9315 Uninterruptible Power Supply 200 kVA -- 300 kVA Operation Manual 164201036 Rev.
-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- IMPORTANT SAFETY INSTRUCTIONS Instructions Importantes Concernant La Sécurité SAVE THESE INSTRUCTIONS Conserver Ces Instructions This manual contains important instructions for your Uninterruptible Power Supply (UPS) system.
Table of Contents 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Using This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . For More Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Getting Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 2 2 2 Getting Started . . . . . . . . . . . . . . . . . . . . .
iv 4 Starting and Stopping the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Using the Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . To Place the UPS in Normal Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . To Shut Down the UPS from Normal Mode . . . . . . . . . . . . . . . . . . . To Start the UPS in Bypass Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . To Shut Down Power to the Critical Load While in Bypass Mode . . . .
System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . System Configuration Mode Main Menu . . . . . . . . . . . . . . . . . . . . . . Program Building Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Enable/Disable Default Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . Customize Alarm Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Program Unit Name . . . . . . . . . . . . . . . . . . . . .
vi 11 Responding to System Events . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 System Event Horns . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . System Event Lights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . System Event Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 79 80 12 Using the LOAD OFF Pushbutton . . . . . . . . . . . . . . . . . . . . . . . .
List of Figures Figure 1. Typical Powerware Plus UPS System . . . . . . . . . . . . . . . . . . . . . 3 Figure 2. Main Elements of the UPS System . . . . . . . . . . . . . . . . . . . . . . . 4 Figure 3. Path of Current Through the UPS in Normal Mode . . . . . . . . . 10 Figure 4. Path of Current Through the UPS in Bypass Mode . . . . . . . . . 11 Figure 5. Path of Current Through the UPS in Battery Mode . . . . . . . . . 12 Figure 6. Location of the Monitor Panel and the Control Panel . . .
List of Tables viii Table 1. Optional Monitoring Accessories . . . . . . . . . . . . . . . . . . . . . . . . 33 Table 2. Pin Assignments for Port 1 (DE---9) . . . . . . . . . . . . . . . . . . . . . . 41 Table 3. Pin Assignments for Port 2 (DB---25) . . . . . . . . . . . . . . . . . . . . . 42 Table 4. Options Available for Each Communication Port . . . . . . . . . . . 44 Powerware 9315 (200 kVA ---300 kVA) Operation 164201036 Rev.
Introduction Congratulations on your purchase of a Powerware 9315 Uninterruptible Power Supply! The Powerware 9315 online power protection can be utilized to prevent loss of valuable electronic information, minimize equipment downtime, and/or minimize the adverse effect on equipment production due to unexpected power problems.
For More Information This manual describes how your UPS system works. For more information about your system, refer to the following: 164201037 Powerware 9315 (200 kVA ---300 kVA) UPS Installation This manual contains the following information: · How to prepare your site and plan for installation · Detailed step-by-step procedures for installing each component of your system · Detailed illustrations of cabinets and optional accessories, including dimensions and connection points.
Getting Started Each component of the UPS system is housed in a free-standing cabinet designed for industrial or computer room applications. The cabinets match in style and color, and have safety shields behind the doors for hazardous voltage protection. Figure 1 shows a typical Powerware 9315 UPS system. UPS CABINET BATTERY CABINET (optional) INPUT CABINET OUTPUT TRANSFORMER (optional) PDM CABINET (optional --requires 480/208 transformer) Figure 1.
Looking Inside the UPS The Powerware 9315 is a continuous duty, solid-state UPS that supports the following equipment: process control, data processing, telecommunications/PBX, research, and medical. The Powerware 9315 maintains power to the critical loads during commercial electrical power brownout, blackout, overvoltage, undervoltage, and out-of-tolerance frequency conditions. In this manual, the power required by your equipment is called the critical load.
UPS Standard Features The UPS has many standard features that provide cost-effective and consistently reliable power protection: Monitor Panel The Monitor Panel on the front of the UPS contains an LCD screen to display the current status of the UPS. You can view a statistical history and log of UPS events and display a real-time graphic representation of power flowing through the UPS components. Backlit status indicators show the operating mode of the UPS and alert you to system events.
Installation Features Power wiring can be routed through the top or bottom of each UPS cabinet. External sensing and monitoring control wire must be installed in accordance with Class 2 wiring methods. Bottom entry is provided for Class 2 wiring.
Output Transformer An optional 480/208 VAC output auto transformer provides a 208 VAC output for applications that require 208 VAC. The transformer is contained in a separate cabinet. Modem An optional modem is available for use with the UPS Remote Notification feature described in Chapter 8, “Remote Notification”. Refer to the manual supplied with the modem for modem operating instructions. Customer Convenience Outlet An uninterruptible 120VAC, 0.
Symbols, Controls, and Indicators These symbols may appear on your UPS system or on labels inside the UPS. They are accepted by most international safety agents. Everyone in your organization who works with your UPS should understand the meaning of these symbols: ON The principal power switch is in the “On” position. OFF The principal power switch is in the “Off” position. PHASE The word “phase.” CAUTION: REFER TO MANUAL Stop and refer to the Operator’s Manual for more information.
Understanding UPS Operation Your UPS functions automatically to supply AC electrical power to your critical load. The UPS always operates in one of three modes: · In Normal mode, the critical load is supplied by the inverter, which derives its power from rectified utility AC power. In this mode, the rectifier also provides charging current for the battery. · In Battery mode, the battery cabinet provides DC power, which maintains inverter operation. The battery supports the critical load.
Normal Mode In Normal mode, utility AC power is supplied to the rectifier. The rectifier supplies DC power to the inverter, which then supplies the critical load with AC power. The rectifier also provides charging power to the battery. The battery charge condition is monitored by the UPS and reported by a status indicator on the Monitor Panel. The message “System Normal” appears in the status area of the LCD screen.
Bypass Mode The UPS automatically switches to Bypass mode if it detects an overload, load fault, or internal failure. The bypass source supplies the commercial AC power to the load directly. CAUTION: The critical load is not protected while the UPS is in Bypass mode. Figure 4 shows the path of electrical power through the UPS system when the UPS is operating in Bypass mode.
Battery Mode The UPS transfers to Battery mode automatically if a utility power outage occurs, or if the utility power does not conform to specified parameters. In Battery mode, the battery provides emergency DC power that the inverter converts to AC power. When the UPS switches to Battery mode, the alarm indications depend on the cause and condition of the battery charge. The length of time the system can operate in Battery mode depends on loading and the battery supply capacity.
Monitoring and Controlling UPS Operation After you start the UPS, no operator intervention is necessary except for periodic checks of the UPS status. Manual operation is required only during routine maintenance or service. Use the Monitor Panel and the Control Panel to monitor and control the UPS. Figure 6 shows the location of these two panels on the front of the UPS. CONTROL PANEL MONITOR PANEL Figure 6.
This Page Intentionally Left Blank. 14 Powerware 9315 (200 kVA ---300 kVA) Operation 164201036 Rev.
Starting and Stopping the UPS This chapter describes how to use the Control Panel to start and stop the UPS. NOTE: Before starting the UPS, ensure all installation tasks are complete and a preliminary startup has been performed by authorized service personnel. The preliminary startup verifies all electrical interconnections to ensure the installation was successful and the UPS system operates properly. Using the Control Panel The Control Panel (see Figure 7) is inside the right door of the UPS cabinet.
The following describes the switches on the Control Panel (see Figure 7): · The MODE switch is a two-position rotary switch that controls the manual transfer of the UPS to and from Bypass mode. The MODE switch is used to: --- Place the critical load in Bypass mode when the UPS is operating in Normal mode and the bypass source is within acceptable limits. If the transfer does not occur within 2 seconds, an alarm sounds. --- Prevent transfer to Normal mode when the UPS is in Bypass mode.
To Shut Down the UPS from Normal Mode: 1. Turn the MODE switch to BYPASS. The UPS switches to Bypass mode. If the bypass source is not available, the power processor remains on and an alarm sounds. 2. When the transfer is complete (the LCD screen reads “On Bypass”), move the CB1 switch to OFF. The bypass source supplies the critical load and the power processor de-energizes. The Bypass mode indicator illuminates on the Monitor Panel.
This Page Intentionally Left Blank. 18 Powerware 9315 (200 kVA ---300 kVA) Operation 164201036 Rev.
Using the Monitor Panel This chapter describes the Monitor Panel and how to monitor and control UPS operation. The Monitor Panel is a black rectangular area on the front of the UPS (see Figure 8). Figure 8. UPS Monitor Panel The Monitor Panel contains a flat liquid crystal display (LCD) screen (1), a horizontal row of pushbuttons (2), a vertical column of backlit status indicators (3), and the red LOAD OFF pushbutton (4).
Using the LCD Screen The LCD screen at the top of the Monitor Panel provides an operator interface with the UPS. Figure 9 identifies the display fields discussed in the following sections. Uninterruptible Power System A B C D 04 MAY 1997 System Normal Alarm: None Notice: None Battery Percent 100% Input VAB 480 VCA 480 FREQ 60.0 IB 480 IC 480 KVA 399 KW 379 PF 0.95 VAB 480 VBC 480 VCA 480 FREQ 60.0 IA 361 IB 361 IC 361 IN 000 KVA 300 F G Output IA 480 KW PF 240 0.
G The information area contains data about UPS status and operations. display statistics or graphics. Select a menu option to You can use the LCD screen and the pushbuttons beneath it to: · Monitor UPS operation · Look at a log of UPS events (alarms, notices, and commands).
Reading the Status Indicators The six symbols on the left side of the monitor panel are status indicators. They are backlit by colored light emitting diode (LED) lamps, and they work in conjunction with the alarm horn to let you know the operating status of the UPS. Normal This green symbol is lit when the UPS is operating in Normal mode. The power processing unit (PPU) is supplying power to the critical load. Battery This yellow symbol is lit when the UPS is operating in Battery mode.
Using the Menu Options The UPS menus allow you to display data in the information area to help you monitor and control UPS operation. The following menus and options are available: · · Meters Displays UPS performance meters for the system or critical load. Events Displays the list of Active System Events and a historical log of system events. · Statistics Displays statistical information about UPS operations for the battery, load, or line.
Select Load Amps from the Meters menu to see a real-time bar graph of the output current of the UPS. The graph shows the current for each phase. Figure 11 shows the Load Amps Meters screen. Uninterruptible Power System 04 MAY 1997 System Normal Alarm: None Notice: None Battery Percent 100% 14:23:45 Output Current 125% 100% 75% Meters 50% System Load Amps 25% 0% Phase A Meters Events Statistics Graphics Phase B Phase C Setup Figure 11.
Select History from the Events menu to display the Event History Log. The Event History Log lists up to 400 system events in chronological order, with the most recent event listed last. The end of the log (the most recent events) appears when you display the screen, and you must scroll upward to view older event listings. Figure 12 shows the Event History Log screen.
Select Active from the Events menu to display a listing of all system events that are currently active. The most recent system event is listed first. As events clear, they are removed from the Active System Events listing. Figure 13 shows the Active System Events screen. Uninterruptible Power System 04 MAY 1997 Alarm: On Battery Notice: None Battery Minutes 001.
Select Unit from the Statistics menu to display a listing of statistics about UPS operation. Figure 14 shows the Unit Statistics screen. Uninterruptible Power System 04 MAY 1997 UPS System Normal Alarm: None Notice: None Battery Percent 100% Statistics Unit Meters Start Date: 14:23:45 04 MAY 1997 Number of Incidents: Month Total Time On: DAYS HR MN On Battery < 1 Min. On Battery 1-4 Min. On Battery > 4 Min. Full Batt.
Select Mimic from the Graphics menu to display a real-time graphical representation of the flow of current through the UPS. Figure 15 shows the Mimic screen. Uninterruptible Power System 04 MAY 1997 UPS System Normal Alarm: None Notice: None Battery Percent 100% 14:23:45 Bypass CB1 K3 Rectifier Inverter Graphics K2 Mimic Battery Meters Events Statistics Graphics Setup Figure 15. Mimic Screen The Mimic screen shows the internal components of the UPS cabinet.
Select Time from the Setup menu to display the Time Setup screen. The Time Setup screen allows you to set the internal timestamp of the UPS. The timestamp is used for logging events in the Event History Log. Figure 16 shows the Time Setup screen. Uninterruptible Power System UPS System Normal Alarm: None Notice: None 04 MAY 1997 Battery Percent 100% 14:23:45 Set Time & Date DAY DT MON YR HR:MN SAVE MON 07 APR 97 15:06 YES Setup Port 1 Port 2 Time Meters Events Statistics Graphics Setup Figure 16.
Select Port 1 or Port 2 from the Setup menu to display one of the Port Setup screens. The Port Setup screens allow you to specify settings for the two serial communication ports on the UPS. Figure 17 shows the Setup Serial Port 1 screen.
Using Features and Options The many standard features of your UPS provide consistent, economical, and dependable power protection. In addition, you can add available options and accessories to enhance the performance of your UPS system. This chapter provides detailed descriptions of some of the features and options introduced earlier in this manual. Building Alarm Monitoring This standard feature lets you connect the UPS to your building alarms, such as smoke detectors or overtemperature alarms.
Summary Alarm Contacts Two summary alarm contacts are provided as a standard feature on the UPS. The alarm contacts (one notice and one alarm) are located inside the UPS on the customer interface panel (see Figure 19). TB2 ALARM NC 10 ALARM NO 11 COMMON 12 NOTICE NC 13 NOTICE NO 14 COMMON 15 Figure 19. Summary Alarm Contacts You can specify that each contact be either normally closed (NC) or normally open (NO).
Remote Monitor Panel As an option, you can install Remote Monitor Panels (RMPs) to monitor the operation of the UPS system from virtually any location within your facility, up to 500 feet from the UPS. Each RMP contains backlit status indicators and a local horn. You can flush-mount or surface-mount an RMP on a desktop, wall, or wherever you have a serial interface line. A maximum of two monitoring accessories (RMPs, Relay Interface Modules (RIMs), or Supervisory Contact Modules (SCMs)) can be installed.
The RMP contains a local horn and the following backlit status indicators: SYSTEM NORMAL The UPS is energized (either with utility power or battery backup) and is supplying conditioned power to the critical load. NO REDUNDANCY This indicator applies only to parallel systems when one cabinet is not functioning. This feature is not available on this system. ON GENERATOR This alarm means that the UPS input and bypass are being supplied by the power from the generator, instead of from the utility power.
Battery Cabinets You can enhance the protection time provided by your UPS by adding one or more battery cabinets. The battery cabinets provided by the UPS manufacturer are equipped with sealed lead-acid, maintenance-free batteries in a cabinet that matches the UPS. Each battery cabinet contains a battery circuit breaker. Several battery capacities are available. The UPS battery cabinets can be paralleled.
Relay Interface Module An optional Relay Interface Module (RIM) uses relay contact closures to indicate the operating status and alarm condition of the UPS system. A maximum of two monitoring accessories (RMPs, RIMs, or SCMs) can be installed. See Table 1 for the number of accessories permitted. Figure 21 shows the RIM with its four 15-pin connectors labeled J1 through J4. Figure 21.
Supervisory Contact Module An optional Supervisory Contact Module (SCM) establishes an interface between the UPS manufacturer’s equipment and the customer’s monitor. This interface allows the customer to monitor operational status of the UPS equipment. A maximum of two monitoring accessories (RMPs, RIMs, or SCMs) can be installed. See Table 1 for the number of accessories permitted. Figure 22 shows the SCM, input connections on TB1, and output connections on TB2. TB2 Figure 22.
This Page Intentionally Left Blank. 38 Powerware 9315 (200 kVA ---300 kVA) Operation 164201036 Rev.
Serial Communications This chapter describes the serial communications feature of the Powerware 9315 UPS. Two serial communications ports on the UPS let you connect equipment to view system event information. The following sections describe the serial communications feature, and provide information about connecting hardware, setting up the ports, changing settings, and changing modes. Powerware 9315 (200 kVA ---300 kVA) Operation 164201036 Rev.
Locating the Communications Panel The Communications Panel inside the UPS contains two serial communications ports, one DE---9 and one DB---25. The ports provide a computer interface to a Remote Monitor Panel (RMP), Relay Interface Module (RIM), or remote terminal and/or printer. The Communications Panel also contains terminals (TB1 and TB2) for connecting your equipment to the UPS. Figure 23 shows the location of these items inside the UPS.
Connecting Equipment to a Serial Port You can connect a wide variety of terminals, printers, and computers to each port, and configure the UPS as the Data Communication Equipment (DCE). Set up the remote equipment using the appropriate parameters for the mode you select. The following section provides more information about configuration. The cables you use for connection depend on the equipment you are connecting to the UPS. Cables should be no longer than 16m (50 ft).
PORT 2 (DB--25) GND 1 RS232 TXD 2 RS232 RXD 3 RS232 RTS 4 RS232 CTS 5 RS232 DSR 6 RTN 7 +12V NOT USED NOT USED 8 9 10 NOT USED 11 NOT USED 12 NOT USED 13 14 NOT USED 15 NOT USED 16 NOT USED 17 NOT USED 18 NOT USED 19 NOT USED 20 RS232 DTR 21 22 23 24 25 NOT USED --12V NOT USED NOT USED NOT USED Figure 25. Port 2 Pin Assignments Table 3.
Configuring the Serial Ports You must configure the port for communications using the LCD screen and pushbuttons on the UPS Monitor Panel. Select Port 1 or Port 2 from the Setup menu to display one of the Setup Port screens. The screens for Port 1 and Port 2 are identical, and allow you to specify settings for the two serial communication ports. Figure 26 shows the Setup Serial Port 1 screen.
Table 4 shows which options are available for each port. The sections that follow describe the configuration settings you can change. Table 4.
Data/Stop The data size and stop bits of the equipment connected to this port. These settings determine the number of bits transmitted per ASCII character. The data size and stop bits you specify depend on the configuration of your equipment. For Port 1, the data size must be set to 8, with 1 or 2 stop bits. Settings of 7 data bits/1 stop bit and 7 data bits/2 stop bits are available for Port 2.
Terminal Mode In this mode, system events are continually logged through the serial port to the device connected to the port. Port 2 operates by default in Terminal mode. The printed log entries contain a time and date stamp and the alarm text message. Terminal mode uses this format for printing alarm entries: MMM DD HH:MM:SS.
Entire Log (Ctrl + P) This key sequence prints the entire Event History Log of the UPS at the time the data is requested. The printout begins with the oldest alarm entry in the queue and ends with the most recent. Any alarms that occur while the Event History Log is printing are included in chronological order. The Event History Log lists up to 400 system events in chronological order with the most recent event listed last. Figure 27 shows a sample Event History Log printout.
Meters Printout (Ctrl + M) This key sequence prints the current readings of the UPS system meters. The Input area shows the phase-to-phase voltage, frequency, and phase current of the incoming utility, followed by the kVA, kW, and power factor measurements. The output area shows the same information for the power being output by the UPS. The Bypass area shows the phase-to-phase voltage of the bypass source. The Battery area displays the DC voltage (V) and the DC current (I).
Battery Test Printout (Ctrl + B) This key sequence prints the Battery Test Log. The log consists of a history of the last 30 battery tests that were run and the results of those tests. The most recent test will appear at the bottom of the log. Figure 29 shows a sample of the Battery Test Log. Uninterruptible Power System UPS # 1 UPS System Normal Alarm: None Notice: None Battery Test Log Date/Time Volts Health AUG SEP OCT NOV DEC JAN FEB MAR APR 1.00 1.00 1.00 0.99 0.99 0.98 0.98 0.00 0.
System Configuration The System Configuration mode allows you to modify special functions in your UPS. These functions include programming of building alarms, customizing building alarm messages, adjusting the nominal output voltage, and scheduling battery tests. The menus provided and their function are described in this section.
Enable/Disable Default Functions From this menu you may either enable the building alarms for general functions or special functions such as On Generator, Go To Bypass, and Go To UPS. You may also customize the alarm messages from this menu. When 1 is selected from this menu, the following menu is displayed: Enable/Disable Default Functions 1. Enable/Disable Go To Bypass 2. Enable/Disable Go To UPS 3. Enable/Disable On Generator 4. Enable/Disable Building Alarm 5.
Customize Alarm Messages If Customize Alarm Messages is selected from the Program Building Alarm menu, you can select a custom message for a building alarm or disable a previously enabled building alarm custom message. When this entry is selected, the following menu is displayed: Customize Alarm Messages Enabled on Building Alarm Number(s) 23 Enter Building Alarm Number: This example indicates that there are custom messages enabled for Building Alarms 2 and 3.
Adjust Output Voltage If Adjust Output Voltage is selected from the main menu, the following menu is displayed: Adjust Output Voltage Output Voltage Setup: 480 Output Voltage Range: 456 --- 504 Enter Desired Output Voltage Setup: The output voltage desired can then be entered or a carriage return for no change. Only values within the range will be accepted.
Battery Test Setup If Battery Test Setup is selected from the main menu, the following menu is displayed: Battery Test Setup 1. Setup One-time Delayed Battery Test 2. Setup Monthly Battery Test 3. Setup Quarterly Battery Test 4. Cancel Pending Battery Test 5. Display Next Scheduled Battery Test 6. Return to Main Menu Enter Selection: This menu allows you to schedule, review schedule, or cancel pending battery tests.
Modify Low Battery Time This menu allows you to modify the low battery time warning. When selected, the following menu will be displayed: Modify Low Battery Time Low Battery Time (Minutes): 004 Enter New Low Battery Time: NOTE: Low Battery Time should be no greater than 999. Enter to return with no change. Enter the new time desired to change the warning level. Calibration Mode Calibration mode is used by factory and field service personnel to calibrate system meters.
This Page Intentionally Left Blank. 56 Powerware 9315 (200 kVA ---300 kVA) Operation 164201036 Rev.
Remote Notification Remote Notification provides the user with the option of receiving alarms and notices at a remote location. Remote Notification also provides some basic controls that can be performed remotely on the UPS. Remote Notification operates through a standard computer modem. Using the Terminal mode, the user calls the UPS to perform basic monitoring and control. In the event of a UPS alarm or notice, the user is notified at the remote location.
Remote Notification Features Remote Notification provides the UPS with the capability to utilize a standard off-the-shelf PC modem as a telephone interface. The features provided by this option are as follows: 58 · Call out to a remote terminal or pager based on programmable events and alarms. · Two separate, programmable notification groups (phone numbers). · Programmable number of redial attempts. · Programmable time delay between call out attempts.
Description of Operation The Remote Notification option performs three basic functions: Call Answer into Terminal mode, Call Out to a remote terminal, and Housekeeping. Remote Notification also allows access to any functions available in the Terminal mode from a remote computer or terminal. Call Answer To use the Call Answer function, the modem is configured to automatically answer by having the user program the S0 register of the modem to a non-zero number.
· The UPS logs a successful notify to the event log when the remote computer or modem answers and leaves an event message with the following format.
Hardware Requirements The following hardware components are required to connect the Remote Notification function. · Modem: Basic external PC modem supporting the following AT commands. E0 M0 N0 Q0 V0 X0 &A0 &D0 &K0 &Q5 --------------------- Do not echo characters in command state. Turn speaker off. Handshake only at speed specified by S37. Return result codes in both originate and answer mode. Display result codes as numbers. Provide basic result codes: CONNECT, NO CARRIER, and RING.
Configuring the Modem The modem must be configured by the user before connecting to the UPS. In addition, the modem must be programmed with the Call Out telephone numbers in order to operate the Remote Notification option. To configure the modem, connect the serial port of a standard PC computer to the modem through the serial cable. Run a terminal emulation program on the computer. Test the connection to the modem by typing [A], [T] and [ENTER]. The modem should respond with either “OK” or “0” (zero).
Configuring the Modem to Call a Remote Computer To configure the modem to call a remote computer, perform the following procedure: NOTE: Perform this procedure only after completing “Basic Modem Configuration” section of this chapter. The brackets ([ ]) in the following steps indicate characters that require keying in prior to pressing [ENTER]. 1. Connect the modem to the PC through the serial port as described in the modem manufacturer’s manual . 2. Key in [A], [T], then press [ENTER]. 3.
Configuring the Modem to Call a Numeric Pager To configure the modem to call a numeric pager system, perform the following procedure. NOTE: Perform this procedure only after completing “Basic Modem Configuration” section of this chapter. The brackets ([ ]) in the following steps indicate characters that require keying in prior to pressing [ENTER]. 1. Connect the modem to the PC through the serial port as described in the modem manufacturer’s manual . 2. Key in [A], [T], then press [ENTER]. 3.
Configuring the Modem to Answer Incoming Calls To configure the modem to answer incoming calls, perform the following procedure. NOTE: Calling into the UPS does not present any type of security risk. There are no commands that can be executed via the call-in feature except those available to the Terminal mode. 1. Connect the modem to the PC through the serial port as described in the modem manufacturer’s manual .
Final Modem Configuration The final step in configuring the PC modem for use with the UPS is to turn off the echo feature of the modem. Perform the following procedure. NOTE: The brackets ([ ]) in the following steps indicate characters that require keying in prior to pressing [ENTER]. 1. Connect the modem to the PC as described in the modem manufacturer’s manual. 2. Key in [A], [T], then press [ENTER]. 3. Confirm that the modem responds with “OK” or “0” (zero). 4.
UPS Setup Configuration Connect the modem to the UPS by connecting one end of the serial cable to the UPS Port 2 DB---25F connector and the other to the modem (refer to Chapter 7, “Serial Communications”). If using a standard serial cable, a null modem adapter is required for the connection to the modem. The Powerware 9315 UPS can only use serial Port 2, DB---25F, for the Remote Notification option.
User-Selected Events Insert a check at each alarm or notice in the appropriate Group 1 or Group 2 block to indicate the configuration of your UPS. INVERTER MESSAGES -ALARMS Group 1 Group 2 INVERTER MESSAGES -NOTICES Inverter AC Over Voltage Inverter AC Under Voltage Inverter Calibration Required Inverter Contactor (K3) Failed Inv.
RECTIFIER MESSAGES -ALARMS Group 1 Group 2 RECTIFIER MESSAGES -NOTICES Input Phase Rotation Battery Test Failed Over Temperature DC Voltage High Over Temperature Warning DC Voltage Low Rectifier Calibration Required Rectifier DC Over Voltage Rectifier DC Under Voltage Rectifier Failure Equalizing Battery Rectifier Setup Required Temperature Sensor Failure Input Transient Group 1 Group 2 Input AC Over Voltage Input AC Under Voltage Input Over Frequency Input Under Frequency Input/Battery Cur
MONITOR MESSAGES -ALARMS Battery Test Failed Battery Test Failed Fan Failure Load Over 100% Load Over 125% Group 1 Group 2 MONITOR MESSAGES -NOTICES Battery Passed Test Group 1 Group 2 Battery Test Aborted (load) Battery Test Aborted (utility) Battery Test Requires Calibration Battery Time Low Monitor Calibration Required Monitor Setup Required Overload Warning Building Alarm 1 Active Power Supply Failure Building Alarm 4 Active Building Alarm 2 Active Building Alarm 3 Active Building Alarm 5 Act
Maintaining the UPS System The components inside the UPS cabinet are secured to a sturdy metal frame that is supported by the UPS magnetics. This design allows authorized service personnel to remove repairable components with very little disassembly. All repairable parts and assemblies are located in the front of the UPS, allowing all routine maintenance and servicing to be performed with front panel access. You must schedule periodic performance checks of your UPS to keep it running properly.
Observe these precautions when working on or around battery cabinets: · Remove watches, rings, or other metal objects. · Use tools with insulated handles. · Wear rubber gloves and boots. · Do not lay tools or metal parts on top of batteries or battery cabinets. · Disconnect the charging source prior to connecting or disconnecting terminals. · Determine if the battery is inadvertently grounded. If it is, remove the source of the ground.
Performing Preventive Maintenance The UPS requires very little preventive maintenance. However, the UPS should be inspected periodically to verify that the unit is operating normally and that the batteries are in good condition. Perform the following checks DAILY: · Check the area surrounding the UPS. Ensure the area is not cluttered, allowing free access to the unit. · Ensure the air intakes (vents on the front doors) and exhaust opening (on top of the UPS cabinet) are not blocked.
This Page Intentionally Left Blank. 74 Powerware 9315 (200 kVA ---300 kVA) Operation 164201036 Rev.
Product Specifications The UPS systems are housed in freestanding, double-front cabinets with safety shields behind the doors. The UPS systems are available in both 50 Hz and 60 Hz, with various output power ratings.
System Output Rectifier/Charger Capacity 125% DC Filtering Ripple voltage less than 0.5% peak to peak UPS Output Capacity 100% rated current at 0.
Environmental Specifications Operating Temperature 0 to 40˚C without derating. However, operating at or near 40˚C will adversely affect battery life (refer to your battery specifications for more information). The recommended operating temperature is 25˚C.
This Page Intentionally Left Blank. 78 Powerware 9315 (200 kVA ---300 kVA) Operation 164201036 Rev.
Responding to System Events When the UPS system is running in Normal mode, it continually monitors itself and the incoming utility power. In Battery or Bypass modes, the UPS may issue alarms to let you know exactly what event caused the change from Normal mode. System events can be indicated by horns, lights on the UPS, or both. Select Active from the Events menu on the LCD screen to look at the Active System Events screen. This screen shows any currently active alarms, notices, or commands.
System Event Messages When a system event occurs, a message is added to the Event History Log. A message may also appear on the Monitor Panel of the UPS. The Event History Log contains all system event messages, whether or not they were displayed on the Monitor Panel.
INVERTER MESSAGES -COMMANDS INVERTER STATUS MESSAGES Bypass Mode Normal Mode Inverter On Inverter Off Keyswitch On Battery Contactor (K2) Closed Battery Contactor (K2) Open Inverter Commanded On Inverter Commanded Off Total Battery Discharge Bypass Contactor (K4) Closed Bypass Contactor (K4) Opened Input Breaker (CB1) Closed Input Breaker (CB1) Opened Inverter Contactor (K3) Closed Inverter Contactor (K3) Opened Inverter Shutdown Inverter Normal Load Transferred to Bypass Auto Mode RECTIFIER MESSAGE
RECTIFIER MESSAGES -COMMANDS Rectifier Commanded On Rectifier Commanded Off RECTIFIER STATUS MESSAGES Rectifier On Rectifier Off Rectifier Shutdown MONITOR PANEL ALARMS Load Over 100% Clear Load Over 100% Overload 100% Clear Overload 100% Overload 125% Clear Overload 125% Power Supply Failure Clear Power Supply Fail. Fan Failure Clear Fan Failure MONITOR PANEL NOTICES Output AC Over Voltage Clear Output AC Over Voltage Output AC Under Voltage Clear Output AC Under Voltage Output Over Freq.
Using the LOAD OFF Pushbutton Load Off is initiated by the covered, red LOAD OFF pushbutton on the Monitor Panel. This pushbutton is protected by a clear plastic shield to prevent accidental activation. In an emergency, you can press this pushbutton to instantaneously open the input breaker and interrupt UPS output. The UPS is cut off from utility power, and your critical load is de-energized. All power to the critical load is lost.
This Page Intentionally Left Blank. 84 Powerware 9315 (200 kVA ---300 kVA) Operation 164201036 Rev.