Corporation Uninterruptible Power Supply Operation Manual 200 kVA -- 300 kVA

50
Powerware 9315 (200 kVA---300 kVA) Operation
164201036 Rev. D 041500
System Configuration
The System Configuration mode allows you to modify special functions in your
UPS. These functions include programming of building alarms, customizing
building alarm messages, adjusting the nominal output voltage, and scheduling
battery tests. The menus provided and their function are described in this section.
System Configuration Mode Main Menu
When the System Configuration mode is selected with a terminal attached, you will
be prompted to enter the password for this mode:
Please Enter Password:
The default password is EXIDE1. You may modify this password using the change
password function in the following menu. When the valid password is entered, the
main menu will be displayed:
Program Mode Main Menu
1. Program Building Alarms
2. Program Unit Name
3. Adjust Output Voltage
4. Change Password
5. Battery Test Setup
6. Modify Low Battery Time
7. Exit Program Mode
Enter Selection:
Program Building Alarms
This menu provides access to all the functions available in the system configuration
mode. If 1 is entered at the prompt, you can program the building alarm functions:
Program Building Alarms
1. Enable/Disable Default Functions
2. Customize Alarm Messages
3. Return to Main Menu
Enter Selection: