Owner's manual

EN
Contact Ports
The contacts port is formed using six (6) pins numbered from left to right (see fig. 1), which can be
connected to an external monitoring system (such as a BMS) in order to monitor the operational
status of the ATS.
The external equipment must respect the voltage and current characteristics of contacts port.
Fig. 1: Focus on contacts port.
The contacts port provides the following pins:
Pin 1: common contact.
Pin 2: Source B” active contact (if the contact between “pin 1” and “pin 2is closed, output is
supplied by “Source B”).
Pin 3: Source A” active contact (if the contact between “pin 3and “pin 1is closed, output is
supplied by “Source A”).
Pin 4: Source A” status OK contact (if the contact between “pin 4 and “pin 1 is closed,
Source A” is present and regular).
Pin 5: Source B” status OK contact (if the contact between “pin 5 and “pin 1 is closed,
Source B” is present and regular).
Pin 6: Status OK contact (if the contact between “pin 6and “pin 1is closed, ATS functioning
status is regular).
The following diagram shows the functioning of the contacts port.
Fig. 2: Contacts port basic diagram.
ATTENTION: The pins of the contact port are able to carry maximum current of 8A and maximum
voltage of 250Vac.