator Check Connections Check Engine RPM 1800 Replace Stator 6 Replace AVR
10 120 / 240 VOLT CONNECTION “M” SERIES EXCITER TYPE
POWER TECHNOLOGY SOUTHEAST, INC.