Powerware 9170 ® User's Guide 3 kVA 18 kVA, 50 and 60 Hz www.powerware.
Requesting a Declaration of Conformity Units that are labeled with a CE mark comply with the following harmonized standards and EU directives: Harmonized Standards: EN 50091-1-1 and EN 50091-2 EU Directives: 73/23/EEC, Council Directive on equipment designed for use within certain voltage limits 93/68/EEC, Amending Directive 73/23/EEC 89/336/EEC, Council Directive relating to electromagnetic compatibility 92/31/EEC, Amending Directive 89/336/EEC relating to EMC The EC Declaration of Conformity is avail
TABLE OF CONTENTS 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Safety Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Physical Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 3 2 Installation Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents Initial Startup Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 Balancing Receptacle Loads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 7 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 Removing Input Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHAPTER 1 INTRODUCTION The Powerware 9170 uninterruptible power system (UPS) is a modular UPS that contains battery modules and power control modules (referred to as power modules). These modules plug into a rack cabinet structure containing additional control, communication, and display functions that enable integrated control of all power modules. The UPS is housed in a single cabinet, with extra battery capacity housed in auxiliary battery cabinets.
Introduction Safety Warnings Read the following precautions before you install the UPS. IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS. This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries. Please read all instructions before operating the equipment and save this manual for future reference.
Introduction Physical Features The Powerware 9170 UPS is available in four cabinet sizes. Figure 1 through Figure 6 show the 3-slot and 9-slot configurations and identify basic Powerware 9170 system features. Six-slot and 12-slot cabinets are also available; external battery cabinets are available in 6-, 9-, and 12-slot sizes. Front Panel Display Front Cover Bezel Figure 1. Three-Slot Cabinet (Front View) BestDock Ports Power Outlets (optional) Input Power Cable (optional) Figure 2.
Introduction Front Panel Display Front Cover Bezels Cabinet Base Figure 3.
Introduction BestDock Ports Power Outlets (optional) Input Power Cable (optional) Figure 4. Nine-Slot Cabinet (Rear View) Handle/Latch Release Handle Thumbscrew Insertion/Extraction Cams Figure 5. Power Module (ASY-0528 and ASY-0567) Secondary Stop Release Latch Release Figure 6.
Introduction 6 Powerware® 9170 User's Guide LTM-1344 B Uncontrolled Copy
CHAPTER 2 INSTALLATION SETUP This chapter explains how to setup and install the Powerware 9170 cabinets: Unpacking and setup, including clearances and location requirements Caster cart installation Stabilizer bracket installation (for 12-slot cabinets with non-isolated output) Rack-mount installation Floor anchor kit installation Moving the cabinets Equipment Clearances All cabinet sizes require the following clearances to allow for servicing and adequate ventilation: From the side panels:
Installation Setup Location Requirements Install the Powerware 9170 UPS as close as possible to the equipment or the load distribution panel it will protect. If this distance is more than 25 ft (7.6m), transient noise can reappear in the electrical distribution system. If additional Powerware 9170 system batteries are in a separate cabinet, the external battery cabinet should be located as close as possible to the Powerware 9170 UPS.
Installation Setup 4. If an optional caster cart is included for cabinet mobility, see Caster Cart Installation" on page 10 for information about mounting the cabinet on the cart and stabilizing it using the cart foot pads. 5. After placing the cabinet in its intended operating location, cut the lifting straps or slip them off the cabinet base tabs. 6. If you are installing an external battery cabinet, continue to Battery Cabinet Installation" on page 17.
Installation Setup NOTE If the floor is uneven and the cabinet is tilted or unstable, you may need to place a thin steel plate under a corner. Do not use the caster bolts to level the cabinet. 7. If you are installing an external battery cabinet, continue to Battery Cabinet Installation" on page 17. If you do not have an external battery cabinet, continue to UPS Startup" on page 49 for plug-receptacle units or to Electrical Installation" on page 23 for hardwired units.
Installation Setup The cart requires no bolts or other hardware to fasten it to the UPS cabinet. It is shaped to fit securely under the cabinet, ensuring proper alignment after placing the cabinet on the cart. Four foot pads under the cart keep the cart from rolling when it is in its intended location. Turn each threaded foot to lower it to the floor. When the foot is tight against the floor, turn the lock nut on the threaded foot up tight against the bottom of the cart to keep the foot from rotating.
Installation Setup Stabilizer Bracket Figure 8. Stabilizer Bracket Installation Rack-Mount Installation The 3- and 6-slot UPS cabinets may be installed in an EIA-standard 19 (48.3-cm) equipment rack. An optional rack-mounting kit (ASY-0547), containing brackets and required hardware, is available for such an installation. For each 3-slot section, use the following mounting procedure to convert the UPS cabinet and install it in the equipment rack: NOTE The UPS cabinet is heavy.
Installation Setup Tab Slots Metal Clip-Nuts Figure 9. Metal Clip-Nut and Tab Slot Locations 5. Install a rack-mount ear (2 for 6-slot cabinets) on each side of the UPS cabinet (see Figure 10). Insert the two offset tabs on the rear edge of the ear into the matching tab slots on the cabinet side frame (see Figure 9). Pivot the ear forward, until it is flush against the UPS cabinet side frame. Secure each ear with three 1/4-20 1/2 Phillips-head bolts, screwed into the metal clip-nuts installed in Step 4.
Installation Setup Equipment Rail Figure 11. Rails Holding UPS 8. With one person lifting each side of the UPS cabinet, position the cabinet onto the two equipment rails. Carefully slide the UPS into the equipment rack until the rack-mount ears of the cabinet are flush with the front vertical rails of the rack. Verify that the holes in the ears align with the holes in the rack. 9.
Installation Setup Mounting Centers for 5/16 (8-mm) Floor Bolts Dimension (see Figure 12) Measurement A 14.5 (36.8 cm) B (3- and 6-slot cabinets) 30.25 (76.8 cm) B (9- and 12-slot cabinets) 34.25 (87 cm) Floor Anchor Bracket B A Figure 12. Floor Anchor Brackets Bolted to UPS Cabinet Moving the Cabinets The Powerware 9170 UPS and the battery cabinet are very heavy with power and battery modules installed.
Installation Setup 3. Pry the caps out of the bolt access holes. 4. Use a 1/2 hex-style socket wrench to turn each of the four bolts clockwise. Doing so lowers the casters to allow the cabinet to roll on the casters. 5. After rolling the cabinet to its intended position, turn all four caster bolts counter-clockwise until the cabinet rests on the floor. Place a plastic cap into each bolt access hole.
CHAPTER 3 BATTERY CABINET INSTALLATION If you are not installing battery modules into a separate external battery cabinet, continue to UPS Startup" on page 49 for plug-receptacle units or to Electrical Installation" on page 23 for hardwired units. WARNING Only qualified service personnel (such as a licensed electrician) should perform the battery cabinet installation. Risk of electrical shock.
Battery Cabinet Installation Entrance Panel Battery Cable Figure 13. UPS Power Entrance Panel 3. Use a pair of pliers to bend the narrow links (1 and 2 in Figure 14) between the outer edge of the lower breakaway panel and the rear panel. 4. Use the pliers to bend the entire breakaway panel (at 3 and 4 in Figure 14) until it breaks away. 1 4 2 3 Figure 14. Breakaway Panel Links 5. Verify all hazardous voltages have been removed from the backplane by testing with a voltmeter or other test device.
Battery Cabinet Installation Backplane Ring Terminal Compression Lug Bus-Bar Extension Assembly Cable Assembly Figure 15. Bus-Bar Extension Installation 6. Remove the nuts holding the +DC and the DC bus bars to the backplane as shown in Figure 15. Remove the ring terminal and the compression lug from the DC bolt. 7. Position the bus-bar extension assembly onto the +DC and DC bolts as shown in Figure 15. Replace the compression lug onto the DC bolt of the bus-bar extension assembly.
Battery Cabinet Installation Cable Assembly Figure 16. Battery Cable Assembly Installation 12. Align the screw holes of the cable assembly's entry plate with holes on the cabinet side panel as shown in Figure 16. Secure the entry plate with screws supplied with the cable assembly. 13. If the battery cable will be installed in customer-supplied flexible or other conduit (as required by local wiring codes), loosen the two screws holding the strain-relief clamp shown in Figure 16.
Battery Cabinet Installation + Figure 17. Battery Cable Installed in Battery Cabinet 17. Secure the +, the , and the conductors to the proper compression lugs on the battery cabinet backplane as shown in Figure 17. Torque all three compression lugs to 75 85 in lb (8.5 9.6 Nm). 18. If an additional battery cabinet will be connected to the first, in a daisy-chain configuration, use another external battery cabinet cable assembly for the connections between the battery cabinets. 19.
Battery Cabinet Installation 22 Powerware® 9170 User's Guide LTM-1344 B Uncontrolled Copy
CHAPTER 4 ELECTRICAL INSTALLATION NOTE If you have a plug-receptacle unit, continue to UPS Startup" on page 49. WARNING Only qualified service personnel (such as a licensed electrician) should perform the electrical installation. Risk of electrical shock. The Powerware 9170 UPS input power may be hardwired through conduit to either a main power source circuit breaker or to an optional external bypass switch.
Electrical Installation External Bypass Switch Off Service Line Building Service Panel Load Distribution Panel UPS Off Service Line UPS Off Service Line UPS User-supplied (If Required) External Batteries (Optional) Figure 18.
Electrical Installation If a bypass switch is not used, the UPS input may be hardwired through conduit to a main power source circuit breaker, and the UPS output may either be hardwired to a circuit breaker in a distribution panel (as shown in Figure 19) or supplied to loads through receptacles on the back of the UPS. Without a bypass switch, power to the load cannot be maintained if the UPS is taken completely offline.
Electrical Installation Input Current Ratings Table 1 contains the required circuit breaker ratings for hardwired installations. Circuit breaker ratings for units having an input line cord are determined by the current capacity of the line cord. Table 1.
Electrical Installation Table 2. Recommended Wire Sizes Input Circuit Breaker Size 75°C Copper Wire Size Conductor Screw Torque 25A 10 AWG (5.3 mm2) 20 in lb (2.3 Nm) 40A 8 AWG (8.4 mm2) 25 in lb (2.8 Nm) 60A 4 AWG (21.2 mm2) 35 in lb (4.0 Nm) 80A 3 AWG (26.7 mm2) 45 in lb (5.1 Nm) 100A 2 AWG (42.1 mm2) 55 in lb (6.2 Nm) 125A 1/0 AWG (53.5 mm2) 65 in lb (7.3 Nm) FOR U.S.
Electrical Installation Table 3. Bypass Switch Positions Switch Position Description LINE Connects the load directly to AC input power and disconnects UPS output. AC input power is still connected to the UPS input. OFF Disconnects the load from the UPS output power and AC input power, as well as AC input power to the UPS input. UPS Connects the UPS output to the load. SERVICE Like the LINE position, SERVICE connects the load directly to AC input power and disconnects UPS output.
Electrical Installation D A E B C Figure 20.
Electrical Installation UPS Installation with an External Bypass Switch WARNING Only qualified service personnel (such as a licensed electrician) should perform the electrical installation. Risk of electrical shock. CAUTION To prevent electrical shock or damage to the equipment, verify that the Powerware 9170 UPS is OFF before you remove the entrance panel. The circuit breaker or disconnect switch must also be off at the AC input service panel.
Electrical Installation Wiring Access Hole for Optional EPO and Bypass Input Signals Wiring Access Hole for an Optional Generator Input Signal Entrance Panel Battery Cable Figure 21. UPS Power Entrance Panel 3. Remove the rear panels of the UPS (top panel on 3- or 6-slot; top 2 panels on 9- and 12-slot) as shown in Figure 21. The entrance panel contains knockout openings for entrance and exit conduits and for conduit to an optional external battery cabinet.
Electrical Installation 5. Install the conduit adapters. AC input and AC output conductors must be run through separate conduits. UPS output circuits must be installed in dedicated conduit systems and not shared with other electrical circuits. 6. Find the terminal strip inside the bypass switch cabinet. Using the label on the back of the bypass switch access panel and the proper installation wiring diagram, make the terminal strip connections and tighten all connections as specified in Table 2 on page 27.
Electrical Installation 3 +DC X2 X1 2 1 N -DC Backplane Board Terminating Studs X2 +DC N X1 -DC Figure 23. UPS Input and Output Terminals 9. Refer to the wiring diagrams beginning on page 38 which show output configurations for various voltages and isolation options. Make UPS output connections on the backplane board terminating studs. Compression lugs (supplied in the accessory kit) may be installed on the proper terminating studs.
Electrical Installation The Generator On signal is isolated from line voltage and can be treated as NEC Class 2 wiring. Use 14 20 AWG, 600V wire (UL) or 14 26 AWG, 300V wire (CSA) for all input control signals. Generator On (Normally Open) Signal Common Plastic Cable Tie Emergency Power-Off (Normally Closed) External Bypass *(Short to Common When Active) Generator Set Figure 24. Input Control Signal Wiring 12.
Electrical Installation Wiring Diagrams Select wiring diagrams from Table 5 based upon the installation voltage and whether your site has an external bypass switch. Table 5.
Electrical Installation CAUTION Confirm that the UPS is wired for the proper input voltage as shown in Figure 25, and that the proper power modules (either universal or split-phase) are installed to produce the desired output voltage. Do not mix the two types of power modules in the same UPS cabinet.
Electrical Installation 50 or 60 Hz 100/200, 110/220, 127/220, 120/208, or 120/240V Out Parameter 7-3-4 set to 200, 220, 208, or 240, as required. X2 X N/-DC X X1 X 200, 220 208, or 240 L2 100, 110, 127, or 120 100, 110, 127, or 120 L1 N Figure 26. Split-Phase Modules with Non-Isolated Output 50 or 60 Hz 208, 220, 230, or 240V Out * Parameter 7-3-4 set to 208, 220, 230, or 240, as required. X2 N/-DC X X1 X * L1 L2/N Figure 27.
Electrical Installation System Wiring Diagrams The following notes are referenced in the non-isolated system wiring diagrams (Figure 28 through Figure 33). To determine which diagram is correct for your site, see Table 5 on page 35. NOTE 1 The customer must provide input overcurrent protection as stated in NEC Section 240-21 or local codes. Size the protection device according to local code requirements (see Table 1 on page 26). NOTE 2 The UPS bypass switch must be installed within sight of the UPS.
Electrical Installation NOTE 1 NOTE 3 NOTE 2 NOTE 3 NOTE 2 NOTE 3 NOTE 3 NOTE 7 NOTE 4 NOTE 5 NOTE 7 110/220 Input, 110/220 Output 120/208 Input, 120/208 Output 120/240 Input, 120/240 Output 100/200 Input, 100/200 Output 127/220 Input, 127/220 Output NOTE 6 Figure 28.
Electrical Installation NOTE 1 NOTE 3 NOTE 2 NOTE 3 NOTE 2 NOTE 3 NOTE 3 NOTE 7 NOTE 4 NOTE 5 NOTE 7 208 Input, 208 Output 220 Input, 220 Output 230 Input, 230 Output 240 Input, 240 Output NOTE 6 Figure 30. External Bypass Switch (L1, L2), Non-Isolated Output, and Universal Power Modules NOTE 1 NOTE 3 NOTE 3 NOTE 5 NOTE 7 NOTE 7 208 Input, 208 Output 220 Input, 220 Output 230 Input, 230 Output 240 Input, 240 Output NOTE 6 Figure 31.
Electrical Installation NOTE 1 NOTE 3 NOTE 2 NOTE 3 NOTE 2 NOTE 3 NOTE 3 NOTE 7 NOTE 4 NOTE 5 NOTE 7 220 Input, 220 Output 230 Input, 230 Output 240 Input, 240 Output NOTE 6 Figure 32. External Bypass Switch (L1, N), Non-Isolated Output, and Universal Power Modules NOTE 1 NOTE 3 NOTE 3 NOTE 5 NOTE 7 NOTE 7 220 Input, 220 Output 230 Input, 230 Output 240 Input, 240 Output NOTE 6 Figure 33.
Electrical Installation 42 Powerware® 9170 User's Guide LTM-1344 B Uncontrolled Copy
CHAPTER 5 ISOLATED OUTPUT WIRING DIAGRAMS The wiring diagrams in this section are unique and specific to installations in which the output of the Powerware 9170 UPS is galvanically isolated from the input. Figure 37 through Figure 40 describe output wiring configurations for various output voltages. Use Table 6 to find the desired wiring diagrams and connect the output AC wiring to the proper Powerware 9170 system power terminals.
Isolated Output Wiring Diagrams 50 or 60 Hz 100/200, 110/220, 115/230, or 120/240V Out with Isolated Output Option Parameter 7-3-4 set to 200, 220, 230, or 240, as required. X0 X2 X1 X3 X X X N-G Bond 100, 110, 115, or 120 L1 100, 110, 115, or 120 200, 220, 230, or 240 N L2 Figure 34. Isolated Outputs Single-Phase Voltages 50 or 60 Hz 120/208 or 127/220V Out with Isolated Output Option Parameter 7-3-4 set to 208 or 220, as required.
Isolated Output Wiring Diagrams If there is any question as to the need for this bond wire, contact your local regulatory agency or your service representative. N-G Bond Wire X1 X3 X0 X2 Figure 36.
Isolated Output Wiring Diagrams System Wiring Diagrams The following notes are referenced in the isolated system wiring diagrams (Figure 37 through Figure 40). To determine which diagram is correct for your site, see Table 6 on page 43. NOTE 1 The customer must provide input overcurrent protection as stated in NEC Section 240-21 or local codes. Size the protection device according to local code requirements (see Table 1 on page 26). NOTE 2 The UPS bypass switch must be installed within sight of the UPS.
Isolated Output Wiring Diagrams NOTE 1 NOTE 4 NOTE 2 NOTE 4 NOTE 2 NOTE 3 NOTE 4 NOTE 4 NOTE 5 NOTE 7 NOTE 9 100/200 Input, 100/200 Output 120/208 Input, 120/240 Output (BBM bypass required) 110/220 Input, 110/220 Output 115/230 Input, 115/230 Output 120/240 Input, 120/240 Output NOTE 6 NOTE 9 NOTE 8 Figure 37.
Isolated Output Wiring Diagrams NOTE 1 NOTE 4 NOTE 2 NOTE 4 NOTE 2 NOTE 3 NOTE 4 NOTE 9 NOTE 5 NOTE 4 NOTE 7 NOTE 6 NOTE 9 NOTE 10 NOTE 8 120/208 Input, 120/208 Output 127/220 Input, 127/220 Output Split-phase (Voltages require the bypass switch to be BBM; contact your service representative for details.) Figure 39.
CHAPTER 6 UPS STARTUP This section provides step-by-step instructions for starting your Powerware 9170 system. Follow these procedures closely to avoid potential damage to your equipment or the UPS and to protect yourself and others from hazardous operating conditions. CAUTION This UPS contains its own energy source (batteries). The output receptacles may carry hazardous voltage even when the UPS is not connected to an AC supply.
UPS Startup Power and Battery Module Installation Use the following procedure to install the power and battery modules into the Powerware 9170 cabinet: 1. Remove the front cover(s) of the cabinet. The covers have spring latches on the left and right sides that hold them in place. NOTE Place battery modules below all power modules in the UPS cabinet. Two battery modules (side-by-side) are required to complete each battery string. 2. Insert the battery modules into the cabinet.
UPS Startup Figure 41. Inserting the Modules 5. If you installed an optional battery cabinet, repeat Steps 1 and 2 to install the battery modules. 6. Reinstall the front covers. 7. Continue to the following section, Startup for Plug-Receptacle Units" if your cabinet has a power cord already attached. If you hardwired the UPS, skip to Startup for Hardwired Units" on page 53. Startup for Plug-Receptacle Units To start a plug-receptacle unit, use the following steps: 1.
UPS Startup 3. If you are installing power management software, connect your computer to the UPS communication port using the supplied communication cable. DB-9 Connector for Computer Cable Figure 42. Communication Port 4. The UPS front panel display automatically turns on whenever input power is present and at least one power module is installed. Set up the initial operating parameters through the front panel display (see Initial Startup Parameters" on page 56).
UPS Startup Startup for Hardwired Units To start a hardwired unit, use the following steps: 1. Confirm that an electrician has completed and tested the connection to the proper power source. 2. Check the cable connections between the UPS and any external battery cabinets. 3. Ensure that all power modules are properly installed and latched into the UPS cabinet. 4. If you are installing power management software, connect your computer to the UPS communication port using the supplied communication cable.
UPS Startup 9. Use an AC voltmeter to measure voltages on the terminal block inside the bypass switch cabinet. See Figure 22 on page 32, which shows the terminal numbering for input and output UPS connections. Record your measurements in the following chart. The voltages in the first column should be nearly equal to the voltages in the second column. If the values differ by more than a few volts, check the terminal block connections and correct any wiring problems.
UPS Startup 15. Reinstall all UPS cover panels. 16. If the UPS will not be operated immediately, switch the bypass switch to SERVICE and push the DC disconnect switch on the back panel of the external battery cabinet closest to the UPS. When starting the UPS, apply input power to the UPS by closing the service circuit breaker or turning the bypass switch to the LINE position. If an external battery cabinet is connected, unlock and pull out the DC disconnect switch on its back panel. 17.
UPS Startup Initial Startup Parameters The first time the UPS is turned on, you must set or verify certain operating parameters before placing the UPS into operation. Use the following procedure to set these initial configuration parameters. 1. Enter the correct user security password: 0377. Move left and right by pressing the buttons below the <- and -> on the display. To change the value of the selected digit, press the and buttons. When the password shows 0377, press the button.
UPS Startup 4. The output voltage is the most important operating parameter you must set as part of the initial configuration screens. Select the desired UPS output voltage using the and buttons. Possible selections are 200, 208, 220, 230, and 240 Vac. (Low voltages are derived from these voltages, as listed in Table 5 on page 35 and Table 6 on page 43.) Press the button when the desired output value is displayed. 5.
UPS Startup 7. To password-protect the UPS On/Off function, press the or button to make your selection; then press the button. If a password is required, the UPS On and Off functions are accessible only after first entering the correct password value (0377). ON OFF Password? No ESC 8. The UPS is now ready to operate, and displays the normal On/Off function screen. These configuration parameters are accessible during normal UPS operation by pressing the Config button through the front panel display.
CHAPTER OPERATION 7 The Powerware 9170 UPS operates in several different modes. Normally it operates under internal control, called Auto mode, to automatically protect loads connected to it. It also functions under operator control to enable manual override should servicing or testing be required. Figure 45 is an illustration of the operating modes. In Auto mode, the UPS automatically switches between modes depending on line and load conditions.
Operation The High Efficiency (H.E.) mode is a user-programmable automatic mode of operation. This mode allows power to flow through the internal UPS bypass path for as long as AC input stays within the user-defined setpoints. If the input voltage or frequency deviates beyond these setpoints, the Powerware 9170 system transfers to the Double Conversion mode of operation. Complete loss of input voltage causes the UPS to transfer to Battery mode. While in H.E.
Operation Removing Input Power Always put the Powerware 9170 UPS into the Off mode before removing input power. Powerware 9170 system batteries will discharge if the input line voltage is disconnected or turned off without first turning off the Powerware 9170 UPS. If the input power source will be disconnected or turned off for more than a day or two, you should put the UPS into Sleep mode.
Operation Front Panel Display The front panel has an alphanumeric display, three LED indicators, and six pushbuttons as described in Figure 47 and in Table 7. 1 2 3 4 3 19 Wout watts Slot USER A B Top #3 2.07 KW ESC C Figure 47. UPS Front Panel Table 7. Front Panel Details Item Description 1 Alphanumeric display of unit function and operating parameters. Also displays alarm/data logs. 2 Alarm LED (red). Illuminates to signal that the unit has detected an alarm condition.
Operation Using the Front Panel Display The front panel display shows several important things (see Figure 48). The numbers in the upper left corner (for example, 3 19) are the display location within the operating menu structure. The word in the top center (for example, USER ) is the security level, which allows various operating parameters to be changed. 3 19 Wout watts Slot A USER Top B #2 1.87 KW ESC C Figure 48.
Operation Operating parameters shown on the third line of the display vary depending on the operating mode. As shown in Figure 49, the UPS output voltage is displayed while the Powerware 9170 UPS operational state is ON LINE. Md: AUTO M4–B7–12 St: ON LINE acvout 232 V Config OFF Menu Figure 49. Front Panel Display (Normal Operation) Parameters The parameters describe the Powerware 9170 system operation. Some useful parameters are input and output voltage, input and output current, and battery voltage.
Operation Changing Parameter Settings The method of changing any operating parameter follows the same procedure as setting initial parameters, as described in Initial Startup Parameters" on page 56. Begin by entering the correct password to allow the change. Use the Menu Map (Figure 50 on page 68) to find the parameter you need to change, and move through the menu structure until the parameter name appears on the display.
Operation In this example, the most recent inverter log (9 1 1) is being displayed. If the unit is still running on inverter (battery power), an asterisk (*) is displayed beside the date. 09/29" is the date of the Battery mode operation: September 29. 13:56" means that Battery mode operation started at 1:56 p.m. And 01:04" means the batteries supplied power for 1 hour and 4 minutes. For further information about the entry, hold down .
Operation In this example, the sixth most-recent alarm (9 2 6) is being displayed. A" means the Powerware 9170 system sounded alarm A (Low Battery). If the alarm is still active, an asterisk (*) is displayed beside the letter alarm code. 02/05" is the date the alarm occurred: February 5. 17:51" means the alarm sounded at 5:51 p.m. And 04:35" means the alarm was active for 4 hours and 35 minutes. See Table 9 and Alarms" on page 83 for information about the alarm codes. Table 9.
Operation (Menu) (ESC) 1 Password (ESC) Enter Password 2 System Mode Preference (Top) 3 3 3 3 3 3 3 3 3 4 System Identification (ESC) 4 1 Model Name 4 2 Model Number 43 44 Serial Number 4 5 Date Manufactured 5 Generator Sensitivity (ESC) 5 5 5 5 5 5 5 5 Freq Glitch Count Line Delta Transfer Delay Low AC Out Delay 6 System Diagnostics (ESC) 7 System Control Configuration 7 1 Communication Config (ESC) 3 System Info (ESC) (Top) 1 2 3 4 5 6 7 8 9 1 2 3 4 Unit Time Unit Date Input Fre
CHAPTER 8 COMMUNICATION Powerware offers several methods of communicating with your Powerware 9170 system in addition to the front panel display: CheckUPS II Software RS-232 Communication Optional Interface Kits Relay Card BestLink Telecom Modem Controller Optional Internal BestLink SNMP/WEB Adapter BestDock Communication Slots Dedicated Input Signals CheckUPS II Software Each Powerware 9170 UPS ships with CheckUPS II software and an interface cable.
Communication Optional Interface Kits For computer systems that already have UPS monitoring software, Powerware offers interface cable kits for connecting the Powerware 9170 system to your computer system. The kit includes the cable, adapters, and instructions. Relay Card This interface provides true relay contact output to peripheral devices. Outputs are user-selectable as normally open or normally closed.
Communication Dedicated Input Signals Emergency Power-Off (EPO): Connection to a facility Emergency Shutdown switch provides a method for emergency Powerware 9170 system shutdown. Opening this connection creates an immediate shutdown of the Powerware 9170 UPS output. Bypass: The signal from an external bypass switch, to isolate the Powerware 9170 system for maintenance purposes, tells the UPS to go into Internal Bypass mode.
Communication Pin Function Description 5 Normally-Open Low-Battery-Alarm Contact* A normally open contact that closes (pulls to Common) to signal a Near Low Battery or Low Runtime alarm. Values that affect this contact closure may be user-programmed. 6 Reserved Reserved 7 Immediate Shutdown Mode Set by External Shutdown parameter, n = 0: Grounding this pin for 5 seconds causes the UPS to switch immediately to the Off mode.
CHAPTER 9 MAINTENANCE Routine Maintenance NOTE Technicians must observe important safety precautions while performing these checks. The Powerware 9170 system is designed to provide years of trouble-free operation. Its internal control system checks the batteries and inverter periodically to ensure reliable operation. In fact, you'll probably find that your Powerware 9170 system requires less maintenance than any of your other computer peripherals.
Maintenance Storage Temperature Store the Powerware 9170 battery modules (in the unit or battery cabinet) at 20 to +40°C ( 4 to +104°F). Batteries will have a longer shelf life if they are kept below +25°C (+77°F). The Powerware 9170 UPS or battery cabinet without batteries may be stored at 40 to +60°C ( 40 to +140°F). External Bypass Switch (Make-Before-Break Only) Operation Before turning the Powerware MBB bypass switch, you must press the red button located next to the handle.
Maintenance 4. Press down on the secondary stop release, pull the module out further, and support the module weight with your second hand as you remove the module from the cabinet. Remove the battery module beside the first in a similar manner. 5. After removing a pair (one string) of battery modules, install a replacement pair. Replacements may be installed in empty cabinet slots before removing original battery modules. 6.
Maintenance 4. Insert a replacement module by sliding it carefully into the cabinet. Lower the front down slightly and lift the rear edge over the safety stop on the center support rail. Keep the module handle extended until the module is fully inserted. 5. Push the module in firmly. Raise the power module handle to secure the module into the cabinet. Be sure the handle latch snaps into place. Tighten the thumbscrew on the handle.
CHAPTER 10 SPECIFICATIONS This section provides the following specifications for the Powerware 9170 models: Electrical input and output Isolation Model specifications Environmental and safety Battery Weights and dimensions Table 11.
Specifications Table 12. Isolation Model 0650C Output Neutral-to-Ground Bonding ±3% load regulation (under any line, load, or battery condition) Neutral is carried through from input to output; a separate neutral-to-ground bond is not required Model 0650I Isolation, Including Output Neutral-to-Ground Bonding True, separately-derived power source as defined by National Electrical Code Article 250-5d, with output neutral bonded to ground.
Specifications Table 14.
Specifications Table 16. Weights and Dimensions Cabinet Size Height Width Depth Weight* 3-slot 17.75 (45 cm) 17.0 (43 cm) 25.5 (65 cm) 66 lb (30 kg) 3-slot (with caster cart) 19.5 (49.5 cm) 17.0 (43 cm) 25.5 (65 cm) 78 lb (35 kg) 31.5 (80 cm) 17.0 (43 cm) 25.5 (65 cm) 103 lb (47 kg) 6-slot (with caster cart) 33.25 (84.5 cm) 17.0 (43 cm) 25.5 (65 cm) 115 lb (52 kg) 9-slot 47.0 (119.5 cm) 24.0 (61 cm) 28.5 (72.5 cm) 158 lb (72 kg) 12-slot 60.75 (154.5 cm) 24.
CHAPTER 11 TROUBLESHOOTING The following questions provide a few quick-to-find answers to commonly asked questions. Table 17. Frequently Asked Questions Question: How do I... " Answer Turn the UPS on? Verify that all power modules are securely plugged into the cabinet, and each module handle is latched. Also confirm that the DC disconnect button on the back of the external battery cabinet is closed (pulled out). Turn the optional external bypass switch to the LINE or UPS position.
Troubleshooting Question: How do I... " Answer Check the condition of the batteries? The results of the most recent battery test are stored at menu 6-2. To run a test of battery condition, go to menu 10-1 and press the button. When the test is complete, the results are again stored in menu 6 parameters. Change the battery low-voltage alarm threshold? (or any other alarm or operating limit?) This is one of the parameters that require a trained person, knowing the correct password, to perform.
Troubleshooting Alarms Figure 51 shows a typical alarm display. Alarms are annunciated by a constant Alarm LED and a constant beep. During alarm display, button (A) silences the audible alarm, button (B) clears the alarm display, and button (C) performs the normal Escape function to exit from the alarm display. The button enables you to scroll through all alarms, and the and buttons scroll through any other parameters related to the displayed alarm.
Troubleshooting Table 18 contains descriptions of critical alarm codes. Critical alarms require immediate operator attention and corrective action. Table 18. Critical Alarm Messages Alarm Message What It Means What to Do Low Battery (A) The UPS has shut down after running on battery and discharging the batteries. Wait for AC input power to be restored. When AC input power returns, the UPS begins recharging batteries and applies power to the load.
Troubleshooting Table 19 contains descriptions of non-critical alarm messages. Non-critical alarms are not as urgent as critical alarms, but should be attended to as soon as convenient to avoid the problem becoming critical. Table 19. Non-Critical Alarm Messages Alarm Message What It Means What to Do Near Low Battery (B) The battery voltage has reached the Near Low Battery setpoint. If the voltage increases, the alarm clears automatically. If it drops further, it will cause a Low Battery alarm.
Troubleshooting Alarm Reason Codes Some alarms have a reason code as well as the alarm code. These reason codes may help you to interpret and isolate the cause of an alarm. Table 20 contains a listing of all reason codes along with the associated alarm codes. It also gives an interpretation of the reason, and a suggested corrective action. Table 20.
Troubleshooting Service and Support If you have any questions or problems with the UPS, call your Local Distributor or the Help Desk at one of the following telephone numbers and ask for a UPS technical representative.
Troubleshooting 88 Powerware® 9170 User's Guide LTM-1344 B Uncontrolled Copy
*LTM1344B* LTM-1344 B 90 Powerware® 9170 User's Guide LTM-1344 B Uncontrolled Copy 90