® Powerware 5115 RM User’s Guide 500–1500 VA www.powerware.
US Patent 6,462,961 Class B EMC Statements FCC Part 15 NOTE This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications.
Special Symbols The following are examples of symbols used on the UPS to alert you to important information: CAUTION Risk of Electric Shock Do Not Open Cover CAUTION To reduce the risk of electric shock, Do not remove cover (or back) No user-serviceable parts inside Refer servicing to the factory RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and the associated warning should be observed.
TABLE OF CONTENTS 1 Powerware 5115 RM – One of the Best! . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 2 Safety Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 3 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Inspecting the Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UPS Setup . .
Table of Contents Testing New Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Recycling the Used Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 8 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 9 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHAPTER 1 POWERWARE 5115 RM – ONE OF THE BEST! The Powerware9 5115 Rack-Mount (RM) uninterruptible power system (UPS) is a high-density power protection solution ideal for servers, storage systems, network equipment, and other critical devices. The slim design and wide range of installation possibilities make the Powerware 5115 RM the most versatile UPS available. With only 1U (1.75”) of rack-height, the UPS can be installed in rack-mount, wall-mount, side-mount (zero U), and bench-top applications.
Powerware 5115 RM – ONE OF THE BEST! : Network Transient Protector guards your network communications equipment from surges. Low voltage models can also protect modems, fax machines, or other telecommunications equipment. : Optional X-SlotZ modules provide enhanced communication capabilities for increased power protection and control. : The Powerware 5115 RM is backed by worldwide agency approvals. 2 Powerware® 5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.
CHAPTER 2 SAFETY WARNINGS Read the following precautions before you install the UPS. IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries. Please read all instructions before operating the equipment and save this manual for future reference. DANGER This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY.
Safety Warnings CAUTION : The wall outlet must be within 2 meters of the equipment and accessible to the operator. : Batteries can present a risk of electrical shock or burn from high short-circuit current. The following precautions should be observed: 1) Remove watches, rings, or other metal objects; 2) Use tools with insulated handles; 3) Do not lay tools or metal parts on top of batteries; 4) Disconnect charging source prior to connecting or disconnecting battery terminals.
Safety Warnings : I overensstemmelse med internationale normer og bestemmelser for el-installation må det udstyr, der er forbundet til udgangen af denne UPS, tilsammen ikke overskride en jordafdelingsspænding på mere end 3,5 milliampere. ADVARSEL : Stikkontakten skal være højest 2 meter fra udstyret og skal være tilgængeligt til operatøren. : Batterier kan udgøre en fare for elektrisk stød eller forbrændinger forårsaget af høj kortslutningsspænding. De korrekte forholdsregler bør overholdes.
Safety Warnings : Teneinde de kans op brand of elektrische schok te verminderen dient deze UPS in een gebouw met temperatuur- en vochtigheidregeling te worden geïnstalleerd, waar geen geleidende verontreinigingen aanwezig zijn. De omgevingstemperatuur mag 40C niet overschrijden. Niet gebruiken in de buurt van water of bij zeer hoge vochtigheid (max. 95%).
Safety Warnings : Vähentääksesi tulipalon ja sähköiskun vaaraa asenna tämä UPS sisätiloihin, joissa lämpötila ja kosteus on säädettävissä ja joissa ei ole virtaa johtavia epäpuhtauksia. Ympäristön lämpötila ei saa ylittää 40 C. Älä käytä lähellä vettä ja vältä kosteita tiloja (95 % maksimi). : Kansainväliset normit ja johdotusmääräykset vaativat, että kaikkien tämän UPS-laitteen ulostulokytkentöjen yhteinen maavuotovirta ei ylitä 3,5 milliampeeria (mA).
Safety Warnings : Pour réduire les risques d’incendie et de décharge électrique, installer l’onduleur uniquement à l’intérieur, dans un lieu dépourvu de matériaux conducteurs, où la température et l’humidité ambiantes sont contrôlées. La température ambiante ne doit pas dépasser 40 C. Ne pas utiliser à proximité d’eau ou dans une atmosphère excessivement humide (95 % maximum).
Safety Warnings : Das Eingangskabel nicht entfernen oder abziehen, während die USV eingeschaltet ist, weil hierdurch die Sicherheitserdung von der USV und den daran angeschlossenen Geräten entfernt wird. : Um die Brand- oder Elektroschockgefahr zu verringern, diese USV nur in Gebäuden mit kontrollierter Temperatur und Luftfeuchtigkeit installieren, in denen keine leitenden Schmutzstoffen vorhanden sind. Die Umgebungstemperatur darf 40C nicht übersteigen.
Safety Warnings ÐñïåéäïðïéÞóåéò ÁóöÜëåéáò ÓÇÌÁÍÔÉÊÅÓ ÏÄÇÃÉÅÓ ÁÓÖÁËÅÉÁÓ ÖÕËÁÎÔÅ ÁÕÔÅÓ ÔÉÓ ÏÄÇÃÉÅÓ ÔÏ ÐÁÑÏÍ ÅÃ×ÅÉÑÉÄÉÏ ÐÅÑÉÅ×ÅÉ ÓÇÌÁÍÔÉÊÅÓ ÏÄÇÃÉÅÓ ÁÓÖÁËÅÉÁÓ ÊÉÍÄÕÍÏÓ Áõôü ôï UPS ðåñéÝ÷åé ÈÁÍÁÔÇÖÏÑÁ ÔÁÓÇ. ¼ëåò ïé åðéóêåõÝò êáé ïé óõíôçñÞóåéò ðñÝðåé íá ãßíïíôáé ÌÏÍÏ ÁÐÏ ÅÎÏÕÓÉÏÄÏÔÇÌÅÍÏ ÃÉÁ ÔÇ ÓÕÍÔÇÑÇÓÇ ÐÑÏÓÙÐÉÊÏ. Ôï UPS ÄÅÍ ÐÅÑÉÅ×ÅÉ ÊÁÍÅÍÁ ÅÎÁÑÔÇÌÁ ÐÏÕ ÍÁ ÌÐÏÑÅÉ ÍÁ ÅÐÉÓÊÅÕÁÓÔÅÉ ÁÐÏ ÔÏ ×ÑÇÓÔÇ. : : : : 10 ÐÑÏÅÉÄÏÐÏÉÇÓÇÊ Ôï óõãêåêñéìÝíï UPS ðåñéÝ÷åé ôç äéêÞ ôïõ ðçãÞ åíÝñãåéáò (óõóóùñåõôÝò).
Safety Warnings : : : ÐÑÏÓÏ×Ç Ïé óõóóùñåõôÝò ìðïñåß íá ðñïêáëÝóïõí çëåêôñïðëçîßá Þ Ýãêáõìá áðü õøçëü ñåýìá âñá÷õêõêëþìáôïò. ËáìâÜíåôå ôéò êáôÜëëçëåò ðñïöõëÜîåéò. Áðáéôåßôáé óùóôÞ äéÜèåóç ôùí óõóóùñåõôþí. Äåßôå ôïõò ôïðéêïýò êáíïíéóìïýò ðïõ áöïñïýí ôéò áðáéôÞóåéò äéÜèåóÞò ôïõò. ÐïôÝ ìçí ðåôÜôå ôïõò óõóóùñåõôÝò óôç öùôéÜ, ãéáôß ìðïñåß íá åêñáãïýí.
Safety Warnings : Per conformità con gli standard internazionali e con le norme in merito al cablaggio, tutta l’apparecchiatura collegata con l’uscita del gruppo statico di continuità non deve avere una corrente di dispersione di terra superiore a 3,5 milliampere. ATTENZIONE : La presa di alimentazione principale non deve trovarsi a oltre 2 metri dall’apparecchiatura e deve essere accessibile all’operatore.
Safety Warnings : Alt utstyr som er forbundet med utgangen av denne UPS’en må ikke ha en sterkere total lekkasjestrøm enn 3,5 milliampere for å være i overensstemmelse med internasjonale standarder og forkablingsbestemmelser. FORSIKTIG : Stikkontakten må befinne seg innen 2 m fra utstyret og må være tilgjengelig for operatøren. : Batterier kan forårsake elektriske støt eller forbrenning på grunn av høy kortslutningsstrøm. Følg instruksene. : Batterier må fjernes på korrekt måte.
Safety Warnings : Para estar de acordo com os padrões internacionais e os regulamentos de fiação, o equipamento total conectado à saída desta UPS não deve ter uma corrente de fuga à terra maior que 3,5 miliampères. PERIGO : O soquete de alimentação principal deve estar à no máximo dois metros do equipamento e acessível ao operador. : As baterias podem apresentar o risco de choque elétrico, ou queimaduras provenientes de alta corrente de curto-circuito. Observe as instruções adequadas.
Safety Warnings : Для снижения опасности пожара или поражения электрическим током устанавливайте ИБП в закрытом помещении с контролируемыми температурой и влажностью, в котором отсутствуют проводящие загрязняющие вещества. Температура окружающего воздуха не должна превышать 40С. Не эксплуатируйте устройство около воды или в местах с повышенной влажностью (макс. 95%).
Safety Warnings Advertencias de Seguridad INSTRUCCIONES DE SEGURIDAD IMPORTANTES GUARDE ESTAS INSTRUCCIONES ESTE MANUAL CONTIENE INSTRUCCIONES DE SEGURIDAD IMPORTANTES PELIGRO Este SIE contiene VOLTAJES MORTALES. Todas las reparaciones y el servicio técnico deben ser efectuados SOLAMENTE POR PERSONAL DE SERVICIO TÉCNICO AUTORIZADO. No hay NINGUNA PARTE QUE EL USUARIO PUEDA REPARAR dentro del SIE. ADVERTENCIA : Este SIE contiene su propia fuente de energía (las baterías).
Safety Warnings PRECAUCIÓN : El tomacorriente de pared debe encontrarse dentro de los 2 metros de distancia del equipo y ser accesible para el operador. : Las baterías pueden presentar un riesgo de descargas eléctricas o de quemaduras debido a la alta corriente de cortocircuito. Preste atención a las instrucciones correspondientes. : Es necesario desechar las baterías de un modo adecuado. Consulte las normas locales para conocer los requisitos pertinentes. : Nunca deseche las baterías en el fuego.
Safety Warnings : För att överensstämma med internationell standard och installationsföreskrifter får inte den totala utrustning som anslutits till uttagen på denna UPS-enhet ha läcksström som överstiger 3,5 milliampere. VIKTIGT : Huvudkontakten måste vara högst 2 meter från utrustningen och inom räckhåll för användaren. : Batterierna kan ge elektriska stötar eller brännskador från hög kortslutningsström. Följ tillämpliga anvisningar.
CHAPTER 3 INSTALLATION This section explains: : Equipment inspection : UPS setup and installation : UPS rear panels Inspecting the Equipment If any equipment has been damaged during shipment, keep the shipping cartons and packing materials for the carrier or place of purchase and file a claim for shipping damage. If you discover damage after acceptance, file a claim for concealed damage.
Installation Mounting the UPS in a 19” Rack Use the following procedure to install the UPS in 19” rack configuration: 1. Place the UPS on a flat, stable surface with the front of the UPS facing toward you. 2. On each side of the UPS, attach the long end of a mounting bracket to the UPS using four of the supplied M3 l 6 screws (see Figure 2). Mounting Bracket 20 Powerware® 5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.
Installation M6 l 10 Rear Rail Screws Clip Nuts Figure 4. Securing the Rear Rail 7. Secure only the bottom hole of the rail to the front of the rack with one M6 l 10 screw and clip nut (see Figure 5). 8. Install a clip nut in the top hole of the rail. 9. Repeat Steps 6 through 8 for the other rail. 10. Tighten the assembly wing nuts on both rail assemblies. Assembly Wing Nuts Clip Nuts M6 l 10 Front Rail Screw Figure 5.
Installation 11. After installing the UPS chassis, secure the front of the UPS to the rack using the supplied hardware (one M6 l 10 screw on each side as shown in Figure 6). 22 Powerware® 5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.
Installation Mounting the UPS in a 23” Rack Use the following procedure to install the UPS in a 23” rack configuration: 1. Place the UPS on a flat, stable surface with the front of the UPS facing toward you. 2. On each side of the UPS, attach the short end of a mounting bracket to the UPS using two of the supplied M3 l 6 screws (see Figure 7). Powerware® 5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.
Installation 4. After installing the UPS chassis, secure the front of the UPS to the rack using the supplied hardware (two M6 l 10 screws and two clip nuts on each side, as shown in Figure 8). Figure 8. Securing the UPS in a 23” Rack 24 Powerware® 5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.
Installation Zero-U Mounting Use the following procedure to install the UPS in a zero-U rack configuration: 1. Place the UPS on a flat, stable surface with the front of the UPS facing toward you. 2. Attach four mounting brackets to the UPS as shown Figure 9. Secure the short end of the mounting bracket to the UPS using two of the supplied M3 l 6 screws. 3. Adjust the sides of the rack to fit the UPS and brackets (within 22.54–22.78” or 56.35–56.95 cm). 4.
Installation Wall-Mount Setup Use the following procedure to mount the UPS to a wall: 1. Place the UPS on a flat, stable surface with the front of the UPS facing toward you. 2. Attach four mounting brackets to the UPS as shown Figure 10. Secure the short end of the mounting bracket to the UPS using two of the supplied M3 l 6 screws. WARNING The UPS MUST be positioned with the front panel at the top to prevent a battery hazard. 3.
Installation Installing the UPS The following steps explain how to install the UPS. See Figure 11 and Figure 12 for the UPS rear panels. 1. If you did not mount the UPS in a rack or to a wall, you can use the UPS as a standalone unit by placing the UPS in a flat, horizontal position. 2. If you are installing power management software, connect your computer to the USB port or UPS communication port using the supplied cable (see page 35).
Installation 10A, IEC-320 Input Connector Communication Port 28 Powerware® 5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.
CHAPTER 4 OPERATION This section describes: : : : : : Turning the UPS on and off Starting the UPS on battery Standby mode The UPS front panel and indicators Initiating the self-test Turning the UPS On After the UPS is connected to a power outlet, the UPS enters Standby mode. To turn on the UPS, press and hold the button until you hear the UPS beep (approximately two seconds). After the UPS is turned on, it conducts a self-test and enters Normal mode.
Operation Standby Mode When the UPS is turned off and remains plugged into a power outlet, the UPS is in Standby mode. All indicators are off and power is not available to your equipment. The battery recharges when necessary. NOTE For 200–240V models, the output receptacles may remain electrically live (up to 100–120V). Unplug the UPS to ensure power is not available to the output receptacles. UPS Front Panel The UPS front panel indicates the UPS status and also identifies potential power problems.
CHAPTER 5 ADDITIONAL UPS FEATURES This section describes: : Changing the voltage configuration : The Network Transient Protector : Load segments Voltage Configuration The DIP switches on the UPS rear panel (see Figure 14) are used to configure the output voltage and input voltage range. 1. The UPS must be completely shutdown. button for two To turn off the UPS, press and hold the seconds and then unplug the UPS from the power outlet. 2. Set the DIP switches according to the configurations in Table 1. 3.
Additional UPS Features Table 1.
Additional UPS Features Load Segments Load segments are sets of receptacles that can be controlled by power management software, providing an orderly shutdown and startup of your equipment. For example, during a power outage, you can keep key pieces of equipment running while you turn off other equipment. This feature allows you to save battery power. See your power management software manual for details. NOTE If the power management software is not used, the individual load segments cannot be controlled.
Additional UPS Features 34 Powerware® 5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.
CHAPTER 6 COMMUNICATION The Powerware 5115 RM has flexible communication options for local, network, or remote monitoring and management. You can use the USB port or the DB-9 communication port to connect your computer to the UPS. The X-Slot communication bay is also available for additional connectivity options. NOTE Select only one method for communication. If an X-Slot card is installed, the USB and DB-9 ports are disabled.
Communication Communication Port To establish communication between the UPS and a computer, connect your computer to the UPS communication port using the supplied communication cable. When the communication cable is installed, power management software can exchange data with the UPS. The software polls the UPS for detailed information on the status of the power environment. If a power emergency occurs, the software initiates the saving of all data and an orderly shutdown of the equipment.
Communication X-Slot Cards X-Slot cards allow the UPS to communicate in a variety of networking environments and with different types of devices. The Powerware 5115 RM is compatible with any X-Slot card, including: : ConnectUPSZ-X Web/SNMP Card - has SNMP and HTTP capabilities as well as monitoring through a Web browser interface; connects to a twisted-pair Ethernet (10/100BaseT) network.
Communication 38 Powerware® 5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.
CHAPTER 7 UPS MAINTENANCE This section explains how to: : : : : Care for the UPS and batteries Replace the batteries Test new batteries Recycle used batteries UPS and Battery Care For the best preventive maintenance, keep the area around the UPS clean and dust-free. If the atmosphere is very dusty, clean the outside of the system with a vacuum cleaner. For full battery life, keep the UPS at an ambient temperature of 25°C (77°F).
UPS Maintenance Replacing Batteries NOTE DO NOT DISCONNECT the batteries while the UPS is in Battery mode. With the hot-swappable battery feature, UPS batteries can be replaced easily without turning the UPS off or disconnecting the load. If you prefer to remove input power to change the battery, press and button for two seconds and then unplug the UPS. hold the Consider all warnings, cautions, and notes before replacing batteries.
UPS Maintenance 2. Disconnect the white battery connector. 3. Remove and set aside the battery cover. 4. Pull the battery group out onto a flat, stable surface. See “Recycling the Used Battery” on page 42 for proper disposal. 5. Slide the new battery group into the UPS. 6. Reinstall the battery cover removed in Step 3. 7. Reconnect the white battery connector. 8. Reinstall the front panel. Powerware® 5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.
UPS Maintenance Testing New Batteries NOTE It is recommended that the batteries charge for 6 to 24 hours before testing. Press and hold the button for three seconds to initiate a self-test. The 15-second test automatically distributes the load to the batteries and tests the battery’s performance. While the test is in progress, the indicators cycle through and the alarm sounds. When complete, the UPS returns to Normal mode as indicated by the and Load indicators.
CHAPTER 8 SPECIFICATIONS This section provides the following specifications for the Powerware 5115 RM models: : : : : Dimensions and weights Electrical input and output Environmental and safety Battery Table 3. Model List and Mechanical UPS Models UPS Dimensions (WxHxD) 120V Models 230V Models PW5115 500 RM PW5115 750 RM PW5115 1000 RM PW5115 1500 RM PW5115 500iRM PW5115 750iRM PW5115 1000iRM PW5115 1500iRM 44.0 x 4.45 x 57.8 cm (17.3 x 1.75 x 22.75) UPS Weights 500 VA: 17.36 kg (38.
Specifications Table 5. Electrical Output Power Levels (rated at nominal inputs) 120V Models 230V Models 500 VA, 320W 750 VA, 520W 1000 VA, 670W 1440 VA, 1000W 500 VA, 320W 750 VA, 520W 1000 VA, 670W 1500 VA, 1000W Power Factor 500 VA, 0.64 750–1500 VA, 0.67–0.
Specifications Table 7. Battery Configuration 500 VA: (2) 6V, 9 Ah internal battery 750 VA: (4) 6V, 7.
Specifications 46 Powerware® 5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.
CHAPTER 9 TROUBLESHOOTING This section explains: : : : : UPS alarms and conditions How to silence an alarm Site wiring fault on 120V models Service and support Audible Alarms and UPS Conditions The UPS has an audible alarm feature to alert you of potential power problems. Use Table 8 to determine and resolve the UPS alarms and conditions. Powerware® 5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.
Troubleshooting Silencing an Audible Alarm Before silencing an alarm, check the alarm condition and perform the applicable action to resolve the condition (see Table 8). To silence the button. If UPS status changes, alarm for an existing fault, press the the alarm beeps, overriding the previous alarm silencing.
Troubleshooting Alarm or Condition Possible Cause Action 1 beep every 4 seconds. The UPS is on battery due to a utility failure. The UPS is powering your equipment with battery power. Prepare your equipment for shutdown. If this is an extended power outage, save your work and turn off your equipment to conserve battery power. 1 beep every 2 seconds. The battery is running low. Two minutes or less of battery power remains (depending on load configuration and battery charge).
Troubleshooting Alarm or Condition Possible Cause Action UPS fan fault. Save your work and turn off your equipment. Turn off and unplug the UPS. Contact your service representative. The alarm cannot be silenced. Failed attempt to start the UPS on battery. Plug the UPS into a power outlet for 24 hours to charge the battery. After charging the battery, press and hold the button for 3 seconds; then check the indicator. The alarm cannot be silenced.
Troubleshooting Service and Support If you have any questions or problems with the UPS, call your Local Distributor or the Help Desk at one of the following telephone numbers and ask for a UPS technical representative.
Troubleshooting 52 Powerware® 5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.