® Powerware FERRUPS FE/QFE UPS Installation Guide 500 VA–18 kVA, 50 and 60 Hz
® Powerware FERRUPS FE/QFE UPS Installation Guide 500 VA–18 kVA, 50 and 60 Hz www.powerware.
Class A EMC Statements FCC Part 15 NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
TABLE OF CONTENTS 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Plug-Receptacle Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Hardwired Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1 2 Safety Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents ii Powerware® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.
CHAPTER 1 INTRODUCTION The Powerware9 FERRUPS uninterruptible power system (UPS) is available in plug-receptacle or hardwired models. The plug-receptacle models have an input plug and receptacles on the rear panel. The hardwired models have terminal strips that an electrician has to wire to AC input. See the following sections for steps on how to use this manual for your UPS installation.
Introduction : If you purchased an external battery cabinet, see Chapter 7, “Battery Cabinet Installation” for wiring connections. : Complete the phase check as described in Chapter 8, “Phase Check.” : Continue to the startup section in the Powerware FERRUPS FE/QFE UPS (500 VA–18kVA) User’s Guide. 2 Powerware® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.
CHAPTER 2 SAFETY WARNINGS Read the following precautions before you install the UPS. IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS. This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries. Please read all instructions before operating the equipment and save this manual for future reference. DANGER This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY.
Safety Warnings CAUTION : Batteries can present a risk of electrical shock or burn from high short-circuit current. Observe proper precautions. Servicing should be performed by qualified service personnel knowledgeable of batteries and required precautions. Keep unauthorized personnel away from batteries. : Proper disposal of batteries is required. Refer to your local codes for disposal requirements. : Never dispose of batteries in a fire. Batteries may explode when exposed to flame.
Safety Warnings ADVARSEL : Batterier kan udgøre en fare for elektrisk stød eller forbrændinger forårsaget af høj kortslutningsspænding. De korrekte forholdsregler bør overholdes. : Korrekt bortskaffelse af batterier er påkrævet. Overhold gældende lokale regler for bortskaffelsesprocedurer. : Skaf dig aldrig af med batterierne ved at brænde dem. Batterierne kan eksplodere ved åben ild.
Safety Warnings OPGELET : Batterijen kunnen gevaar voor elektrische schok of brandwonden veroorzaken als gevolg van un hoge kortsluitstroom. Volg de desbetreffende aanwijzingen op. : De batterijen moeten op de juiste wijze worden opgeruimd. Raadpleeg hiervoor uw plaatselijke voorschriften. : Nooit batterijen in het vuur gooien. De batterijen kunnen ontploffen.
Safety Warnings VARO : Akusto saattaa aiheuttaa sähköiskun tai syttyä tuleen, jos akusto kytketään oikosulkuun. Noudata asianmukaisia ohjeita. : Akusto täytyy hävittää säädösten mukaisella tavalla. Noudata paikallisia määräyksiä. : Älä koskaan heitä akkuja tuleen. Ne voivat räjähtää. Consignes de sécurité CONSIGNES DE SÉCURITÉ IMPORTANTES CONSERVER CES INSTRUCTIONS CE MANUEL CONTIENT DES CONSIGNES DE SÉCURITÉ IMPORTANTES DANGER! Cet onduleur contient des TENSIONS MORTELLES.
Safety Warnings ATTENTION! : Les batteries peuvent présenter un risque de décharge électrique ou de brûlure par des courts-circuits de haute intensité. Prendre les précautions nécessaires. : Une mise au rebut réglementaire des batteries est obligatoire. Consulter les règlements en vigueur dans votre localité. : Ne jamais jeter les batteries au feu. L’exposition aux flammes risque de les faire exploser. Sicherheitswarnungen WICHTIGE SICHERHEITSANWEISUNGEN AUFBEWAHREN.
Safety Warnings VORSICHT! : Batterien können aufgrund des hohen Kurzschlußstroms Elektroschocks oder Verbrennungen verursachen. Die entsprechenden Vorsichtsmaßnahmen sind unbedingt zu beachten. : Die Batterien müssen ordnungsgemäß entsorgt werden. Hierbei sind die örtlichen Bestimmungen zu beachten. : Batterien niemals verbrennen, da sie explodieren können.
Safety Warnings : Ãéá íá óõìöùíåß ìå ôá äéåèíÞ ðñüôõðá êáé ôïõò êáíïíéóìïýò êáëùäßùóçò, ôï ñåýìá äéáññïÞò ðñïò ôç ãç ïëüêëçñïõ ôïõ åîïðëéóìïý, ðïõ åßíáé óõíäåäåìÝíïò ìå ôçí Ýîïäï ôïõ óõãêåêñéìÝíïõ UPS, äåí ðñÝðåé íá åßíáé ìåãáëýôåñï áðü 1,5 mA. : ÐÑÏÓÏ×Ç Ïé óõóóùñåõôÝò ìðïñåß íá ðñïêáëÝóïõí çëåêôñïðëçîßá Þ Ýãêáõìá áðü õøçëü ñåýìá âñá÷õêõêëþìáôïò. ËáìâÜíåôå ôéò êáôÜëëçëåò ðñïöõëÜîåéò. : Áðáéôåßôáé óùóôÞ äéÜèåóç ôùí óõóóùñåõôþí. Äåßôå ôïõò ôïðéêïýò êáíïíéóìïýò ðïõ áöïñïýí ôéò áðáéôÞóåéò äéÜèåóÞò ôïõò.
Safety Warnings : Per ridurre il rischio di incendio o di scossa elettrica, installare il gruppo statico di continuità in un ambiente interno a temperatura ed umidità controllata, privo di agenti contaminanti conduttivi. La temperatura ambiente non deve superare i 40°C. Non utilizzare l’unità in prossimità di acqua o in presenza di umidità eccessiva (95% max).
Safety Warnings : Alt utstyr som er forbundet med utgangen av denne UPS’en må ikke ha en sterkere total lekkasjestrøm enn 1,5 milliampere for å være i overensstemmelse med internasjonale standarder og forkablingsbestemmelser. FORSIKTIG : Batterier kan forårsake elektriske støt eller forbrenning på grunn av høy kortslutningsstrøm. Følg instruksene. : Batterier må fjernes på korrekt måte. Se lokale forskrifter vedrørende krav om fjerning av batterier.
Safety Warnings PERIGO : As baterias podem apresentar o risco de choque elétrico, ou queimaduras provenientes de alta corrente de curto-circuito. Observe as instruções adequadas. : Siga as instruções apropriadas ao desfazer-se das baterias. Consulte os códigos do local para maiores informações sobre os regulamentos de descarte de produtos. : Nunca jogue as baterias no fogo, porque há risco de explosão.
Safety Warnings : Для обеспечения соблюдения требований международных стандартов и требований к разводке электрических цепей, суммарная величина тока утечки на землю всего оборудования, подключенного к выходу ИБП, не должна превышать 1,5 миллиампера. ОСТОРОЖНО : Аккумуляторы могут вызвать опасность поражения электрическим током или ожога от тока короткого замыкания. Соблюдайте соответствующие меры предосторожности. : Необходимо соблюдать правила утилизации аккумуляторов.
Safety Warnings : Para reducir el riesgo de incendio o de choque eléctrico, instale este SIE en un lugar cubierto, con temperatura y humedad controladas, libre de contaminantes conductores. La temperatura ambiente no debe exceder los 40°C. No trabaje cerca del agua o con humedad excesiva (95% máximo).
Safety Warnings : Minska risken för brand eller elektriska stötar genom att installera denna UPS-enhet inomhus, där temperatur och luftfuktighet är kontrollerade och där inga ledande föroreningar förekommer. Omgivande temperatur får ej överstiga 40°C. Använd inte utrustningen nära vatten eller vid hög luftfuktighet (max 95 %).
CHAPTER 3 SETUP This chapter explains the requirements for setting up the UPS: : : : : : UPS, battery cabinet, and bypass switch dimensions Equipment clearances Location requirements Moving the UPS and batteries Storage and operating environment Dimensions Table 1. FERRUPS FE/QFE 500 VA–3.1 kVA Dimensions Dimensions (See Figure 1) Height (A) Width (B) Depth (C) 122 (30.5 cm) 102 (25.5 cm) 21.252 (54.0 cm) 1.15 kVA and 1.4 kVA 15.12 (38.5 cm) 15.22 (39.0 cm) 20.22 (51.5 cm) 1.8 kVA, 2.
Setup Table 2. FERRUPS FE/QFE 4.3–18 kVA Dimensions Dimensions (See Figure 1) Height (D) Width (E) UPS Model Depth without Internal Bypass (F) Depth with Internal Bypass Switch (F) 4.3 kVA and 5.3 kVA 29.52 (75.0 cm) 15.52 (39.5 cm) 252 (63.5 cm) 332 (84.0 cm) 7 kVA, 10 kVA, 12.5 kVA, and 18 kVA 36.52 (93.0 cm) 322 (81.5 cm) 402 (102.0 cm) 192 (48.5 cm) Table 3. Battery Cabinet Dimensions Dimensions (See Figure 2) Height Width Depth ASY-0468 12.252 (31.5 cm) 15.752 (40.0 cm) 28.52 (72.
Setup B A E C E B A C D D BPE-01 BPE-02, 04, and 05 Figure 3. Bypass Switch Dimensions Equipment Clearances All cabinet sizes require the following clearances to allow for servicing and adequate ventilation: Table 5. Clearances for the UPS and Battery Cabinets Dimensions (see Figure 4) Sides (G) Front (H) Top (I) Back (J) 362 (91.5 cm) 362 (91.5 cm) 122 (30.5 cm) 42 (10.0 cm) NOTE A minimum clearance of 42 (10 cm) is required on the sides, front, and back and 122 (30.
Setup I I J G H G H Figure 4. Installation and Service Clearances Location Requirements Install the FERRUPS as close as possible to the equipment to be protected. If the UPS is more than 25 ft (7.6m) from the equipment, transient noise can reappear in the electrical distribution system. The UPS should be well ventilated and away from direct sunlight or other heat source. The environment can affect the reliability and performance of both the UPS and the batteries.
Setup Storage and Operating Environment Storage Temperature: Store the batteries (in the UPS or external battery cabinet) at -20° to +40°C (-4° to +104°F). Batteries will have a longer shelf life if they are kept below 25°C (77°F). The UPS or external battery cabinet without batteries may be stored at -20° to +60°C (-4° to +140°F). Ventilation: The air around the UPS must be clean and free of dust, corrosive chemicals, and other contaminants.
Setup 22 Powerware® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.
CHAPTER 4 ELECTRICAL INSTALLATION NOTE If you have a plug-receptacle unit, continue to “Battery Cabinet Installation” on page 53 to install optional battery cabinets or to the startup section in the Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide. WARNING Only qualified service personnel (such as a licensed electrician) should perform the hardwired installation. Risk of electrical shock. Before installing your UPS, complete the following information: 1.
Electrical Installation Bypass Switches Bypass switches are available in two types: external (a separate cabinet that is wall-mounted) or internal (attached to the back of the UPS). The bypass switch has three positions as described in Table 6. Table 6. Bypass Switch Positions Switch Position Description LINE Connects the load directly to AC input power and disconnects UPS output. AC input power is still connected to the UPS input. OFF Disconnects the load from the UPS output power and AC input power.
Electrical Installation Table 7 and Table 8 show the bypass switch models available for the FERRUPS UPS. Table 7. External Bypass Switch Specifications Model Number Ratings (UL/CSA) Continuous Ratings (TÜV) Continuous Weight BPE-01 30A/300 Vac 30A/300 Vac 8.25 lb/3.7 kg BPE-02 40A/300 Vac 50A/300 Vac 19.75 lb/9 kg BPE-04 80A/300 Vac 80A/300 Vac 30 lb/13.6 kg BPE-05 104A/300 Vac 120A/300 Vac 32.75 lb/14.9 kg Table 8.
Electrical Installation External Bypass Switch Building Service Panel AC Disconnect Line Bypass Switch Off Off Load Distribution Panel UPS On Connect to (DC) External Batteries UPS Figure 5. Typical Hardwired Installation with External Bypass Switch 26 Powerware® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.
Electrical Installation Figure 6 shows a UPS with a separate battery cabinet and an internal bypass switch. Internal bypass switches are available only for FE/QFE 4.3–18 kVA models. Continue to Chapter 6, “Internal Bypass Switch Installation” on page 45 for electrical connections. Back of UPS Internal Bypass Switch Building Service Panel AC Disconnect Bypass Switch Line Off Off Load Distribution Panel UPS On Connect to (DC) if there are External Batteries Figure 6.
Electrical Installation 28 Powerware® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.
CHAPTER 5 EXTERNAL BYPASS SWITCH INSTALLATION WARNING Only qualified service personnel (such as a licensed electrician) should perform the hardwired installation. Risk of electrical shock. CAUTION Before you install the bypass switch, verify that the bypass switch and the AC disconnect switch are in the OFF position. 1. Identify the installation wiring diagram that applies to your FERRUPS (see Table 9). Table 9. External Bypass Switch Wiring Diagrams Model (Frequency) FE 500 VA–3.
External Bypass Switch Installation Model (Frequency) FE 4.3–18 kVA (60 Hz) QFE 4.3–18 kVA (50 Hz) UPS Input Voltage UPS Output Voltage Bypass Switch Type Wiring Diagram 120 (4.
External Bypass Switch Installation 2. Review the installation wiring diagram and applicable notes to find the proper circuit breaker size for your installation. In the US, see Table 10 to size the wire. In other areas, use 75°C copper wire and size according to the local code. Table 10. Recommended Wire Sizes Input Circuit Breaker Size 75°C Copper Wire Size 15A, 20A 12 AWG (3.3 mm2) 25A, 30A 10 AWG (5.3 mm2) 35A, 40A, 45A, 50A 8 AWG (8.4 mm2) 60A 6 AWG (13.3 mm2) 70A, 80A 4 AWG (21.
External Bypass Switch Installation CAUTION To prevent electrical shock or damage to your equipment, verify that the UPS ON/OFF switch is in the OFF position before you remove the UPS front cover panel. The circuit breaker or disconnect switch must be turned off at the AC input service panel. 5. Remove the UPS front cover panel according to the UPS model: FE or QFE 500 VA–3.1 kVA : Remove the #1 Phillips grounding screw on top of the UPS.
External Bypass Switch Installation 8. Find the terminal strip inside the bypass switch. Using the label on the back of the switch’s lower front cover panel, wire the terminal strip and tighten all connections securely. Use copper wire and the appropriate wire size for the current. See Figure 7 for sample terminal strip labels. BPE-01 BPE-02, BPE-04, and BPE-05 Figure 7. External Bypass Switch Terminal Strip Labels 9.
External Bypass Switch Installation 10. If your UPS does not have an external battery cabinet(s), continue to “Phase Check” on page 65. If your UPS has an external battery cabinet(s), continue to “Battery Cabinet Installation” on page 53. Installation Wiring Diagrams for External Bypass Switches The following notes are referenced in the external bypass switch wiring diagrams (Figure 8 through Figure 15). To determine which diagram is correct for your site, see Table 9 on page 29.
External Bypass Switch Installation NOTE 8 External UPS batteries are optional. The battery cable must not be disconnected if a load is applied. Shut off the UPS before disconnecting the cable. See “Battery Cabinet Installation” on page 53 for external battery cabinet installation. NOTE 9 UPS output circuits must be installed in dedicated conduit and not shared with other electrical circuits. NOTE 10 The load fuse or circuit breaker should be sized to match the load current requirements.
External Bypass Switch Installation QFE: 50 Hz 120 Vac Input and Output OR FE: 60 Hz 120 Vac Input and Output OR FE 1.15–3.1 kVA only: 60 Hz 220 Vac Input and Output (with single-voltage output) For 220 Vac, use only a BBM switch. Figure 8. FE or QFE 500 VA–3.1 kVA UPS with External Bypass Switch Table 11. Minimum Recommended Circuit Breakers for 60 Hz 120 Vac Charger 500 VA, 700 VA, and 850 VA 1.15 kVA 1.4 kVA 1.8 kVA 2.1 kVA 3.
External Bypass Switch Installation 60 Hz 208 Vac or 240 Vac Input - 120/208 Vac or 120/240 Vac Output For 208 Vac, use only a BBM switch. Figure 9. FE 500 VA–3.1 kVA UPS with External Bypass Switch Table 14. Minimum Recommended Circuit Breakers for 208 Vac or 240 Vac 208 Vac Charger 500 VA –1.4 kVA 240 Vac 1.8 kVA 2.1 kVA 3.1 kVA 500 VA –1.4 kVA 1.8 kVA 2.1 kVA 3.
External Bypass Switch Installation 60 Hz 208 or 480 Source/240 Vac Input - 120/240 Vac Output (with Transformer) Figure 10. FE 500 VA–3.1 kVA UPS with External Bypass Switch Table 15. Minimum Recommended Circuit Breakers for 240 Vac Charger 500 VA–1.4 kVA 1.8 kVA 2.1 kVA 3.1 kVA Standard 15 15 15 15 15A 15 20 20 25 38 Powerware® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.
External Bypass Switch Installation 50 Hz 220, 230, or 240 Vac Input and Output Figure 11. QFE 500 VA–3.1 kVA UPS with External Bypass Switch Table 16. Input Current - Size Overcurrent Protection According To Local Code Voltage Charger 500 VA 700 VA 850 VA 1.15 kVA 1.4 kVA 1.8 kVA 2.1 kVA 3.1 kVA 220 Vac Standard 2.6A 3.9A 4.4A 4.9A 5.7A 7.9A 8.2A 13A 15A 4.7A 6.0A 6.5A 7.0A 7.8A 14A 15A 19A Standard 2.5A 3.8A 4.2A 4.6A 5.4A 7.5A 7.8A 12A 15A 4.6A 5.9A 6.3A 6.
External Bypass Switch Installation 60 Hz 120 Vac Input - 120 Vac Output Figure 12. FE 4.3–7 kVA UPS with External Bypass Switch Table 17. Minimum Recommended Circuit Breakers for 120 Vac Charger 4.3 kVA 5.3 kVA 7 kVA Standard 40 50 70 10A 45 60 70 20A 50 60 70 40 Powerware® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.
External Bypass Switch Installation 60 Hz 208 Vac or 240 Vac Input - 120/208 Vac or 120/240 Vac Output For 208 Vac, use only a BBM switch. Figure 13. FE 4.3–18 kVA UPS with External Bypass Switch Table 18. Minimum Recommended Circuit Breakers for 208 Vac or 240 Vac 208 Vac 240 Vac Charger 4.3 kVA 5.3 kVA 7 kVA 10 kVA 12.5 kVA 18 kVA 4.3 kVA 5.3 kVA 7 kVA 10 kVA 12.
External Bypass Switch Installation 60 Hz 208 or 480 Source/240 Vac Input - 120/240 Vac Output (with Transformer) Figure 14. FE 4.3–18 kVA UPS with External Bypass Switch Table 19. Minimum Recommended Circuit Breakers for 240 Vac Charger 4.3 kVA 5.3 kVA 7 kVA 10 kVA 12.5 kVA 18 kVA Standard 20 25 35 50 70 100 10A 20 30 35 60 70 100 20A 20 35 35 60 80 110 42 Powerware® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.
External Bypass Switch Installation QFE: 50 Hz 220, 230, or 240 Vac Input and Output OR FE: 60 Hz 220 Vac Input and Output For FE 60 Hz 220 Vac, use only a BBM switch. Figure 15. FE or QFE 4.3–18 kVA UPS with External Bypass Switch Table 20. Input Current - Size Overcurrent Protection According To Local Code Voltage Charger 4.3 kVA 5.3 kVA 7 kVA 10 kVA 12.
External Bypass Switch Installation 44 Powerware® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.
CHAPTER 6 INTERNAL BYPASS SWITCH INSTALLATION WARNING Only qualified service personnel (such as a licensed electrician) should perform the hardwired installation. Risk of electrical shock. CAUTION Before you install the bypass switch, verify that the bypass switch and the AC disconnect switch are in the OFF position. 1. Identify the installation wiring diagram that applies to your FERRUPS (see Table 21). Table 21. Internal Bypass Switch Wiring Diagrams Model (Frequency) FE 4.3–18 kVA (60 Hz) QFE 4.
Internal Bypass Switch Installation 2. Review the installation wiring diagram and applicable notes to find the proper circuit breaker size for your installation. In the U.S., see Table 22 to size the wire. In other areas, use 75°C copper wire and size according to the local code. Table 22. Recommended Wire Sizes Input Circuit Breaker Size 75°C Copper Wire Size 15A, 20A 12 AWG (3.3 mm2) 25A, 30A 10 AWG (5.3 mm2) 35A, 40A, 45A, 50A 8 AWG (8.4 mm2) 60A 6 AWG (13.3 mm2) 70A, 80A 4 AWG (21.
Internal Bypass Switch Installation CAUTION To prevent electrical shock or damage to your equipment, verify that the AC input is OFF at the service panel and the bypass and AC disconnect switches are in the OFF position before you connect any wires to the bypass switch terminal strip. 5. Find the terminal strip inside the bypass switch. Using the label on the back of the switch’s lower front cover panel, wire the terminal strip and tighten all connections securely.
Internal Bypass Switch Installation Installation Wiring Diagrams for Internal Bypass Switches The following notes are referenced in the internal bypass switch wiring diagrams (Figure 17 through Figure 20). To determine which diagram is correct for your site, see Table 21 on page 45. NOTE 1 The customer must provide input overcurrent protection as stated in NEC Section 240-21 or local codes. Size the protection device according to local code requirements.
Internal Bypass Switch Installation NOTE 10 The load fuse or circuit breaker should be sized to match the load current requirements. NOTE 11 For 208 Vac, use a step-up transformer For 480 Vac, use a step-down transformer. Use an isolation transformer with a 120/240 grounded center-tapped neutral output. Do not use a buck/boost transformer. 60 Hz 120 Vac Input - 120 Vac Output Figure 17. FE 4.3–7 kVA UPS with Internal Bypass Switch Table 23. Minimum Recommended Circuit Breakers for 120 Vac Charger 4.
Internal Bypass Switch Installation 60 Hz 208 Vac or 240 Vac Input - 120/208 Vac or 120/240 Vac Output For 208 Vac, use only a BBM switch. Figure 18. FE 4.3–18 kVA UPS with Internal Bypass Switch Table 24. Minimum Recommended Circuit Breakers for 208 Vac or 240 Vac 208 Vac 240 Vac Charger 4.3 kVA 5.3 kVA 7 kVA 10 kVA 12.5 kVA 18 kVA 4.3 kVA 5.3 kVA 7 kVA 10 kVA 12.
Internal Bypass Switch Installation 60 Hz 208 or 480 Source/240 Vac Input - 120/240 Vac Output (with Transformer) Figure 19. FE 4.3–18 kVA UPS with Internal Bypass Switch Table 25. Minimum Recommended Circuit Breakers for 240 Vac Charger 4.3 kVA 5.3 kVA 7 kVA 10 kVA 12.5 kVA 18 kVA Standard 20 25 35 50 70 100 10A 20 30 35 60 70 100 20A 25 35 35 60 80 110 Powerware® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.
Internal Bypass Switch Installation QFE: 50 Hz 220, 230, or 240 Vac Input and Output FE: 60 Hz 220 Vac Input and Output For FE 60 Hz 220 Vac, use only a BBM switch. Figure 20. FE or QFE 4.3–18 kVA UPS with Internal Bypass Switch Table 26. Input Current - Size Overcurrent Protection According To Local Code Voltage Charger 4.3 kVA 5.3 kVA 7 kVA 10 kVA 12.
CHAPTER 7 BATTERY CABINET INSTALLATION NOTE If you have an optional Floor Saver battery cabinet, see the Floor Saver instructions that came with your FERRUPS UPS. WARNING Only qualified service personnel (such as a licensed electrician) should perform the electrical installation. Risk of electrical shock. CAUTION Full voltage and current are always present at the battery terminals. The batteries used in this system can produce dangerous voltages, extremely high currents and a risk of electric shock.
Battery Cabinet Installation : Align the cables on the battery terminals so that the cable lug will not contact any part of the cabinet even if the battery is moved. Keep the cable away from any sharp metal edges. : Install the battery cables so they cannot be pinched by the battery cabinet or UPS doors. : Make sure the fuse is positioned so that it will not contact any cabinet parts or other battery posts if the batteries should move.
Battery Cabinet Installation Table 27. Nominal DC Battery Voltage Models Nominal Battery Voltage QFE 500 VA, 700 VA, 850 VA, 1.15 kVA, and 1.4 kVA 12 Vdc FE 500 VA, 700 VA, and 850 VA 24 Vdc QFE 1.8 kVA, 2.1 kVA, 3.1 kVA, 4.3 kVA, 5.3 kVA, and 7 kVA FE 1.15 kVA, 1.4 kVA, 1.8 kVA, 2.1 kVA, 3.1 kVA, 4.3 kVA, 5.3 kVA, and 7 kVA 48 Vdc FE and QFE 10 kVA, 12.5 kVA, and 18 kVA 120 Vdc The battery cable or wire used is #1 AWG (42.
Battery Cabinet Installation Installing and Connecting the Batteries 1. Use the battery installation diagram that came with your UPS batteries and cabinet as you follow the steps below. 2. Place the battery cabinet or rack as close as possible to the FERRUPS UPS. If the batteries will be further from the unit than the standard cables allow, contact your service representative or your local distributor for assistance.
Battery Cabinet Installation 4. The battery cabinet ground (or earth) must be connected to the UPS chassis ground (or earth). You must make a good connection to the battery cabinet chassis ground (or earth). If the battery cabinet has a terminal strip, you can make the ground connection at the terminal strip ground (or earth) lug inside the cabinet. If not, you can make the ground connection at one of the screws on the battery cabinet; to ensure a good connection, remove the paint under the cabinet screw.
Battery Cabinet Installation 5. Arrange the batteries in the cabinet or rack. If optional straps are included, install the straps as shown in the battery installation diagram that was packed with your batteries. Arrange the batteries so there is as much air flow as possible around the batteries and so the batteries can be cooled as much as possible. Some battery cabinets have cooling slots cut in the shelves to increase air flow. Arrange the batteries so these slots are not blocked.
Battery Cabinet Installation NOTE If you have an external DC disconnect switch between the UPS and batteries, see the instructions that came with your disconnect switch. 8. Clean the cable and battery post (terminal) before you make the battery connection. Apply a thin coating of high-temperature conductive grease on the post and cable terminals to slow corrosion. If you use a nonconductive grease like petroleum jelly, do not apply any grease before you make the connections.
Battery Cabinet Installation Square: Torque to Modified Square: Torque 17 in lb or 1.9 Nm. (BAT-0058) to 35 in lb or 3.9 Nm. (BAT-0065) Screw Posts: Torque to 85 in lb or 9.6 Nm. (BAT-0071) Figure 23. Battery Terminal Types Connect the battery cables between batteries as shown in the battery installation diagram. Do not connect the cables between battery strings or between the UPS and the batteries yet. If you are only using one string of batteries, go to step 11. 9.
Battery Cabinet Installation : If your battery cabinet has a DC switch on the front, the positive and negative cables connect to the terminal strip in the back of the battery cabinet. First, find the positive (+) cable, and strip 0.52 (1.3 cm) of insulation from the end. Insert the cable into the positive (+) battery cabinet terminal. Next, strip 0.52 (1.3 cm) of insulation from the end of the negative (–) cable, and connect that cable to the negative (–) terminal in the battery cabinet.
Battery Cabinet Installation NOTE If you have an external DC disconnect switch, see the instructions that came with your disconnect switch. Now, turn the DC ON/OFF switch on the battery cabinet(s) to the ON position. Leave the UPS DC switch in the OFF position. 12. Use the meter to check for proper nominal DC voltage at the UPS end of the cable. Make sure the polarity agrees with the markings on the UPS battery terminals. Table 29.
Battery Cabinet Installation Replacing the Batteries CAUTION Only qualified service personnel (such as a licensed electrician) should perform the battery installation. Risk of electrical shock. Consider all warnings, cautions, and notes before replacing batteries. WARNING : Batteries can present a risk of electrical shock or burn from high short-circuit current.
Battery Cabinet Installation 3. Handle used batteries with care! Assume that old batteries are fully charged. Use the same precautions you would use when handling a new battery. Do not short battery terminals or the battery string with a cable or tool when you disconnect the batteries! See “Recycling the Used Battery” on page 64 for proper disposal. Recycling the Used Battery Contact your local recycling or hazardous waste center for information on proper disposal of the used battery.
CHAPTER 8 PHASE CHECK After all hardwired connections are complete (including external battery cabinets, if applicable), complete the phase check using the following steps. You will need an AC voltmeter for the phase check. CAUTION Before operating the bypass switch, use the following procedure to check the wiring for correct installation. To prevent damage to the load, turn off the main circuit breaker in the load service panel or verify that the load cannot receive power from the UPS. 1.
Phase Check 10–18 kVA: If you have an external battery cabinet(s) with a DC switch, turn the switch to the ON position. 6. Turn the UPS ON/OFF switch to the ON position. The switch is located on the back of the 500 VA–3.1 kVA models and on the front of the 4.3–18 kVA models. The load should still be disconnected at this time. After a short startup test, the READY indicator blinks for a few seconds and then remains illuminated. The UPS is ready to supply output power. 7.
Phase Check External Bypass Switch BPE-01 AC from UPS Output Measurement 5 to 6 Vac AC Line Input 8 to 9 Measurement Vac BPE-02, BPE-04, or BPE-05 AC from UPS Output Measurement AC Line Input Measurement 7 to 8* Vac 11 to 12 Vac 6 to 7 Vac 10 to 11 Vac 6 to 8* Vac 10 to 12 Vac *60 Hz, 208 or 240V only. 9. If the bypass switch is a Break-Before-Make type, skip this step and proceed to Step 10.
Phase Check 10. Measure the AC voltage between the following points on the terminal strip. This reading must be no more than 1 Vac; if it is, call your service representative. Internal Bypass Switch N (AC to UPS Load) to N (AC Line Input) Vac External Bypass Switch (BPE-01) 5 to 8 Vac External Bypass Switch (BPE-02, BPE-04, or BPE-05) 6 to 10* Vac 8 to 12** Vac *60 Hz, 208 or 240V only. **60 Hz, 120V or 50 Hz, 220/230/240V. 11. Turn the bypass switch to the LINE position.
Phase Check 16. Turn off the DC switch, if applicable, according to your UPS model: 500 VA–3.1 kVA: If you have an external battery cabinet(s) with a DC switch, turn the switch to the OFF position. 4.3–7 kVA: If you have an external battery cabinet(s) with a DC switch, turn the switch to the OFF position. If you do not have an external battery cabinet(s): unlock the UPS front cover panel using the FERRUPS key and remove the front cover panel. Locate the DC switch behind the front cover panel.
Phase Check 70 Powerware® FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.