02/20/2001 ® powerware 9 Prestige Series User’s Guide 600 VA - 1800 VA www.powerware.
FCC Statement The Powerware9 9 Prestige Series UPS configurations vary. Some configurations may or may not be classified by the Federal Communications Commission (FCC). If your Prestige unit is classified by these standards, the corresponding information applies: Class A NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules.
120V MODEL QUICK INSTALLATION 1 2
230V MODEL QUICK INSTALLATION NOTE For 208, 220, or 240V models, follow the instructions for changing the output voltage on page 32.
TABLE OF CONTENTS 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 UPS Model and Battery Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Load Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Battery Times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Battery Test on Demand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Battery Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UPS Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHAPTER 1 INTRODUCTION Congratulations on the purchase of your Powerware9 9 Prestige Series uninterruptible power system (UPS). The Prestige UPS meets the toughest measures of superior design and manufacturing, including ISO 9001. You now own the most reliable power protection available. The Prestige provides a steady, well-regulated power supply for your computing and communications equipment, while protecting it from the frequent irregularities that are inherent in commercially available power.
Introduction UPS Model and Battery Configurations This UPS is designed to work with single-phase, three-wire, AC power sources. There are two important considerations when selecting the UPS model and battery configuration to properly safeguard your equipment: : Load requirements : Battery times Load Requirements The load is the equipment to be protected by the UPS. Select the UPS model that meets the power consumption requirements of the load in volt-amperes (VA).
Introduction 3. Add all of the resultant VA ratings together to obtain the total load requirements of the equipment to be protected (see Figure 2). If the load consists of the power-factor corrected supplies, it is recommended to use total watts for the load requirements. COMPUTER MONITOR EXTERNAL MODEM 100 WATTS 2 AMPS 50 VA 100 WATTS x 1.4 = 140 VA 2 AMPERES x 120 = 240 VA or 1 AMPERE x 240 = 240 VA 50 VA 140 VA + 240 VA + 50 VA = 430 VA (Total Load Requirements) Figure 2.
Introduction Prestige 600 - 1500 VA, 120V Models Load (VA) at .7 PF* Load (W) 650 800 1000 750 EXT 1000 EXT 1250 EXT 1500 EXT 200 140 37 37 37 68 68 68 68 400 280 22 22 22 32 32 32 32 600 420 12 12 12 20 20 20 20 8 15A 14 14 14 11 11 11 8 8 800 560 1000 700 1250 875 1500 1050 Load (VA) at .
Introduction Prestige 600 - 1250 VA, 208 - 240V Models Load (VA) at .7 PF* Load (W) 600 800 1000 800 EXT 1000 EXT 1250 EXT 200 140 33 33 33 56 56 56 400 280 21 21 21 29 29 29 600 420 11 11 11 19 19 19 800 560 7 7 13 13 13 1000 700 10 10 1250 875 Load (VA) at .
Introduction Prestige 1500 - 1800 VA, 208 - 240V Models UPS with External Battery Cabinet Configurations (Rounded to the Nearest Minute) Load (VA) at .
Introduction Special Symbols The following common symbols may be found on the UPS: LOAD ON - Press the button with this symbol to energize the output receptacles (Output On). LOAD OFF - Press the button with this symbol to de-energize the output receptacles (Output Off). SAFETY EARTHING TERMINAL - Indicates the primary safety ground. RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and the associated warning should be observed.
Introduction 8 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.
CHAPTER 2 SAFETY WARNINGS IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS. This manual contains important instructions that you should follow during installation of the UPS. Please read all instructions before operating the equipment and save this manual for future reference. DANGER This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside the UPS.
Safety Warnings : Do not remove or unplug the input cord when the UPS is turned on. This removes the safety ground from the UPS and the equipment connected to the UPS. : To comply with international standards and wiring regulations, the total equipment connected to the output of this UPS must not have an earth leakage current greater than 2.75 milliamperes. : The wall outlet must be within 2 meters of the equipment and accessible to the operator.
Safety Warnings : Brug kun den netledning, som blev leveret med UPS’en. Denne netledning er tilsluttet ifølge specifikationerne for NEC (National Electrical Code). Sørg for, at stikket, som skal bruges til UPS’en, er tilsluttet ifølge de samme specifikationer for at undgå skade på dit udstyr. Sørg for, at der er overstrømsbeskyttelse på AC-stikket på monteringstidspunktet. Sørg for, at stikket er sat helt ind i stikkontakten. Brug en enfaset, -treledet AC-kilde, som er jordet.
Safety Warnings Belangrijke Veiligheidsinstructies BELANGRIJKE VEILIGHEIDSINSTRUCTIES BEWAAR DEZE INSTRUCTIES DEZE HANDLEIDING BEVAT BELANGRIJKE VEILIGHEIDSINSTRUCTIES GEVAAR Deze UPS bevat LEVENSGEVAARLIJKE ELEKTRISCHE SPANNING. Alle reparaties en onderhoud dienen UITSLUITEND DOOR ERKEND SERVICEPERSONEEL te worden uitgevoerd. Er bevinden zich GEEN ONDERDELEN in de UPS die DOOR DE GEBRUIKER kunnen worden GEREPAREERD.
Safety Warnings : Verwijder de ingangsnoer niet of haal de stekker van de ingangsnoer er niet uit terwijl de UPS aan staat. Hierdoor zou de UPS en uw aangesloten apparatuur geen aardebeveiliging meer hebben. : Om aan de internationale normen en bedradingsvoorschriften te voldoen mag de gehele apparatuur die op de uitgang van deze UPS is aangesloten, geen aardlekstroom van meer dan 2,75 milliampère hebben.
Safety Warnings 14 : Käytä vain tämän UPS-laitteen mukana toimitettua virtakaapelia, joka on kytketty kansallisten määräysten mukaisesti. Varmista, että UPS-laitteen kanssa käytetty pistorasia on johdotettu näiden samojen määritysten mukaisesti, jotta laitteet eivät vahingoittuisi. Varmista myös, että asennuksen yhteydessä vaihtovirran pistorasia varustetaan ylivirtasuojauksella. Työnnä kosketin kokonaan pistorasiaan. Käytä pelkästään yksivaihteista, kolmijohtoista, maadoitettua verkkopistorasiaa.
Safety Warnings Consignes de sécurité CONSIGNES DE SÉCURITÉ IMPORTANTES CONSERVER CES INSTRUCTIONS CE MANUEL CONTIENT DES CONSIGNES DE SÉCURITÉ IMPORTANTES DANGER! Cet onduleur contient des TENSIONS MORTELLES. Toute opération d’entretien et de réparation doit être EXCLUSIVEMENT CONFIÉE A UN PERSONNEL QUALIFIÉ AGRÉÉ. AUCUNE PIÈCE RÉPARABLE PAR L’UTILISATEUR ne se trouve dans l’onduleur.
Safety Warnings : Ne pas retirer le cordon d’alimentation lorsque l’onduleur est sous tension sous peine de supprimer la mise à la terre de l’onduleur et du matériel connecté. : Afin d’être conforme aux normes et règlements internationaux de câblage, le courant de fuite à la terre de la totalité du matériel branché sur la sortie de l’onduleur ne doit pas dépasser 2,75 mA. : La prise secteur doit se trouver à moins de 2 m du matériel et être accessible à l’utilisateur.
Safety Warnings : Nur das Netzkabel verwenden, das dieser USV beiliegt. Dieses Kabel ist gemäß den Spezifikationen des International Electrical Code (IEC) verdrahtet. Sicherstellen, daß die Wandsteckdose, die für die USV verwendet wird, gemäß den selben Spezifikationen verdrahtet ist, um eine eschädigung der Geräte zu vermeiden. Sicherstellen, daß bei Installation ein Überstromschutz für die Wechselstromsteckdose vorhanden ist.
Safety Warnings ÐñïåéäïðïéÞóåéò ÁóöÜëåéáò ÓÇÌÁÍÔÉÊÅÓ ÏÄÇÃÉÅÓ ÁÓÖÁËÅÉÁÓ ÖÕËÁÎÔÅ ÁÕÔÅÓ ÔÉÓ ÏÄÇÃÉÅÓ ÔÏ ÐÁÑÏÍ ÅÃ×ÅÉÑÉÄÉÏ ÐÅÑÉÅ×ÅÉ ÓÇÌÁÍÔÉÊÅÓ ÏÄÇÃÉÅÓ ÁÓÖÁËÅÉÁÓ ÊÉÍÄÕÍÏÓ Áõôü ôï UPS ðåñéÝ÷åé ÈÁÍÁÔÇÖÏÑÁ ÔÁÓÇ. ¼ëåò ïé åðéóêåõÝò êáé ïé óõíôçñÞóåéò ðñÝðåé íá ãßíïíôáé ÌÏÍÏ ÁÐÏ ÅÎÏÕÓÉÏÄÏÔÇÌÅÍÏ ÃÉÁ ÔÇ ÓÕÍÔÇÑÇÓÇ ÐÑÏÓÙÐÉÊÏ. Ôï UPS ÄÅÍ ÐÅÑÉÅ×ÅÉ ÊÁÍÅÍÁ ÅÎÁÑÔÇÌÁ ÐÏÕ ÍÁ ÌÐÏÑÅÉ ÍÁ ÅÐÉÓÊÅÕÁÓÔÅÉ ÁÐÏ ÔÏ ×ÑÇÓÔÇ.
Safety Warnings : : : : : Ãéá íá ìåéþóåôå ôïí êßíäõíï ðõñêáãéÜò Þ çëåêôñïðëçîßáò, åãêáôáóôÞóôå ôï óõãêåêñéìÝíï UPS óå åóùôåñéêü ÷þñï ìå åëåã÷üìåíç èåñìïêñáóßá êáé õãñáóßá, ï ïðïßïò íá ìçí ðåñéÝ÷åé áãþãéìá õëéêÜ. Ç èåñìïêñáóßá ðåñéâÜëëïíôïò äåí ðñÝðåé íá îåðåñíÜåé ôïõò 40° C. Ìç ÷ñçóéìïðïéåßôå ôï UPS êïíôÜ óå íåñü Þ õðåñâïëéêÞ õãñáóßá (ìÝãéóôç ôéìÞ: 95%). Ìçí âãÜæåôå áðü ôçí ðñßæá ôï êáëþäéï ôñïöïäïóßáò üôáí ôï UPS åßíáé áíïé÷ôü.
Safety Warnings Avvisi di sicurezza IMPORTANTI ISTRUZIONI DI SICUREZZA CONSERVARE QUESTE ISTRUZIONI QUESTO MANUALE CONTIENE IMPORTANTI ISTRUZIONI DI SICUREZZA PERICOLO la TENSIONE contenuta in questo gruppo statico di continuità è LETALE. Tutte le operazioni di riparazione e di manutenzione devono essere effettuate ESCLUSIVAMENTE DA PERSONALE TECNICO AUTORIZZATO. All’interno del gruppo statico di continuità NON vi sono PARTI RIPARABILI DALL’UTENTE.
Safety Warnings : per ridurre il rischio di incendio o di scossa elettrica, installare il gruppo statico di continuità in un ambiente interno a temperatura ed umidità controllata, privo di agenti contaminanti conduttivi. La temperatura ambiente non deve superare i 40EC. Non utilizzare l’unità in prossimità di acqua o in presenza di umidità eccessiva (95% max).
Safety Warnings 22 : Batterier må aldri åpnes eller ødelegges. Frigjorte elektrolytter er skadelige for hud og øyne og kan være ekstremt giftige. : Bruk kun den strømforsyningskabelen som følger med denne UPS’en. Strømkabelen er koblet i overensstemmelse med spesifikasjonene i IECs (International Electrical Code) bestemmelser. Sjekk at stikkontakten som anvendes for UPS’en er koblet i overensstemmelsen med de samme spesifikasjonene for å unngå skade på utstyr.
Safety Warnings Regulamentos de Segurança INSTRUÇÕES DE SEGURANÇA IMPORTANTES GUARDE ESTAS INSTRUÇÕES ESTE MANUAL CONTÉM INSTRUÇÕES DE SEGURANÇA IMPORTANTES CUIDADO A UPS contém VOLTAGEM MORTAL. Todos os reparos e assistência técnica devem ser executados SOMENTE POR PESSOAL DA ASSISTÊNCIA TÉCNICA AUTORIZADO. Não há nenhuma PEÇA QUE POSSA SER REPARADA PELO USUÁRIO dentro da UPS.
Safety Warnings : Para estar de acordo com os padrões internacionais e os regulamentos de fiação, o equipamento total conectado à saída desta UPS não deve ter uma corrente de fuga à terra maior que 2,75 miliampères. : O soquete de alimentação principal deve estar no máximo dois metros do equipamento e acessível ao operador. O interruptor on/off da UPS não isola eletricamente as peças internas. Desconecte-o do soquete de alimentação se não for usá-lo por um longo período.
Safety Warnings : Никогда не открывайте и не деформируйте аккумуляторы. Вытекающий электролит опасен для кожи и глаз, и может быть крайне токсичным. : Пользуйтесь только сетевым шнуром, поставляемым в комплекте с ИБП. Разводка сетевого шнура выполнена в соответствии с требованиями Международных электрических норм (IEC). Во избежание повреждения Вашего оборудования убедитесь в том, что разводка настенной розетки, которая будет использоваться с ИБП, выполнена в соответствии с теми же требованиями.
Safety Warnings Advertencias de Seguridad INSTRUCCIONES DE SEGURIDAD IMPORTANTES GUARDE ESTAS INSTRUCCIONES ESTE MANUAL CONTIENE INSTRUCCIONES DE SEGURIDAD IMPORTANTES PELIGRO Este SIE contiene VOLTAJES MORTALES. Todas las reparaciones y el servicio técnico deben ser efectuados SOLAMENTE POR PERSONAL DE SERVICIO TÉCNICO AUTORIZADO. No hay NINGUNA PARTE QUE EL USUARIO PUEDA REPARAR dentro del SIE.
Safety Warnings : No retire o desenchufe el cable de entrada mientras el SIE se encuentre encendido. Esto suprime la descarga a tierra de seguridad del SIE y de los equipos conectados al SIE. : Para cumplir con los estándares internacionales y las normas de instalación, la totalidad de los equipos conectados a la salida de este SIE no debe tener una intensidad de pérdida a tierra superior a los 2,75 miliamperios.
Safety Warnings 28 : Använd endast den nätsladd som medföljer denna UPS-enhet. Nätsladden är kompatibel med IEC-specifikationerna (International Electrical Code). Kontrollera att det vägguttag som ska användas med UPS-enheten är draget enligt samma specifikationer, så att skada på utrustningen undviks. Kontrollera att det finns överspänningsskydd för växelströmsuttaget vid installationstillfället. Kontrollera att UPS-kontakten är ordentligt inskjuten i vägguttaget.
CHAPTER 3 INSTALLATION The following sections describe UPS storage requirements and the installation and startup of the UPS. Unpacking and Inspection Carefully unpack the UPS and optional battery cabinets, making sure to retain the packaging materials. Examine each unit carefully for any signs of damage and immediately notify your distributor if damage is present. UPS and Battery Cabinet Storage If you plan to store the UPS or battery cabinets prior to use, store them in a cool, dry environment.
Installation 2. Place the battery cabinets underneath or beside the UPS as shown in Figure 3. NOTE For stacked cabinets, do not place more than three battery cabinets in one stack. The UPS cabinet must be placed on top of the battery cabinets. UPS Cabinet Air Vents Battery Cabinet Battery Cabinet Stacked Cabinets UPS Cabinet Side-by-Side Cabinets Figure 3. Cabinet Setup 3. Verify the circuit breaker on all battery cabinets is in the OFF (O) position (see Figure 4). 4.
Installation Breaker Input Connector Serial Port Air Exhausts Battery Circuit Breaker Power Output Receptacles Breaker Tie UPS Cabinet Battery Cabinet External Battery Connector Battery Output Connector Battery Cable Battery Input Connector Figure 4. Typical UPS Rear Panel UPS Startup for 120V Models To start up the UPS for 120V models: 1. Plug the UPS power supply cord into the input connector on the UPS rear panel. 2.
Installation 3. The equipment to be protected by the UPS should be powered off. Plug the equipment into the power output receptacles on the UPS rear panel. DO NOT protect laser printers with the UPS because of the exceptionally high power requirements of the heating elements. The optional PowerPass has a surge-protected receptacle for laser printers. 4. Turn on the equipment that is connected to the UPS. 5. Press and hold the Output On button until you hear the UPS beep (approximately one second).
Installation 4. Press and hold the Output On button until the alarm beeps again. Two indicators, corresponding with the current setting, remain flashing. The output voltage is factory-configured for 230V. OVERLOAD SITE FAULT OVERTEMP BATTERY SELF TEST 240V 230V 220V 208V Figure 5. Output Voltage Indicators 5. Press the Output Off button to scroll through the output voltage options, top to bottom. Each time you press the button, the UPS beeps and the next two indicators flash.
Installation 12. Press and hold the Output On button until you hear the UPS beep (approximately one second). The indicator remains lit and the Self Test indicator turns on. The front panel displays the percentage of full load being applied to the UPS. The UPS is now in Normal mode with the load online. See “Normal Mode” on page 36 for more information. Troubleshooting Tips If you should encounter any problems during startup, see the troubleshooting chart on page 57.
CHAPTER 4 UPS OPERATION This chapter covers the operation of the UPS including front panel functions, operating modes, using the Battery Start feature, shutting down the UPS, and using the PowerPass. UPS Front Panel The UPS front panel has three distinct functions: : Displays the UPS operational mode (Normal, Bypass, or Battery). : Displays any alarm conditions present during operation (the indicators flash).
UPS Operation Operating Modes After you install and apply power to the UPS, the UPS filters and regulates incoming AC power, eliminating noise and voltage spikes, and provides consistent power to your equipment (see Figure 7). While power is applied to the UPS, the maintenance-free battery is automatically kept in a fully-charged condition.
UPS Operation Bypass Mode The indicator and the indicator illuminate simultaneously, indicating Bypass mode (see Figure 9). When the UPS is in Bypass mode, the load is powered by utility power. However, utility power continues to be passively filtered by the UPS. OVERLOAD SITE FAULT OVERTEMP BATTERY SELF TEST LOAD ON UNIT ON BYPASS Figure 9.
UPS Operation When shutdown is imminent, the Self Test indicator flashes. These warnings are approximate, and the actual time to shutdown may vary significantly. Once these warnings are indicated, immediately complete and save your work to prevent data loss and similar difficulties. When utility power is restored after the UPS shuts down, the UPS automatically connects to the load when the startup is complete.
UPS Operation Battery Start NOTE Before using this feature, the UPS must have been powered by utility power at least once. This feature allows you to start the UPS without utility power. After utility power has been unavailable for one minute, press and hold the Output On button until the alarm beeps. The UPS supplies power to your equipment and goes into Battery mode. The indicator remains lit and the front panel displays the percentage of battery capacity remaining to the UPS.
UPS Operation Using the PowerPass The PowerPass provides a high level of reliability with surge suppression and continuous online power for your equipment. It also maximizes uptime by providing a second source of power and surge protection.
UPS Operation Using Maintenance Bypass Use the following procedure to transfer the critical load to Maintenance Bypass (AC Line operation) and remove the UPS: 1. Disconnect the DB-25 serial communications cable from the serial port on the UPS rear panel. 2. Toggle the Bypass switch on the PowerPass to the BYPASS position (see Figure 13 or Figure 14). The PowerPass is now powering your equipment from utility power. Off button until the long beep 3.
UPS Operation Bypass Switch UPS Circuit Breaker Access Power Output Receptacles Laser Printer Receptacle Mounting Screw Circuit Breaker Input Connector Figure 13. PowerPass Front Panel (120V Model) Bypass Switch Power Output Receptacles UPS Circuit Breaker Access Circuit Breaker Mounting Screw Input Connector Laser Printer Receptacle Figure 14. PowerPass Front Panel (208V - 240V, IEC Model) 42 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.
UPS Operation Use the following procedure to reinstall the UPS and transfer the critical load from Maintenance Bypass (AC Line operation) to the UPS: 1. Reconnect the battery cabinet to the battery connector on the UPS rear panel. 2. Switch the circuit breaker on all battery cabinets to the ON ( | ) position. 3. Reconnect the DB-25 serial communications cable on the UPS rear panel. 4. Plug the PowerPass into the UPS.
UPS Operation 44 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.
CHAPTER 5 COMMUNICATION The UPS is equipped with a communications interface port that allows communication with a wide variety of external devices including: : Video or dumb terminal : Serial printer : Computer with power management or shutdown software The serial port enables you to monitor and record diagnostic data with the following communication interfaces: : Serial Communications Interface Terminal Mode Data Dump Mode Printer Mode, 2400 Baud, with Novell Contacts (default) Printer Mode, 19200
Communication Front Panel Communications Access Before you access the front panel, review the following configurations and note the indicator that corresponds with the communication mode. NOTE Only the Printer mode front panel options change the baud rate. Use the UPS Serial Communications Menu to select other baud rates (see page 48).
Communication To access the front panel communication options, perform the following steps: 1. If the UPS is powered on, prepare your equipment for shutdown. Off button until the long beep Press and hold the Output ceases (approximately three seconds). Unplug the UPS. Wait until all indicators turn off and then continue to the next step. Off button until 2. Plug in the UPS while pressing the Output the alarm beeps. All indicators begin flashing. 3. Press and hold the Output alarm beeps again.
Communication UPS Serial Communications Menu With the UPS Serial Communications (Main) Menu, you can view or select UPS communication modes, baud rates, and LAN configurations. To change or display the current communications configuration: 1. Connect the UPS serial port to a video monitor with a serial interface or to your computer’s serial port. If you are using OnliNet or LanSafe software, the UPS should already be connected to your computer. 2.
Communication &DWDORJ 6HULDO 9HUVLRQ &200 PRGH %DXG [ /$1 PRGH 6LWH )DXOW 'HWHFWLRQ ' %. % 6HUB3ULQW 1RYHOO (QDEOHG 1HZ &200 $6&,, 1HZ %DXG 1HZ /$1 1RYHOO 3UHVV VSDFH EDU WR FRQWLQXH NOTE Catalog #, Serial #, and Version # are all identification numbers unique to your UPS and can also be found on the UPS nameplate. 1 > Continuous Dump The UPS regularly transmits status information to the computer.
Communication 6(/(&7 /$1 &21),*85$7,21 4 ! ! ! ! ! 129(// $6 &20 /$1 0$1$*(5 &86720 &21),*85$7,21 72 48,7 7+,6 0(18 (17(5 6(/(&7,21 ! ! Select the AS400 option if you are using OnliSafe software to monitor the UPS. The Custom Configuration option has two screens: the first screen has options available for inverter shutdown, and the second screen has options available for the contact configuration.
Communication Z > Set Baud Rate allows you to select a new baud rate. The Select Baud Rate Menu displays a list of baud rate options. 4 ! ! ! ! ! ! ! 6(/(&7 %$8' 5$7( 48,7 7+,6 0(18 (17(5 6(/(&7,21 ! ! 5. To save the configuration settings, type S at the Main Menu prompt. The UPS operates and communicates under the new configuration, and defaults to these settings each time it is started. If you want to abandon the selections you have made, type Q to quit.
Communication UPS Communications Interface Port In addition to configuring the UPS for specific communication options, you must also ensure proper use of the serial port when connecting the UPS to your network or monitoring equipment. CAUTION The serial port LAN contacts are transistors and are rated at a maximum current of 50 mA and a maximum of +40 Vdc. Do not exceed these ratings or apply any negative voltage or AC voltage to these contacts; otherwise, damage may occur to your UPS.
Communication Communications Mode Reference Chart The following chart defines the UPS serial port contacts. Serial communication is not available with 3Com and AS/400 network configurations. Use only the applicable pins for the selected communication mode; otherwise, interference problems may occur. Communication Mode Function Signal Name Pin No. True Condition Serial Data to UPS RS232 TxD 2 N/A Data from UPS RS232 RxD 3 N/A Signal Ground Novell (D f l ) (Default) 7 Battery On ON.
Communication 54 Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.
CHAPTER 6 SPECIFICATIONS Prestige UPS Model Specifications 120V Models VA Watts Input Current (nominal) Output Current for 120V 650P1SE 650 455 4.9A 5.4A 87W 800P1SE 800 560 5.8A 6.7A 99W 1000P1SE 1000 700 7.2A 8.3A 114W 750P2SE (EXT) 750 525 5.5A 6.3A 93W 1000P2SE (EXT) 1000 700 7.2A 8.3A 114W 1250P2SE (EXT) 1250 875 9.3A 10.4A 142W 1500P2SE (EXT) 1500 1050 11.2A 12.
Specifications Prestige UPS Physical Specifications Parameter Standard Unit with Battery Standard EXT Unit with Battery External Battery Cabinet Height 252 mm (9.91 in) 252 mm (9.91 in) 252 mm (9.91 in) Width 142.5 mm (5.61 in) 142.5 mm (5.61 in) 142.5 mm (5.61 in) Depth 400 mm (15.75 in) 400 mm (15.75 in) 400 mm (15.75 in) Weight 12.93 kg (28.5 lb) 15.6 kg (34.3 lb) maximum EBC60-1 Battery: 12.25 kg (27 lb) EBC60-2 Battery: 22 kg (48.
CHAPTER 7 TROUBLESHOOTING The Prestige UPS is designed for durable, automatic operation and also alerts you whenever potential operating problems may occur. Use the following troubleshooting chart to determine the UPS alarm condition. Indicator Legend Unlit Amber Green Flashing Condition Possible Cause Action UPS does not turn on. UPS is not plugged in. Plug UPS into working outlet. Dead wall socket. Test wall socket, repair as required. UPS circuit breaker is tripped.
Troubleshooting Condition Possible Cause Action indicator remains lit, even though line voltage is present. present Utility line is out of specification. Test wall socket, repair as required. UPS circuit breaker is tripped. Reduce load, then reset breaker. PowerPass circuit breaker is tripped. Reset breaker. Low battery capacity. Allow battery to charge for 24 hours, then retest. Protected equipment power requirements exceed UPS capacity. Reduce load, then retest.
Troubleshooting Condition OVERTEMP Possible Cause Action UPS internal temperature is too high. The alarm beeps and the UPS switches to Bypass mode for approximately 10 minutes, allowing the UPS to cool down. Shut down the UPS. Clear vents. Remove any heat sources. Wait approximately 5 minutes and retry. Contact your service representative if condition persists. Weak battery while in Normal mode. The alarm beeps. Allow the battery to charge for 24 hours, then retest.
Troubleshooting Service and Support The troubleshooting chart on page 57 covers most of the difficulties you may encounter during normal operations. If you have any questions or problems with the UPS, call your Local Distributor or the Help Desk at one of the following telephone numbers and ask for a UPS technical representative.
INDEX Numeric 3Com Network Interface front panel configuration, 46 LAN Configuration Menu, 50 A installation, 29 output connector, 31 storage, 29 Battery Fault condition, 59 indicator, 35 Battery Mode, 37 AC Line Bypass switch, 41 operation, 41 Battery Online, indicator, 35 alarm silencing, 59 UPS, 58 baud rates, 48, 51 Alarm Conditions Battery Fault, 59 Overload, 58 Overtemperature, 59 Self Test Failure, 59 Site Fault, 58 Utility Out of Spec, 58 AS/400 Network Interface front panel configuration, 46
Index cord, power, 31, 32, 33, 56 I Custom LAN Configuration Menu, 50 indicators, front panel, 35 customer service, 60 Inverter Shutdown Control, 50 input cord, 31, 32, 33, 56 L D LAN Configuration Main Menu option, 48 menu, 50 Data Dump Modes, 49 diagnostics, 38 Display Configuration Screen, 49 load definition, 2 requirements, 2 LOW_BATT, 50 E M Main Menu, 48 exiting Main Menu, 51 Maintenance Bypass feature See also PowerPass activating, 41 deactivating, 43 EXT models, 3 F front panel conf
Index N Normal Mode indicator, 35 operation, 36 PowerPass AC Line operation, 41 block diagram, 41 Maintenance Bypass feature, 40 operation, 40 Novell Network Interface front panel configuration, 46 LAN Configuration Menu, 50 Printer Mode front panel configuration, 47 Main Menu configuration, 49 O R rear panel, 31 Operating Modes, 36 Operation Battery, 37 Bypass, 37 Normal, 36 UPS with PowerPass, 40 Output Off Button, 7, 35 Output On Button, 7, 35 output voltage, changing, 39 Overload condition, 58 in
Index storage temperature, 29 Switch, Bypass, 42 system requirements, 2 T Terminal Modes, 49 Tests Battery (on demand), 38 diagnostic, 38 transistors, contact ratings, 52 troubleshooting chart, 57 tips, 34 shutdown, 39 special symbols, 7 startup (120V), 31 startup (208V-240V models), 32 storage, 29 unpacking and inspection, 29 UTIL_FAIL, 50 Utility Out of Spec, 58 V volt-amperes, 2 VT100 Terminal Mode, 49 U uninterruptible power system, 1 UPS alarm silencing, 59 alarms, 58 block diagram, 36 circuit bre