User Manual

EN
Caution:
The EPO must not be connected to any utility connected circuits. Reinforced
insulation to the utility is required. The EPO Switch must have a minimum
rating of 24Vdc and 20mA and be a dedicated latching-type switch not tied into
any other circuit. The EPO signal must remain active for at least 20ms for
proper operation
EPO Connections
Wire Function Terminal Wire Size Rating Suggested Wire Size
EPO 4-0.32mm
2
(12-22AWG) 0.82mm
2
(18AWG)
Note: Leave the green EPO connector installed in the EPO port of the UPS even
if the EPO function is not need. Remove the small cable from EPO connector.
EPO Connector
5.3 Network Management Card (Optional)
Network Management Card allows the UPS to communicate in a variety of
networking environments and with different types of devices. The series UPS
has one available communication slot for Webpower or other optional card to
achieve remote management of the UPS through internet/ intranet. Please
contact your local dealer for further information.