Owner manual

20
External Battery Cabinet Positive
Pole(+),Neutral pole,Negative
pole(-),
Min.conductor cross section[mm
2
]
Max.conductor cross section[mm
2
]
10
13
21
25
Line input Backfeed protection
device
A 4-pole disconnection device with
100A/250VAC, less than 15s break
time and min. 1.4mm clearance will be
used in final installation for backfeed
protection in line input.
M2 input Backfeed protection device
A 2-pole disconnection device with
100A/250VAC, less than 15s break
time and min. 1.4mm clearance will be
used in final installation for backfeed
protection in line input.
Protective Earthing conductor[mm
2
]
Max.13 Max.25
Torque for fixing above terminals (10 1b in) (18 1b in)
Sheet.1 PowerWalker VFI 10000-20000TP 3/1 models
Model PowerWalker VFI 10000TCP 3/1
Input L2,L3
Min.conductor cross section[mm
2
]
Max.conductor cross section[mm
2
]
2.5
4
Input L1,L2,L3,N switch (A) 63A,250VAC
Output switch(A)/maintain switch(A) 63A,250VAC
Input L1,N
Min.conductor cross section[mm
2
]
Max.conductor cross section[mm
2
]
10
13
Input fuse (A) 30A,250VAC
Output L,N,