User's Guide Getting Started This chapter explains: • Packing the card • Installation Checklist • Card defaults • INTERFACE (EK381V4L 14pin & RJ45) • Cable RJ45 TO DB9 (F) • INTERFACE (UPS side) • Dry contact Function • Configuring the Card Introduction Packing the Card - Dry contact Management Card - Screw - RJ45 to DB9 cable (for RS232, P/N 720-60679-00) - USER MANUAL - Safety Cover - Carton Figure 1.
Card Details Figure 2. Component distribution PCBA Size: 146.2*60*1.
INTERFACE (EK381V4L 14pin & RJ45) Segment PIN NO Specification/Function remark Segment 1 Pin 9 & Pin 2 240Vac/1A(Max) or 30Vdc/1A(Max) Output signal , NO or NC Segment 2 Pin 10 & Pin 3 240Vac/1A(Max) or 30Vdc/1A(Max) Output signal , NO or NC Segment 3 Pin 11 & Pin 4 240Vac/1A(Max) or 30Vdc/1A(Max) Output signal , NO or NC Segment 4 Pin 12 & Pin 5 240Vac/1A(Max) or 30Vdc/1A(Max) Output signal , NO or NC Segment 5 Pin 13 & Pin 6 240Vac/1A(Max) or 30Vdc/1A(Max) Output signal , NO or NC Segm
Note: Segment 7 (PIN14 & PIN1 / USER SW2) is fixed to UPS On function. Segment 8 (PIN7 & PIN1 / USER SW3) is fixed to UPS Off function. (Refer to Dry contact Function Section at next page of this document) We Suggest User do not push down USER SW2 and SW3 at the same time. If user pushes down USER SW2, AS400 Card will send a UPS On command to UPS. If user pushes down USER SW3, AS400 Card will send a UPS Off command to UPS.
INTERFACE (UPS side) Item Specification/Function Pin Assignment - Pin 1 GND - Pin 2 SNMPPOW - Pin 3 RXDUPS - Pin 4 TXDUPS - Pin 5 *UNUSED* - Pin 6 *UNUSED* - Pin 7 -VCC - Pin 8 SNMPSIG - Pin 9 GND - Pin 10 +VCC - Pin 11~26 RESERVE Dry contact Function: Output signals (Segment 1~5): User can choose one function for a Segment from below table.
Input signals (Segment 6): User can choose one function for a Segment from below table. *Input signal (Segment 6): Description Meaning “1” Battery mode shutdown Only Battery mode “0” Normal shutdown Any mode shutdown Shutdown Normal Emergency power off OFF Normal Remote On/Off OFF ON Input signals (Segment 7): Segment 7 is fixed to UPS On function. *Input signal (Segment 7): Description Meaning “1” UPS On ON “0” Normal Input signals (Segment 8): Segment 8 is fixed to UPS Off function.
2. Definitions 2.1. Common items (1) Computer (Software) has Initiative for communicate by this protocol. Computer will send command ended with . Dry contact Management Card will respond the information of ended with Note : means ASCII code “Carriage Return” (HEX-code 0D). (2) All the information is provided in ASCII format. (3) Communication start timing Dry contact Management Card should be received the command from PC, and send the right response to PC. 2.2.
3. Installing 3.1. Installing the Card The Dry contact Management Card can be installed in UPS equipped with a communication bay without turning off the UPS or disconnecting the load. To install the Dry contact Management Card: 1. Remove the communication bay cover from the UPS. Retain the screws. 2. To prevent electrostatic discharge (ESD), place one hand on a metal surface. 3. Slide the card into the open slot and secure with the screws removed in Step 1 Figure4.
3.3. Configuring the Card To configure the card: 1. Verify that the serial cable (supplied) is connected to the card's Settings port and the computer's COM port. 2. Open your terminal emulation program (such as HyperTerminal). a. StartÆAll ProgramsÆAccessoriesÆCommunicationsÆHyper Terminal Or type HYPERTRM in Windows OS Run Dialog b. Name the new connection Figure6.
3. Select the serial connection (such as COM1). Figure7. Select the serial connection 4. Set the serial line to 2400 baud, 8 data bits, No parity, 1 stop bit, no flow control. Figure8.
5. Set the PropertiesÆSettingsÆASCII Setup. Figure9. Set the Properties 4. Setting operation menu 4.1. Password menu Type continuity 3 times, the password menu displays as below Enter Password to Activate Maintenance Menu: Figure10. Password menu Enter admin. The main menu displays (see Figure 12).
4.2. Main menu There are six item can be setting or inquire firmware version, user need base on menu number and enter the correct menu ----------------------------------------------------------------------------Dry contact Management Card ----------------------------------------------------------------------------1. Function Segment Logic 2. Output Segment Function Configure 3. Input Segment Function Configure 4. Function Segment Active Delay Time 5. Return to Default Configuration 6. Firmware Version 0.
----------------------------------------------------------------------------Function Segment Logic ----------------------------------------------------------------------------1. Segment 1 Logic, Current Setting(Normal Open) 2. Segment 2 Logic, Current Setting(Normal Open) 3. Segment 3 Logic, Current Setting(Normal Open) 4. Segment 4 Logic, Current Setting(Normal Open) 5. Segment 5 Logic, Current Setting(Normal Open) 6. Segment 6 Logic, Current Setting(Normal Open) 7.
4.4. Output Segment Function Configure menu When main menu Type 2 and press Enter. The menu displays the Output Segment Function Configure and current setting status as below, in this menu type 0, the menu will return to Figure12. Main menu ----------------------------------------------------------------------------Output Segment Function Configure ----------------------------------------------------------------------------1. Segment 1 function, Current Setting(Utility Failure) 2.
Function description: 1. Utility Failure: UPS input mains voltage or frequency out of range 2. Battery Low: UPS Battery voltage level is low 3. General Alarm: UPS fail condition 4. Bypass Status: UPS under Bypass mode 5. Summary Alarm: Any one of AS400 “Utility Failure”, “General Alarm”, ”Bypass”, “Battery Low”, “Over Load Warning” active will send this signal 6. Battery Testing: Battery Testing is in progress 7.
----------------------------------------------------------------------------Segment 6 Function ----------------------------------------------------------------------------1. Battery Mode Shutdown 2. Any Mode Shutdown 3. Emergency Power Off 4. Remote On/Off 0. Exit ----------------------------------------------------------------------------Please Enter Number: Figure19. Input function select menu Function description: 1.
----------------------------------------------------------------------------Function Segment Active Delay Time ----------------------------------------------------------------------------1. Segment 1 Active Delay Time, Current Setting(Immediately) 2. Segment 2 Active Delay Time, Current Setting(Immediately) 3. Segment 3 Active Delay Time, Current Setting(Immediately) 4. Segment 4 Active Delay Time, Current Setting(Immediately) 5. Segment 5 Active Delay Time, Current Setting(Immediately) 6.
Enter Y or y. below menu will display as below, if enter any other character, the only main menu displays (see Figure 12) and not show “Default All Configuration Parameter” string and do not change to default value Default All Configuration Parameter ----------------------------------------------------------------------------Dry contact Management Card ----------------------------------------------------------------------------1. Function Segment Logic 2. Output Segment Function Configure 3.
----------------------------------------------------------------------------Exit ----------------------------------------------------------------------------1. Exit and Save 2. Exit and Without Save 0. Not Exit ----------------------------------------------------------------------------Please Enter Number: Figure26. Exit and save select menu Type 1 and press Enter means exit setting mode and Save change data, the menu string will as below Exit Setting Mode and Save Data Figure27.
614-09976-00 20