User's Manual

1018946 Rev. A
2/2
Table 1. Relay information available.
Relay # System state D15 pin # NC / NO *
on board connected
K1: Line Line OK 1 - 2 NC
Line failure 1 - 3 NO
K2: Battery Battery normal 4 - 5 NC
Battery low 4 - 6 NO
K3: UPS Alarm UPS alarm 7 - 8 NC
UPS ON / OK 7 - 9 NO
K4: Bypass UPS on bypass 10 - 12 NC
UPS normal / On inverter 10 - 11 NO
UPS shutdown ** 13 - 15
Table 1
* Normally closed (NC) /open (NO) connection state when the Relay Interface Card is not powered.
** The shutdown pin (15) needs minimum of 5 seconds high level signal (connection to +12VDC) to
perform the UPS shutdown.
NOTICE: The relay contacts must not be galvanically connected to any mains connected circuits. Do not use
+12VCD (Pin13) of the Relay Interface Card for any power supply purposes for external devices. Reinforced
insulation to the mains is required for equipment and cables connected to these connections.
The relay contacts are rated for maximum 1A/30VAC or 200mA/60VDC. All relay outputs are galvanically
isolated from the other circuits of the UPS (IEC 950, EN 50091-1).
Shut down function
The Relay Interface Card shut down functionality depends on the jumper (JP1, JP2 & JP3) selected on the
board and on the UPS mode (Normal or On Battery). The functions are described in table 2.
Table 2. Shut down options.
JP1 (factory default) JP2 JP3
PW
9110
UPS
Normal
- - -
On Battery - UPS Off immediately, back
online when power returns.
-
PW
9120
UPS
Normal
- Immediate output off, back
on line when shut down
pins are opened
Immediate output off
On Battery Shut down as in RS-232
port. Output off after 120
sec, back on line when
power returns.
Immediate output off, back
on line when shut down
pins are opened
Immediate output off
PW
9170+
UPS
Normal
- - Immediate output off
On Battery - Immediate output off Immediate output off
Table 2