Owner manual

14
2.2.2 Inspect the appearance of the UPS to see if there is any
damage during transportation. Do not turn on the unit and notify
the dealer immediately if there is any damage or lack of some
parts.
2.3 Installation steps of wiring
1) Make sure the mains wire & breakers in the building are enough for
the rating of UPS to avoid the hazards of electric shock and fire.
Note: Do not use the wall receptacle as the input power source for
the UPS, as its rated current is less than the UPSs maximum input
current. Otherwise the receptacle may be burned and destroyed.
2) Cut off the mains switch in the building before installation.
3) Turn off all the load switches before connect the load to the UPS.
4) Prepare wires according to the following table:
Wiring spec (AWG)
Model
Input Output Battery Ground
6K 12 12 12
6KS 12 12 12 12
10K 9 9 9
10KS 9 9 9 9
Note 1: The cable for 6K/6KS should be able to carry the current
of >40A, the cross section area should be greater than 3.31 mm
2
.
It is recommended to use 12 AWG wire or thicker for safety and
efficiency.
Note 2: The cable for 10K/10KS should be able to carry the
current of >60A, the cross section area should be greater than
6.63 mm
2
. It is recommended to use 9 AWG wire or thicker for
safety and efficiency.
Note 3: The color of wires should be selected according to the
local electrical laws and regulations.