51
Current
26.4A@230Vac 44.0A@230Vac
Power Factor
0,99 @100% Nominal Load
0,98 @50% Nominal Load
0,95 @25% Nominal Load
THDI
< 5 %@Full load and battery full charged
Battery & Charger
Battery 180VDC/5Ah 240VDC/9Ah
Current 39A 48A
Charger current >1A >1.7A
7.2 Dimension and Weight
Dimension
(W*D*H) mm
438*698*129 438*704*215.5
Net Weight (KG) 46 82.5
Gross Weight (KG) 50 87.5
7.3 Operating Environment
Item Specification/Function Standards/Comments
Cooling Force Air Cooling
Operating
Temperature
Range
0°C ~ 40 °C
Nominal power & continuous
operating mode
Storage
Temperature
-15°C~60°C UPS
0~35°C Battery
Relative
Humidity
0-95% No condensing
Altitude <1000m for Nominal power
Over 1000 m the power
derating is 1 % every 100 m
Acoustic
Noise
<55dB