335 9 Uninterruptible Power Supply 80 kVA and 120 kVA Installation and Operation Manual 164201396 Rev.
IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for your Uninterruptible Power Supply (UPS) system. You should follow these instructions during the installation and maintenance of the UPS, options, accessories and batteries. This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules.
Table of Contents A Introduction ....................................... Basic System Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . Using This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Conventions Used in This Manual . . . . . . . . . . . . . . . . . . . . . . . Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Getting Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Section II Operation 5 Understanding UPS Operation 5.1 5.2 5.2.1 5.2.2 5.2.3 5.2.4 5.3 5.3.1 5.3.2 5.3.3 5.3.4 5.3.5 5.3.6 Looking Inside the UPS System . . . . . . . . . . . . . . . . . Normal, Battery and Bypass Modes . . . . . . . . . . . . . Normal Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bypass Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Battery Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Maintenance Bypass Mode . . . . . . . . . .
7.3.7 7.3.8 7.3.9 7.4 7.4.1 7.4.2 7.4.3 7.4.4 UPS Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Set-Up User . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Set-Up Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . “ON-LINE” Mode (Inverter Mode) . . . . . . . . . . . . . . . “OFF-LIINE” Mode (BYPASS or ECONOMY Mode) . “MAINTENANCE BYPASS” Mode . . . . . . . . . . . . . .
List of Figures Figure 1 – 1 Figure 4 – 1 Figure 5 – 1 Figure 5 – 2 Figure 5 – 3 Figure 5 – 4 Figure 5 – 5 Figure 6 – 1 Figure 6 – 2 Figure 7 – 1 Figure 7 – 2 Figure 7 – 3 Figure 10 – 1 Figure 10 – 2 Figure 11 – 1 Powerware 9335 (80 kVA and 120 kVA) UPS Cabinet Typical Remote EPO Control Main Elements of the UPS System Path of Current through the UPS in Normal Mode Path of Current through the UPS in Bypass Mode Path of Current through the UPS in Battery Mode Path of Current through the UPS in Maintenance B
List of Tables Table 4 – 1 Remote EPO Wire Terminations Table 4 – 2 Remote EPO Table 10 – 1 Communication Port Pin Assignments vii Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV.
Introduction Powerware 9335 UPS true double conversion online power protection can be utilized to prevent loss of valuable electronic information, minimize equipment downtime, and/or minimize the adverse effect on equipment production due to unexpected power problems. The Powerware UPS System continuously monitors incoming electrical power and removes the surges, spikes, sags, and other irregularities that are inherent in commercial utility power.
Basic System Configurations These basic UPS system configurations are possible: • Single Cabinet UPS with External Battery Cabinet, Single Utility Feed • Single Cabinet UPS with External Battery Cabinet, Dual Utility Feed You can enhance any of these system configurations by adding optional accessories, such as Remote Emergency Power Off (EPO) control and X–Slot communications connectivity features.
Section II – Operation • • • • • • • • • • • Chapter 5 – Understanding UPS Operation – provides information on understanding how your UPS works. Chapter 6 – Operational Controls and Features – describes the standard and optional operational features and controls of the UPS system. Chapter 7 – Using the Control Panel – describes the controls and indicators found on the Control Panel and shows the various information screens displayed on the LCD screen.
Safety Considerations The UPS cabinet is designed for industrial or computer room applications, and contain safety shields behind the doors. However, the UPS system is a sophisticated power system and should be handled with appropriate care, following these guidelines: • Keep surroundings clean and free from excess moisture. • Do not operate the UPS system close to gas or electric heat sources. • The system is not intended for outdoor use.
Section I Installation
This page left intentionally blank
Getting Started 1 1.1 Installing the UPS The complete UPS cabinet is shipped on a single pallet. Use a forklift or a pallet jack, rated to handle the weight of the cabinets (refer to Table J in Appendix A for cabinet weights) to move the packaged cabinet to the installation site, or as close as possible to the site, before unloading from the pallet. This is the basic sequence of the installation steps: 1. Create an installation plan for the UPS system. (Chapter 1) 2.
1.1.2 Preparing Your Site For your UPS to operate at peak efficiency, your installation site should meet the environmental parameters outlined in this manual. If you intend to operate the system at an altitude higher than 1500 meters (5000 feet), contact your local sales or service office for important information about high altitude operation. The operating environment must meet the weight, airflow, size and clearance requirements specified in Appendix A.
1.1.5 Inspecting and Unpacking Each Cabinet The first task in preparing for installation is inspecting and unpacking the UPS. The UPS and accessory cabinets are shipped bolted to wooden pallets, as shown in Figure 1–1, and protected with outer protective packaging material. NOTE: Packed inside the shipping carton on top of the UPS cabinet is an accessory carton containing the metal grilles to be installed at the unit base after it is fixed in the final position.
1. Carefully inspect the outer packaging for evidence of damage during transit. CAUTION: Do not install a damaged cabinet. Report any damage to the carrier and contact your local sales or service office immediately. 2. Use a forklift or other material handling equipment to move the cabinet to a convenient unpacking area. Insert the forklift forks between the pallet supports on the bottom of the unit. CAUTION: Do not tilt cabinets more than ±10 degrees from vertical. 3.
Installing the UPS System 2 2.1 Preliminary Installation Information WARNING: Only qualified personnel should perform installation. All wiring and installation of the UPS system must be done in accordance with the most current NEC standards or local electrical code. Refer to the following while installing the UPS system: • Refer to Appendix A of this manual for installation drawings and additional installation notes. • Dimensions in this manual, unless otherwise noted, are in millimeters and (inches).
2.2 UPS Cabinet Installation To install an UPS cabinet, perform the procedures in the following paragraphs. 2.2.1 Unloading the Powerware 9335 (80 kVA and 120 kVA) UPS Cabinet from the Pallet The UPS cabinet is bolted to a wooden shipping base using two steel angles. To remove the shipping material, perform the following procedure. WARNING: The UPS cabinet is heavy. Refer to Table J in Appendix A for weight of cabinets.
2.2.2 Installing External Battery Power Wiring The Powerware 9335 contains no internal batteries and must therefore be used with an external battery system. The procedure for wiring the battery system to the 9335 is described as follows. Also read the manual provided with the battery system to ensure proper interconnections on the battery side. 1. If not already done, open the UPS cabinet door using the provided operator handle and remove the bottom internal protective panel. Retain hardware.
WARNING: The Powerware 9335 UPS requires a neutral input power connection for proper operation. Internal input and output neutrals are permanently connected inside the cabinet. WARNING: An insulated grounding conductor must be provided per NEC. 4. If the installation is for a single utility feed with common rectifier and bypass input, proceed to step 7. For a separate bypass and rectifier input, proceed to step 5. 5.
2. Remove Customer Interface conduit landing plate from the UPS cabinet. Drill or punch conduit holes for interface wiring. 3. Open UPS cabinet front door and remove the front safety shield panel to gain access to the wire way to bring wires from the conduit landing panel at the bottom rear of the cabinet. 4. Locate required connection points by referring to Figure A–1 in Appendix A. 5. Refer to Appendix A of this manual for wiring and termination requirements. 6.
completed Installation Checklist to be sure you have completed all applicable equipment installation. NOTE: The Installation Checklist MUST be completed prior to starting the UPS system for the first time. 2.5.1 Installation Checklist All packing materials and restraints have been removed from each cabinet. Each cabinet in the UPS system is placed in the installed location. All conduits and cables are properly routed to the UPS and auxiliary cabinets. All power cables are properly sized and terminated.
Installing and Connecting Batteries 3 3.1 Important Safety Instructions The Powerware 9335 UPS does not contain batteries. It must, however, be used with a properly configured battery cabinet or rack with a properly sized battery system for proper operation. The installation of batteries should be performed or supervised by personnel knowledgeable of batteries and their associated precautions. Keep unauthorized personnel away from batteries.
This page left intentionally blank 3-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV A 071103
Installing a Remote EPO Control 4 4.1 Installation Procedures EMERGENCY OFF Figure 4–1. Typical Remote EPO Control 4.2 To Install a Remote EPO: NOTE: Before installing a Remote EPO, be sure you have prepared the UPS according to the instructions in Chapter 2. To Install a Remote EPO control: 1. Securely mount the remote EPO switch. Recommended locations include near operator’s consoles or near exit doors.
Table 4 – 1. Remote EPO Wire Terminations From Remote EPO Switch(s) Refer to switch manufacturers installation instructions To X1 connector on front of inner UPS panel Remarks Twisted wires (2) 1418 gauge X1 - 1 X1 - 2 Table 4 – 2. Remote EPO REMOTE EPO SWITCH (N.C.) TWISTED WIRES (2) X1 UPS Remote EPO switch rating is 24 VDC, 1 Amp maximum NOTE: This switch must be a dedicated switch not tied into any other circuits. 4.
Section II Operation Powerware 9335 (80 kVA and120 kVA) Installation and Operation 164201396 REV.
This page left intentionally blank Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV A 071103
Understanding UPS Operation 5.1 Looking Inside the UPS System 5 The Powerware 9335 is a continuous duty, solid-state, transformerless (at 480 VAC) three phase, true online system that provides conditioned and uninterruptible AC power to the UPS systems output. The UPS supports process control, data processing, telecommunications/PBX, and research equipment.
Maintenance Bypass Switch IA1 Contactor K4 Static Bypass Switch EMI Filter Contactor K1 Input Filter Rectifier Booster Inverter Output filter Output Contactor K2 Output Switch IA2 N EMI Filter EMI Filter Battery Charger Battery Fig. 5–1.
5.2 Normal, Battery and Bypass Modes The UPS system functions automatically to supply AC electrical power to the critical load. There are four standard operation modes. • In Normal mode, the critical load is supplied by the inverter, which derives its power from rectified utility AC power. In this mode, the battery charger also provides charging current for the battery, if needed. • In Battery mode, the critical load is supplied by the inverter which derives its power from the battery DC power.
5.2.1 Normal Mode Figure 5–2 shows the path of electrical power through the UPS system when the UPS is operating in Normal mode. Normal Mode IA1 Static Switch K4 Input Filter K1 Rectifier Booster Inverter K2 IA2 F1 Breaker Contactors Battery Charger Switches Closed Main Power Trickle Current Open Battery Breaker Energized De-Energized Battery Figure 5–2.
The DC boost converter derives power from the unregulated DC rectifier and produces a higher, stable DC voltage and current source for the inverter. A fixed system neutral is also carried through the boost converter to allow full support of single phase AC loads from any phase of the inverter output. The output neutral of the system is connected to the required neutral, both from the main utility supply and the bypass supply and should never be bonded to protective earth ground at the UPS output.
5.2.2 Bypass Mode The UPS automatically switches to Bypass mode if it detects an overload, load fault, or internal failure. The bypass source supplies the commercial AC power to the load directly. Figure 5–3 shows the path of electrical power through the UPS system when operating in the Bypass mode. CAUTION: The critical load is not protected while the UPS is in the Bypass mode.
contactor and together are wired to enable the inverter and rectifier to be bypassed when this path is active. The static switch, as an electronically controlled device, can be turned on immediately to pick up the load from the inverter. The backfeed protection contactor is normally always closed, ready to support the static switch unless the bypass input source becomes unavailable.
5.2.3 Battery Mode The UPS transfers to battery mode automatically if a utility power outage occurs, or if the utility power does not conform to specified parameters. In Battery mode, the battery provides emergency DC power that the inverter converts to AC power. Figure 5–4 shows the path of electrical power through the UPS system when operating in Battery mode.
While in battery mode, the UPS will enunciate an audible horn, indicate the status change on the front panel display with the message “MAINS NOT OK”, and make an entry into the alarm event history. As the battery discharges, the boost converter and inverter constantly make small adjustments to ensure a steady output. The UPS will remain in this operating mode until the input power to the rectifier is again within the specified voltage or frequency acceptance window.
5.2.4 Maintenance Bypass Mode An internal maintenance switch (IA1) is used to safely supply utility power to the system output during periods of maintenance or repairs. Before this switch is used, the system should be transferred to bypass. This switch has two positions: “O” (OFF) and “l” (ON). When switched to “l” (ON), the bypass source supplies the commercial AC power to the load directly.
5.3 Functional Description The UPS is an online double-conversion unit with a series power train. An uncontrolled rectifier feeds a boost converter, which in turn powers the inverter. The internal static bypass utilizes a static switch and an independent maintenance bypass switch is also included internal to the UPS cabinet. The unit input must be 4-wire in (plus ground) at the rectifier and 4-wire in (plus ground) at the bypass.
or constant voltage mode (temperature compensated, available as an option) based on battery condition. All batteries used in conjunction with the Powerware 9335 are external to the UPS cabinet. The internal charger charges the entire battery system, with a maximum current as indicated in Chapter 13, “Product Specifications”. Note that the higher the battery capacity, the longer the recharge time required to fully recharge the batteries. 5.3.
6 Operational Controls and Features 6.1 General The UPS system should function automatically and require very little attention during normal operation. The controls and indicators identified in this section are used during startup to monitor normal operation and during abnormal events. Figure 6–1 identifies and shows the location of the controls and indicators on the Powerware 9335 (80 kVA and 120 kVA) UPS. The descriptions provide a brief overview of the UPS controls, and standard and optional features.
6.2 UPS Operational Controls The UPS has many standard features that provide cost effective and consistently reliable power protection. 6.2.1 Control Panel The Control Panel on the front of the UPS, pictured in Fig. 6–2, contains a LCD screen to display the current status of the UPS system. You can view a statistical history and log of system events and display a real-time representation of power flow through the system components.
6.2.3 Maintenance Bypass Switch An internal Maintenance Bypass Switch is provided to completely isolate the main power processing of the UPS during service. The Maintenance Bypass Switch is described in detail in Chapter 8, “UPS Operating Instructions.” 6.2.4 Cold Start Capability The 9335 UPS system cannot be powered up without a utility input initially present. Accordingly, it is not able to power a load if the system is not started first on utility power. 6.3 UPS Standard Features 6.3.
6.4 Options and Accessories Contact your sales representative for information about any of these available options: 6.4.1 Remote EMERGENCY POWER OFF A REMOTE EMERGENCY POWER OFF pushbutton is an option to provide for situations where you must instantaneously control the UPS output. The operation of the REMOTE EMERGENCY POWER OFF pushbutton is described in detail in Chapter 8, “UPS Operating Instructions.” 6.4.
6.5 Safety Considerations The UPS enclosure is designed for industrial or computer room applications and contains safety shields. However, the system is sophisticated and should be handled with appropriate care, following these guidelines. • Keep surroundings clean and free from excess moisture. • Do not operate the system close to gas or electric heat sources. • The system is not intended for outdoor use.
6.6 Symbols, Controls, and Indicators These symbols may appear on your UPS system or on labels inside the UPS. Most international safety agents accept them. Everyone in your organization who works with your system should understand the meaning of these symbols: PROTECTIVE GROUNDING TERMINAL A terminal which must be connected to earth ground prior to making any other connection to the equipment. A terminal to which or from which a direct current or voltage may be applied or supplied.
7 Using the Control Panel 7.1 Description This chapter describes the UPS Control Panel, including controls and indicators, and how to monitor UPS operation. The control panel is located on the front of the UPS (see Figure 7–1). 2 1 4 LINE 2 BYPASS BATTERY LINE 1 ALARM INV 3 Figure 7–1.
7.2 Using the Control Panel The Control Panel provides an operator interface with the UPS system. Figure 7–2 identifies the display and pushbutton areas discussed in the following sections as well as LED indicators that provide a visual display of system operating status. LINE 2 BYPASS LOAD PROTECTED BATTERY LINE 1 S ON/OFF ALARM INV RESET ON/OFF ENTER Figure 7–2. LCD Screen and Pushbuttons 7.2.
INDICATOR INDICATOR STATUS MEANING ALARM No alarm condition Alarm condition Alarm condition persists Utility supply to rectifier available Utility supply to rectifier not available Bypass supply available Bypass supply not available or not OK Load on bypass (Bypass or Eco-mode) Bypass not operating (or switched off) Load on inverter Inverter fault or load not transferable to inverter Inverter not operating (switched off) Battery OK Battery fault or battery is discharged Battery discharging or battery fus
CAUTION: ACTIVATION OF THE ON/OFF PUSHBUTTONS WHEN THE UPS IS NOT IN MAINTENANCE BYPASS MODE WILL INTERRUPT THE POWER SUPPLY TO THE CRITICAL LOAD. If, for security or emergency reasons, it is necessary to immediately disconnect the load from the UPS, press the two red ON/OFF pushbuttons simultaneously. In this case, make sure that the maintenance bypass switch (IA1) is in the “O” position (Normal=Off). 7.3 Description of the LCD Screen 7.3.
7.3.2 LCD Display Structure and Navigation The menu structure is shown in Figure 7–3, below. Navigation through the menu is accomplished by using the “ENTER” pushbutton to go to the menu level, or to activate an action, then using the “UP” or “DOWN” arrows to select a specific function within each menu category. The “RESET” pushbutton will immediately return to the highest screen. PRESS RESET, RETURNS TO TOP LEVEL LOAD PROTECTED • HH-MM-SS EVENT LOG LOAD TO INV. BATT. RUN TIME (MIN) 0.
7.3.3 Main Menu Screen DESCRIPTION • • • • • • LCD DISPLAY EVENT LOG Logging Control. A log of the last 64 events is stored in the Power Management Display. Menu Measurements allow monitoring voltages, power, frequencies, current, battery run time, and other information. Command Menu enables performance of “Load to Inverter”, “Load to Bypass”, and battery test functions. UPS Data Menu shows UPS serial number, date of manufacture, current time & date.
• Battery Voltage BATTERY VOLTAGE (V) +240 -240 • Battery Charger Current BATT. CHARGE CUR. (A) + 0.0 - 0.0 • Discharge Current DISCHARGE CURRENT (A) + 0.0 - 0.
7.3.7 UPS Data DESCRIPTION • LCD DISPLAY Information displayed is installed at the time of manufacture. UPS SERIAL NUMBER MDATE OF MANUFACTURE DD-MM-YY • Manufacturing Date • EPROM Version EPROM VERSION V-000 • Actual Date and Time (set by user under user set-up menu. DATE DD-MM-YY TIME HH-MM-SS 7.3.8 Set-Up User DESCRIPTION LCD DISPLAY • SET-UP DATE/TIME Set-up Date and Time (Press ENTER to access) DD-MM-YY • HH-MM-SS SET-UP BATT.
7.3.9 Set-Up Service DESCRIPTION • This menu is reserved for authorized service engineers. It is not to be accessed by End-Users. • Type in password.
7.4 O perating Modes 7.4.1 “ON LINE” Mode (INVERTER MODE) The ON-LINE Mode is the UPS Operating Mode in which the load is supplied through the RECTIFIER and INVERTER. LED indicators are illuminated when shown shaded: LINE 2 LED’s green when shown shaded BYPASS BATTERY LINE 1 INV. Using the control panel (see Figure 7–2) the UPS can easily be transferred to the ONLINE mode. The ON-LINE mode provides the highest degree of protection, especially in the event of a supply disturbance or failure.
inverter within 5 milliseconds. When utility power returns, the UPS will startup in NORMAL (inverter) mode. Operator intervention is required to reset to ECO mode. The battery charger remains active in the “Bypass-Mode”. The “Bypass-Mode” is recommended only if the loads can tolerate power interruptions of up to 5 ms, the transfer time from Bypass Mode to ON-LINE Mode.
7.4.4 Parallel Isolator (IA2) The UPS unit is provided with an output isolator switch (IA2) which, when opened, isolates the corresponding unit from the LOAD. Once IA2 is open, there is no power coming from the inverter. This switch should always be in the “I” (ON) position, except for servicing the UPS when in the maintenance bypass mode. Rotating this switch to the “O” (OFF) position while the inverter is supplying power to the load will dump the critical load.
UPS Operating Instructions 8 8.1 Operation The following procedures provide instruction for operating the UPS system. Refer to Chapters 6 and 7 of this manual for a description of the UPS controls and monitor panel functions. NOTE: Before starting the UPS, ensure all installation tasks are complete and authorized service personnel have performed a preliminary startup. The preliminary startup verifies all electrical interconnections to ensure the installation was successful and the UPS operates properly.
LED Indicator LINE 1 LINE 2 BYPASS INVERTER BATTERY Color Green Green Green OFF Flashing Green 6. If necessary, perform Command: LOAD TO INVERTER (see sections 7.3.2 and 7.3.6) On LCD Display, “LOAD PROTECTED” will appear and the LED-indicators will display as follows: LED Indicator LINE 1 LINE 2 BYPASS INVERTER BATTERY Color Green Green OFF Green Flashing Green 7. Close the external battery cabinet circuit breaker. 8.
12. Rotate the Maintenance Bypass Switch IA1 to the “O” (OFF) position. On the LCD Display, “MANUAL BYP. OPEN” will appear followed by “LOAD NOT PROTECTED”. 13. Using the Measurements menu (see sections 7.3.2 and 7.3.5) verify proper values for output powers, voltages, currents and frequencies. 14. Perform Load transfer to Inverter • Go to COMMANDS menu on UPS cabinet control panel and choose command “LOAD TO INVERTER” to transfer the load to inverter output. (see sections 7.3.2 and 7.3.
2. If the loads are all disconnected, press simultaneously the two ON/OFF buttons on the UPS control panel. On the LCD Display, “LOAD OFF, SUPPLY FAILURE” will appear and the LED-indicator will indicate as shown below: LED Indicator LINE 1 LINE 2 BYPASS INVERTER BATTERY Color Green OFF OFF OFF Flashing Green 3. Rotate the Parallel Isolator Switch (IA2) to the “O” (OFF) position. 4. Open battery cabinet breakers in external battery cabinets or racks. 5.
• Rotate the Maintenance Bypass Switch IA1 to “I” (ON) On LCD Display: “MANUAL BYP CLOSED” will appear and the LED indicators will indicate as shown below: LED Indicator LINE 1 LINE 2 BYPASS INVERTER BATTERY Color Green Green Green Red Green 2) Simultaneously press both ON/OFF pushbuttons on the UPS cabinet control panel.
This page left intentionally blank.
Responding to System Events 9 9.1 Alarms In the event of an alarm condition, the red LED-Indicator “Alarm” and the audible alarm will turn on. In this case proceed as follows: A. Silence the audible alarm by pressing the "Reset" button. B. Identify the cause of the alarm condition by means of the EVENT LOG in the MAIN menu. C. In case of alarm conditions, please contact the Global Service Center. D. Fault identification and suggested corrective action is given on the following pages. 9.
9.3 Fault Identification and Correction The major alarm conditions that will be encountered are shown in the following table: Alarm Condition Meaning Suggested Solution UPS FAULT There is a fault in the UPS and therefore normal operation cannot be guaranteed. Call the authorized service center for assistance MAINS FAILURE The utility power supply is outside its prescribed tolerance. The input power to UPS is too low or missing. If site power appears to be OK, check the input circuit breakers etc.
Communications 10 10.1 X – Slot Communication Modules This section describes the several types of X–Slot cards, which can be used with the Powerware 9335. X-Slot cards allow the UPS to communicate to a variety of environments and with different types of devices. The Powerware 9335 is compatible with any X–Slot card, including, but not limited to: • ConnectUPSTM SNMP/WEB Card – provides 10Base-T Ethernet connectivity for web-based remote monitoring in addition to SNMP capabilities.
Control Panel X–Slot location for insertion of X–Slot Cards JD8 SW2-9 SW1-1 X4 X3 X2 X1 JD2 JD1 IA1 IA2 Figure 10–1. X–Slot Location on Front of Powerware 9335 UPS Cabinet 10.2 Single-Port Serial Card To establish communications between the UPS and a computer, connect your computer to the UPS communication port using the supplied communication cable. When the communication cable is installed, power management software installed on your computer can exchange data with the UPS.
power environment. If a power emergency occurs, the software initiates the saving of all data and an orderly shutdown of the connected critical load. The cable pins are identified in Figure 10–2 and the pin functions are described in Table 10–1. 5 4 9 3 8 2 7 1 6 Figure 10–2.
This page left intentionally blank.
11 Options 11.1 Generator ON Facility The generator ON facility must use a normally open contact that closes to indicate that a generator is running and supplying input power to the UPS. When used, this facility disables the UPS static bypass and prevents the UPS from transferring the load into the generator power supply. The user may also elect prevention of battery charging while on generator input. Both or either of these features may be selected via the control panel. (See section 7.3.
This page left intentionally blank 11-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV A 071103
Maintaining the UPS System 12 12.1 General The components inside the UPS cabinet are secured to a sturdy metal frame. All repairable parts and assemblies are located for easy removal, and very little disassembly. This design allows authorized service personnel to perform routine maintenance and servicing quickly. You must schedule periodic performance checks of your UPS system to keep it running properly.
12.3 Performing Preventive Maintenance The UPS system requires very little preventive maintenance. However, the system should be inspected periodically to verity that the units are operating normally and that the batteries are in good condition. Perform the following checks DAILY: 1. Check the area surrounding the UPS system. Ensure the area is not cluttered, allowing free access to the unit. 2. Ensure the air intakes (vents on the bottom) and exhaust opening (on the top of the cabinet) are not blocked. 3.
13 Product Specifications 13.1 System Information The UPS systems are housed in freestanding cabinets with safety shields behind the front panels. The UPS systems are available in 50 or 60 Hz configurations with either 80 or 120 kVA output ratings. The following sections detail the input output, environmental and battery specifications for each model. 13.
13.3 UPS System Output DC Ripple UPS Output Capacity Output Voltage Regulation Output Voltage Harmonic Content Output Voltage Balance Output Voltage Phase Displacement Output Transients Frequency Regulation Synchronous to Bypass Frequency Slew Rate Overload Capacity Maximum Output Capability less than 1% voltage ripple 100% rated current at 0.8 power factor ±1.5% (10–100% load) Less than 1% Each phase may be loaded to 100% independently with voltage regulation within stated tolerance.
Appendix A – Customer Information A The information in this appendix will help you plan for and install your UPS system.
Table A. INPUT/OUTPUT Ratings & External Wiring Requirements for Powerware 9335 – 80 kVA Ratings Basic unit ratings at 0.8 lagging PF load AC INPUT A AC INPUT B DC INPUT C AC OUTPUT D AC Input to UPS Rectifier (0.95 min. PF) 3 phase, 1 neutral, 1 ground Minimum conductor size *Max. amps include full load current plus battery recharge current AC Input to UPS Bypass - Full Load Current 3 phase, 1 neutral, 1 ground Minimum conductor size DC Input from Ext.
Table B. INPUT/OUTPUT Ratings & External Wiring Requirements for Powerware 9335 – 120 kVA Ratings Basic unit ratings at 0.8 lagging PF load AC INPUT A AC INPUT B DC INPUT C AC OUTPUT D AC Input to UPS Rectifier (0.95 min.PF) 3 phase, 1 neutral, 1 ground Minimum conductor size *Max. amps include full load current plus battery recharge current AC Input to UPS Bypass - Full Load Current 3 phase, 1 neutral, 1 ground Minimum conductor size (number/phase) DC Input from Ext.
7. Terminals are UL rated at 90o C. Refer to Table C for power cable terminations and Table D for conduit requirements. Figure A–1 shows the location of power cable terminals inside the UPS. Table C.
11. External overcurrent protection is not provided by this product, but is required by codes. Refer to A and B for wiring requirements. If an output lockable disconnect is required, it is to be supplied by designated personnel. 12. Table E lists the maximum rating for input circuit breakers. 13. Battery voltage is computed at 2 volts per cell as defined by Article 480 of the NEC. Rated battery current is computed at the computed voltage. Table E.
Terminal X1 X2 X3 X4 JD-1-1 JD-1-2 JD-1-3 JD-1-4 JD-1-5 JD-1-6 JD-1-7 JD-1-8 JD-1-9 JD-2-1 JD-2-2 JD-2-3 JD-2-4 JD-2-5 JD-2-6 JD-2-7 JD-2-8 JD-2-9 JD-2-10 JD-2-11 JD-2-12 JD-2-13 JD-2-14 JD-2-15 JD-2-16 JD-2-17 JD-2-18 JD-2-19 JD-2-20 JD-2-21 JD-2-22 JD-2-23 JD-2-24 JD-2-25 A-6 Table G.
Table H.
Table I. Definition of pins on JD1 and interface cable connections to 9 or 25 pin connectors. 1 1 2 2 3 3 5 5 . . . . . . 9 9 JD1 connector at UPS DB-9 connector to computer 1 1 2 2 3 3 5 . . . 9 . . . 7 . . . . 25 JD1 connector at UPS DB-25 connector to computer 1. The UPS equipment operating environment must meet the size and weight requirements shown in Table J, according to your UPS system configuration. 2.
Powerware Model 9335 – 80 kVA 9335 – 120 kVA Table J. Equipment Weight Weight Kg (lbs.) Shipping Installed 360 (792) 333 (733) 367 (807) 340 (748) Point Loading 4 at 83 (183) 4 at 85 (187) 5. The clearances required around the UPS system are shown in Table K. Table K. System Clearances From Front of Cabinet 36 inches working space From Back of Cabinet 30 inches working space From Right or Left side of Cabinet ~0 inches clearance 6.
ELEMENTS: IA1 IA2 JD1 JD2 JD8 SW1-1 SW2-9 X1 X2 X3 X4 Control Panel JD8 SW2-9 SW1-1 X4 X3 X2 X1 Maintenance Bypass Parallel Isolator Smart Port- RS232 (SUB-D9P/F) Dry Port-volt-free relays (SUB-D25/F) Parallel Port Single/Parallel Switch System Configuration Switches Emergency Power OFF (EPO) Generator ON Battery Temperature Battery Breaker control JD2 JD1 SW1-1 IA1 IA2 HIGH Single Module LOW Parallel Module SW2-9 1A 1B 1C 1N 2A 2B 2C 2N 3A 3B 3C 3N Utility Input (Single Feed) Bypass Input (
F17 F16 F6 F7 F10 F11 F8 F12 F9 F13 F4 Fuses F14 F15 F5 80 kVA F1a,b,c 600Vac/125A F3a,b 500Vdc/50A F4,5 600Vac/200A F6,7,8,9 600Vac/125A F10,11,12 13,14,15 600Vac/160A F16,17 660Vac/63A F18a,b,c F19a,b,c 600Vac/16A UPS Type 80 kVA F1a,b,c F19a,b,c F18a,b,c F3a,b IA1 Mains Input Bypass Input LISTED UNINTERRUPTIBLE POWER SUPPLY 1ZD3 IA2 Maintenance Bypass Parallel Isolator Output Battery 1A 1B 1C 1N 2A 2B 2C 2N 3A 3B 3C 3N + 0 N -- USE 75°C COPPER CONDUCTORS ONLY R
STANDARD VERSION (DUAL INPUT FEED CONNECTION) SHOWN A Fuse A Fuse B Cable A Cable B K4 F1 Fuse C C B Rectifier Inverter Cable C Static Switch IA2 9335 Maintenance Bypass IA1 Cable D D Fuse D Load Figure A–3. Powerware 9335 Oneline Drawing PE GRND Figure A–4. Power Terminals on Powerware 9335 1A, 1B, 1C, 1N 2A, 2B, 2C, 2N 3A, 3B, 3C, 3N RECTIFIER INPUT BYPASS INPUT OUTPUT TO LOAD Figure A–4.
Figure A-5.
Figure A-6.
700 mm. (27.6 inches) 1800 mm. (70.9 inches) Removable Conduit Landing Plate Figure A–7.
750 mm. (29.6 inches) 700 mm. (27.6 inches) 1800 mm. (70.9 Figure A–8.
LIMITED FACTORY WARRANTY FOR THREE-PHASE POWERWARE PRODUCTS Subject to the conditions herein, Invensys Powerware (Powerware ®) warrants solely, to the original end-user, the electronics (the “Unit”), and Powerware built battery cabinets, against defects in material and workmanship for the warranty period of 12 months, from the date of equipment start up, or 18 months from date of shipment, whichever occurs first.
This page left intentionally blank W-2 Powerware 9335 (80 kVA – 120 kVA) Installation and Operation 164201396 REV A.